One transformer is Dy1 and the other is Dy11
In this case there are already 60° phase shift between phase R
local end and the phase R of the remote end. Supposing you
have connected the T1000 PLUS to phase R in the remote end,
you have three possibilities on the local end:
If you measure something like 200 or 346 A, it means the two
T1000 PLUS are connected to a different phase reference. As
you may see, in this condition Phase B of one end correspond
to the phase R + 180° of the other end.
Switch SWT3 to the next position until you get the proper
values.
1.16.3 T1000 PLUS setup for End to End test
T1000 PLUS is
connected to
You may
measure
approximately
1
phase B
0 or 400 A
2
phase R
200 or 346 A (200
x 1.732)
3
phase Y
200 or 346 A (200
x 1.732)
I
R local
I
B local
I
R Remote
I
Y Remote
I
B Remote
I
Y local