background image

13

14.  All horizontal runs of pipe should be as short as possible and are 

required by NFPA No. 211 to have an upward pitch or rise in the 

same direction the smoke travels of no less than 1/4” to the linear 

foot. The connector pipe must meet minimum clearances in any 

direction to walls or other combustible materials. It must attach to 

a listed double wall metal chimney at least 6” in diameter or to a 

masonry chimney with a flue passage of at least 48 square inches.

15.  It is required that a chimney connector pipe not extend further than 

the inner wall of the flue when it is connected to a masonry chimney 

and that it either be cemented to the masonry or be installed without 

cement in a thimble connected to the masonry wall. When the 

connector is inserted into a thimble, the joint must be tight enough 

so that it will not be dislodged in normal use.

        Install connector at no less than the minimum clearances from the 

ceiling when using a 90-degree elbow to pass through combustible 

constructions.

16.  Chimney connector pipes should never pass through a floor, ceiling, 

fire wall, partition, or combustible construction of any type unless 

certain precautions are taken. The best method is to use a listed 

thimble and a listed chimney in accordance with the manufactures 

directions. NFPA No. 211 gives approved methods for passing a flue 

pipe through combustible constructions.

1.  If not previously installed, install floor protection and move the 

heater into the desired location.

2.  Position the stove on your floor protection in the exact location 

where it is to be located, making sure all minimum clearances are 

met.

3.  If you are installing outside air on your stove, mark a 4” circle on 

the floor protection just below the oblong ring. When cut out, this 

hole will accommodate the flexible outside air tube.

4.  If the stove is to be fastened to the floor, locate the hold down 

brackets inside the leg box and mark the floor protection below the 

holes in the brackets.

5.  If you are installing outside air on your stove, remove the stove and 

cut the floor protection and the floor where the 4” air tube circle 

had been previously drawn. If the stove is to be fastened to the 

floor, drill 1/2” holes through the floor protection only, at the marks 

that were for fastening the stove to the floor if so desired. Slip the 

flexible outside air tube through the hole in the floor, leaving 1” of 

tube above the floor protector surface, using tape to hold it in place.

6.  Place the stove on the floor protection so that the previously cut or 

drilled holes line up. Attach the stove to the floor with the lag bolts 

if so desired.

7.  If you are installing outside air on your stove place the hose clamp 

over the flexible air tube and slide the tube up over the 4” ring on 

the outside air adaptor box and tighten the hose clamp. Push the 

outside air adaptor forward 1/4” until full contact is made with the 

lower heatshield. Tighten the 1/4” bolt until the adaptor box is held 

firmly in place. Use silicone sealant to create a seal between the 

flexible air tube and your floor protection.

8.  If it is necessary to level, secure or ground your stove, use the holes 

in the bottom of the leg for those applications. To level the stove on 

Olympic cast legs, locate the front leg that is not touching the hearth 

pad. Insert the allen head screw through the slotted washer (supplied 

with the legs) and into the threaded hole in the bottom of the leg. 

See Figure 12. Push the slotted washer down until it touches the 

hearth pad and then tighten the screw into the leg. Should any other 

leg not be resting on the hearth pad, install a washer and screw in 

that leg as well.

9.  Install baffle boards and baffle blanket as per instructions on Pages 

15 and 16. It is highly recommended that the baffle be assembled 

before the chimney is installed so that the baffle blanket can be 

adjusted into place through the flue collar.

10.  If installed into a mobile home, the stove shall be grounded to the 

mobile home chassis with a #8 AGW copper wire or equivalent.

11.  For residential installations, install the first section of stove pipe 

with the crimped end going down inside the flue collar on the heater. 

Continue with your stove pipe, installing each section-crimped 

end down. Make the final connection to your chimney. Your dealer 

carries the necessary pipe and fittings to connect to the various 

listed factory-built chimneys. 

YOUR CHIMNEY INSTALLATION 

MUST COMPLY WITH LOCAL BUILDING AND FIRE CODES.

12.  Be sure to fasten each stove pipe connection with at least 3 sheet 

metal screws.

13.  Install chimney as per manufacturer’s instructions. Some brands of 

pipe may require removal of the spacer ring in the flue collar.

Figure 12

STOVE INSTALLATION

Insert the allen 

head screw 

through the 

slotted washer

Summary of Contents for Striker S160

Page 1: ...18 A French manual is available upon request Order P N 900127 00 Ce manuel d installation est disponible en francais simplement en faire la demande Num ro de la pi ce 900127 00 This appliance must be...

Page 2: ...for Installation 7 Installation Clearances 8 Typical Installation Figures 9 Chimney Installation 10 USING THIS MANUAL Please read and carefully follow all of the instructions found in this manual Plea...

Page 3: ...g season to check for soot and creosote accumulations Any accumulations over 1 8 thick should be removed by a professional chimney sweep Do not attempt to burn out heavy creosote accumulations with a...

Page 4: ...he actual vertical vent height to determine your effective draw In this case if you had 14 feet of vertical vent the effective draw would only be approximately 9 feet 14 ft 5 ft 9 ft therefore it may...

Page 5: ...a steel container with a tight fitting lid and moved outdoors immediately Other waste shall not be placed in this container The closed container of ashes should be placed on a non combustible floor o...

Page 6: ...THE AMOUNT OF AIR ENTERING THE STOVE IMMEDIATELY BURN IN PERIOD PAINT CURING 4 4 8 Standard Cord of Wood 8 Ft 2 4M 4 Ft 1 2M 4 Ft 1 2M Thisapplianceisdesignedtoburndryseasonednaturalwoodonly see Page...

Page 7: ...Shield attaches to rear of stove pipe and must run from stove top to ceiling Pipe shield shall be UL listed Residential chimney systems must be from the same brands as listed for mobile homes but conn...

Page 8: ...m 72 1829mm USA 8 200mm from door opening Canada 8 200mm from sides and back of unit u Dimensions to Stove Body v Clearances may only be reduced by means approved by the regulatory authority Mobile Ho...

Page 9: ...ure 5 Typical Installation Figure 6 Connected to a Masonry Chimney Floor Protector Floor Protector Fasten each stove pipe connection with at least 3 sheet metal screws Single wall stove pipe must not...

Page 10: ...nted to the masonry or be installed without cement in a thimble connected to the masonry wall When the connector is inserted into a thimble the joint must be tight enough so that it will not be dislod...

Page 11: ...ll be 12 in 305 mm Chimney section concentric with and spaced 1 in 25 4 mm away from connector by means of sheet steel support plates on both ends of chimney section Opening shall be covered and chimn...

Page 12: ...the contents upon receipt and check for any damaged or missing parts If there is hidden damage notify your freight company or IHP dealer immediately CAUTION Wear gloves during installation in case of...

Page 13: ...the floor if so desired Slip the flexible outside air tube through the hole in the floor leaving 1 of tube above the floor protector surface using tape to hold it in place 6 Place the stove on the fl...

Page 14: ...pper wire or equivalent 11 Install bricks as per instructions on Pages 15 and 16 It is highly recommended that the baffle be assembled before the chimney is installed so that the baffle blanket can be...

Page 15: ...he baffle boards so as not to block exhaust flow to the flue Use a ruler or a piece of kindling to reach over the baffle blanket to be sure it is completely flat on top of the baffle boards Measure br...

Page 16: ...the front to rear of the firebox Start by setting the back side of the board on the rear baffle making sure that it is placed far enough back to lift up and onto the front baffle Next you will place...

Page 17: ...l tool to help ensure you are not over firing your appliance and it will also ensure you are burning fuel at a rate that is most efficient Place a stove thermometer on the top of the appliance Monitor...

Page 18: ...ot enough to effectively heat the air moved by the blower If the air coming from the blower feels cool one should either decrease the blower speed or stoke the fire to build up more heat NOTE Turn blo...

Page 19: ...d the appliance let the appliance top cool down to 275 to 400 degrees on Elites locatethermometeronthefaceoftheinsertjustabovethedoor Now load the firebox and set the draft control At this point you m...

Page 20: ...pected at least once a year by a qualified service technician to ensure gaskets air tubes baffles and venting are in good repair to ensure proper performance Have degraded items replaced by a qualifie...

Page 21: ...r burns more build up Higher burns less build up Keep freshly loaded wood away from the glass After reloading allow all the wood to catch flame before dampering down the appliance GLASS REPLACEMENT IN...

Page 22: ...20 SMOKES WHEN 1 If smoke is entering the room check to make sure your baffle boards are properly installed DOOR IS OPEN and that the baffle blanket is pushed back flush with the front of the baffle b...

Page 23: ...nts in your area Carbon Monoxide Monitor Recommended Carbon Monoxide Poisoning Early signs of carbon monoxide poison ing are similar to the flu with headaches dizziness and or nausea If you have these...

Page 24: ...tside Air Plenum Box FSB BLOWER PARTS 25 H8062 FSB700 Blower Only Assembly w blower wiring harness 26 H5658 Fan Blade FSB700 27 H5657 Fan Cage FSB700 28 H8063 FSB700 Blower Only Wire Harness 29 H8064...

Page 25: ...25 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE 25 REPLACEMENT PARTS MODELS S160 AND SA160...

Page 26: ...26 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE REPLACEMENT PARTS MODELS S160 AND SA160 Door Parts Blower Parts 7 13 1 2 3 4 5 6 8 1 2 3 4 5 9 10 8 14 11 6 7 12 25 29 31 28 27 26 32 30...

Page 27: ...27 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE REPLACEMENT PARTS MODELS S160 AND SA160 22 24 18 20 21 23 Leg and Leg Parts...

Page 28: ...28 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE REPLACEMENT PARTS MODELS S160 AND SA160 15 18 15 18 19 16 17 19 Ash Drawer Pedestal and Pedestal...

Page 29: ...pic Sculptured Nickel 4 per pkg 70008 LEG OLY BRN Olympic Sculptured Brushed Nickel 4 per pkg 70003 LEG CAS B Cascade Steel Black 4 per pkg HEAT SHIELD REQUIRED WITH LEGS 71110 WSHS 160 Heat Shield re...

Page 30: ...ctured By INNOVATIVE HEARTH PRODUCTS 1502 14th St NW Auburn WA 98001 USA PREVENT HOUSE FIRES Install and use only in accordance with manufacturer s installation and operating instructions and your loc...

Page 31: ...inder may burn at excessive temperatures and may cause damage to the Product or may cause it to function improperly IHP stoves inserts and high efficiency EPA fireplaces are approved for burning dry s...

Page 32: ...he Serial Number of the appliance 3 The part number 4 The description of the part 5 The quantity required 6 The installation date of the appliance If you encounter any problems or have any questions c...

Reviews: