background image

11

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Chimney Connector Systems and Clearances from Combustible 

Walls for Residential Heating Appliances (NFPA 211) 

Refer to 

Figure 8

System A.

 Minimum 3.5 in. (90 mm) thick brick masonry wall 

framed into combustible wall with a minimum of 12 in. (305 mm) 

brick separation from clay liner to combustibles. Fireclay liner (ASTM 

C 315, Standard Specification for Clay Flue Linings, or equivalent), 

minimum 5/8 in. (16 mm) wall thickness, shall run from outer surface 

of brick wall to, but not beyond, the inner surface of chimney flue 

liner and shall be firmly cemented in place.
Clearance: 12 in. (305 mm)

System B

. Solid-insulated, listed factory-built chimney length of the 

same inside diameter as the chimney connector and having 1 in. 

(25.4 mm) or more of insulation with a minimum 9 in. (229 mm) air 

space between the outer wall of the chimney length and combustibles.
The inner end of the chimney length shall be flush with the inside of 

the masonry chimney flue and shall be sealed to the flue and to the 

brick masonry penetration with non-water-soluble refractory cement. 

Supports shall be securely fastened to wall surfaces on all sides.
Fasteners between supports and the chimney length shall not pen-

etrate the chimney liner.
Clearance: 9 in. (229 mm)

System C.

 Sheet steel chimney connector, minimum 24 gauge [0.024 

in. (0.61 mm)] in thickness, with a ventilated thimble, minimum 24 

gauge [0.024 in. (0.61 mm)] in thickness, having two 1 in. (25.4 

mm) air channels, separated from combustibles by a minimum of 6 

in. (152 mm) of glass fiber insulation. Opening shall be covered, and 

thimble supported with a sheet steel support, minimum 24 gauge 

[0.024 in. (0.61 mm)] in thickness.
Supports shall be securely fastened to wall surfaces on all sides and 

shall be sized to fit and hold chimney section. Fasteners used to secure 

chimney section shall not penetrate chimney flue liner.
Clearance: 6 in. (152 mm)  

System D.

 Solid-insulated, listed factory-built chimney length with 

an inside diameter 2 in. (51 mm) larger than the chimney connector 

and having 1 in. (25.4 mm) or more of insulation, serving as a pass-

through for a single wall sheet steel chimney connector of minimum 

24 gauge [0.024 in. (0.61 mm)] thickness, with a minimum 2 in. 

(51 mm) air space between the  outer wall of chimney section and 

combustibles. Minimum length of chimney section shall be 12 in. 

(305 mm). Chimney section concentric with and spaced 1 in. (25.4 

mm) away from connector by means of sheet steel support plates 

on both ends of chimney section. Opening shall be covered, and 

chimney section supported on both sides with sheet steel supports 

of minimum 24 gauge [0.024 in. (0.61 mm)] thickness.
Supports shall be securely fastened to wall surfaces on all sides and 

shall be sized to fit and hold chimney section. Fasteners used to secure 

chimney section shall not penetrate chimney flue liner.
Clearance: 2 in. (51 mm)

Additional requirements:

1. Insulation material used as part of wall pass-through system shall be 

of noncombustible material and shall have a thermal conductivity of 

1.0 Btu-in./hr-ft

2

 - ºF (4.88 kg-cal/hr-m

2

 - ºC) or less.

2. All clearances and thicknesses are minimums; larger clearances and 

thicknesses shall be permitted.

3. Any material used to close up an opening for the connector shall be of 

noncombustible material.

4. A connector to a masonry chimney, except for System B, shall extend 

in one continuous piece through the wall pass-through system and the 

chimney wall to the inner face of the flue liner, but not beyond.

Factory Built 

Chimney Length 

Air Space – 9 in. 

(228.6mm) Min. 

Chimney Length 

Flush with 

Inside of Flue 

Min. Clearance 

9 in. (229mm) 

Chimney 

Connector 

Use Chimney 

Mfrs. Parts to 

Attach 

Connector 

Solid-Insulated 

Listed Factory-

Built Chimney 

Length

Sheet Steel Supports

Sheet Steel Supports

Sheet Steel Supports

Minimum Chimney Clearance from Masonry to Sheet Steel 

Supports & Combustibles – 2 in. (51mm) 

Nonsoluble 

Refractory  

Cement

Minimum chimney clearance to sheet

steel supportrs and combustibles

2 in. (51mm)

Chimney 

Connector 

2 Air Channels, Each 1 

in. (25.4 mm) 

2 Ventilated Air 

Channels, Each 

1 in. (25.4 mm) 

Construction of 

Sheet Steel 

Minimum chimney clearance to sheet steel 

supports and combustibles 2 in. (51mm) 

Sheet Steel 

Supports 

Chimney 

Connector 

Chimney 

Section

Air Space – 2 in. 

(51mm) Min. 

Chimney connector  

Chimney length

1 in. (25.4 mm) 

air space to 

        chimney length

Min. Clearance  

2 in. (51 mm) 

Minimum

12 in. (305mm)

to combustibles

Masonry chimney

constructed to NFPA 211

Masonry chimney

constructed to NFPA 211

Masonry chimney

constructed to NFPA 211

Masonry chimney

constructed to NFPA 211

Minimum chimney clearance to brick

and combustibles 2 in. (51mm)

Minimum clearance

12 in. (305mm)

of brick

Chimney

Chimney

flue

Chimney

flue

Chimney

flue

connector

Fire clay

liner

Figure 8 - 

Chimney Connector Systems and Clearances from Combustible Walls

System A

System B

System C

System D

Summary of Contents for Striker S160

Page 1: ...18 A French manual is available upon request Order P N 900127 00 Ce manuel d installation est disponible en francais simplement en faire la demande Num ro de la pi ce 900127 00 This appliance must be...

Page 2: ...for Installation 7 Installation Clearances 8 Typical Installation Figures 9 Chimney Installation 10 USING THIS MANUAL Please read and carefully follow all of the instructions found in this manual Plea...

Page 3: ...g season to check for soot and creosote accumulations Any accumulations over 1 8 thick should be removed by a professional chimney sweep Do not attempt to burn out heavy creosote accumulations with a...

Page 4: ...he actual vertical vent height to determine your effective draw In this case if you had 14 feet of vertical vent the effective draw would only be approximately 9 feet 14 ft 5 ft 9 ft therefore it may...

Page 5: ...a steel container with a tight fitting lid and moved outdoors immediately Other waste shall not be placed in this container The closed container of ashes should be placed on a non combustible floor o...

Page 6: ...THE AMOUNT OF AIR ENTERING THE STOVE IMMEDIATELY BURN IN PERIOD PAINT CURING 4 4 8 Standard Cord of Wood 8 Ft 2 4M 4 Ft 1 2M 4 Ft 1 2M Thisapplianceisdesignedtoburndryseasonednaturalwoodonly see Page...

Page 7: ...Shield attaches to rear of stove pipe and must run from stove top to ceiling Pipe shield shall be UL listed Residential chimney systems must be from the same brands as listed for mobile homes but conn...

Page 8: ...m 72 1829mm USA 8 200mm from door opening Canada 8 200mm from sides and back of unit u Dimensions to Stove Body v Clearances may only be reduced by means approved by the regulatory authority Mobile Ho...

Page 9: ...ure 5 Typical Installation Figure 6 Connected to a Masonry Chimney Floor Protector Floor Protector Fasten each stove pipe connection with at least 3 sheet metal screws Single wall stove pipe must not...

Page 10: ...nted to the masonry or be installed without cement in a thimble connected to the masonry wall When the connector is inserted into a thimble the joint must be tight enough so that it will not be dislod...

Page 11: ...ll be 12 in 305 mm Chimney section concentric with and spaced 1 in 25 4 mm away from connector by means of sheet steel support plates on both ends of chimney section Opening shall be covered and chimn...

Page 12: ...the contents upon receipt and check for any damaged or missing parts If there is hidden damage notify your freight company or IHP dealer immediately CAUTION Wear gloves during installation in case of...

Page 13: ...the floor if so desired Slip the flexible outside air tube through the hole in the floor leaving 1 of tube above the floor protector surface using tape to hold it in place 6 Place the stove on the fl...

Page 14: ...pper wire or equivalent 11 Install bricks as per instructions on Pages 15 and 16 It is highly recommended that the baffle be assembled before the chimney is installed so that the baffle blanket can be...

Page 15: ...he baffle boards so as not to block exhaust flow to the flue Use a ruler or a piece of kindling to reach over the baffle blanket to be sure it is completely flat on top of the baffle boards Measure br...

Page 16: ...the front to rear of the firebox Start by setting the back side of the board on the rear baffle making sure that it is placed far enough back to lift up and onto the front baffle Next you will place...

Page 17: ...l tool to help ensure you are not over firing your appliance and it will also ensure you are burning fuel at a rate that is most efficient Place a stove thermometer on the top of the appliance Monitor...

Page 18: ...ot enough to effectively heat the air moved by the blower If the air coming from the blower feels cool one should either decrease the blower speed or stoke the fire to build up more heat NOTE Turn blo...

Page 19: ...d the appliance let the appliance top cool down to 275 to 400 degrees on Elites locatethermometeronthefaceoftheinsertjustabovethedoor Now load the firebox and set the draft control At this point you m...

Page 20: ...pected at least once a year by a qualified service technician to ensure gaskets air tubes baffles and venting are in good repair to ensure proper performance Have degraded items replaced by a qualifie...

Page 21: ...r burns more build up Higher burns less build up Keep freshly loaded wood away from the glass After reloading allow all the wood to catch flame before dampering down the appliance GLASS REPLACEMENT IN...

Page 22: ...20 SMOKES WHEN 1 If smoke is entering the room check to make sure your baffle boards are properly installed DOOR IS OPEN and that the baffle blanket is pushed back flush with the front of the baffle b...

Page 23: ...nts in your area Carbon Monoxide Monitor Recommended Carbon Monoxide Poisoning Early signs of carbon monoxide poison ing are similar to the flu with headaches dizziness and or nausea If you have these...

Page 24: ...tside Air Plenum Box FSB BLOWER PARTS 25 H8062 FSB700 Blower Only Assembly w blower wiring harness 26 H5658 Fan Blade FSB700 27 H5657 Fan Cage FSB700 28 H8063 FSB700 Blower Only Wire Harness 29 H8064...

Page 25: ...25 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE 25 REPLACEMENT PARTS MODELS S160 AND SA160...

Page 26: ...26 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE REPLACEMENT PARTS MODELS S160 AND SA160 Door Parts Blower Parts 7 13 1 2 3 4 5 6 8 1 2 3 4 5 9 10 8 14 11 6 7 12 25 29 31 28 27 26 32 30...

Page 27: ...27 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE REPLACEMENT PARTS MODELS S160 AND SA160 22 24 18 20 21 23 Leg and Leg Parts...

Page 28: ...28 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE REPLACEMENT PARTS MODELS S160 AND SA160 15 18 15 18 19 16 17 19 Ash Drawer Pedestal and Pedestal...

Page 29: ...pic Sculptured Nickel 4 per pkg 70008 LEG OLY BRN Olympic Sculptured Brushed Nickel 4 per pkg 70003 LEG CAS B Cascade Steel Black 4 per pkg HEAT SHIELD REQUIRED WITH LEGS 71110 WSHS 160 Heat Shield re...

Page 30: ...ctured By INNOVATIVE HEARTH PRODUCTS 1502 14th St NW Auburn WA 98001 USA PREVENT HOUSE FIRES Install and use only in accordance with manufacturer s installation and operating instructions and your loc...

Page 31: ...inder may burn at excessive temperatures and may cause damage to the Product or may cause it to function improperly IHP stoves inserts and high efficiency EPA fireplaces are approved for burning dry s...

Page 32: ...he Serial Number of the appliance 3 The part number 4 The description of the part 5 The quantity required 6 The installation date of the appliance If you encounter any problems or have any questions c...

Reviews: