DOC. MIE91093 Rev. 1.34
Page 127 of 145
For the purpose of quickly identifying the phase reference, the
switching tool SWT3, provided as an option to the T1000
PLUS, will allow switching the supply to phases L1-N, L2-N and
L3-N. More details will be given ahead in this manual.
Due to the complexity of the test, the following will describe
the complete setup of the instruments.
1.16. 1 Test setup
To perform the test it is necessary the following material at
both ends:
1 x T1000 PLUS: current generator
1 x GPS: with antenna and cables for the synchronization
1 x SWT3: to change the Mains supply
1 x HCSW: high current switch, to rotate the phase angle
of the output by 180°
And follow the following steps:
1.
Connect the GPS output to digital input START of the
T1000 PLUS
2.
Select GPS Pulse Rate equal to 10 seconds