DOC. MIE91093 Rev. 1.34
Page 56 of 145
. Power-on T1000 PLUS, acting on switch (2): the internal light
turns on.
. Press the button (70) to have the AC voltage available.
. If you wish to use the DC voltage output to supply the relay
under test, press the button (69), then use knob (20) to
adjust the voltage value, that is displayed on the LCD display
(23). Connect the DC supply input of the relay to sockets (63).
. Select the auxiliary voltage range and the pre-fault + fault
mode as follows.
AUX VAC/VDC > Aux VAC control > Range (RET)
Mode > Pre-fault+fault > Pre-
fault amplitude > (Value) ESC
The range should be the closest one to the nominal voltage.
The pre-fault amplitude is adjusted by the multi-function knob
and display; the value is computed from the nominal relay
(phase – to – phase) voltage VN: