DOC. MIE11110 Rev. 5
Page 84 of 110
5. Same LTC as above; fault on this selection.
1.3.4 PT tests: PT ratio test
•
Connect low V to the transformer HV side phase 1 and 2.
•
Adjust the voltage of V1 to 100 V.
•
Connect the measuring input Ext V (the 600 V or the 10 V
input, as a function of the transformer ratio) between one
phase and ground. You will find that two outputs have half