background image

20

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE

Pre-lighting Instructions

During an initial start-up, or in the case where the hopper has run out of 

fuel, it will be necessary to prime the auger feed system.

To prime the auger feed system:

1. Fill the hopper with recommended pellet fuel and plug the stove into 

the wall outlet.

2. Press the "START" button on the control board to start the fuel feed. 

Next, press the "HEAT OUTPUT" button to position #5 (maximum feed 

rate).

3.  Look through the combustion chamber door and when you see the first 

pellets dropping into the UltraGrate™, the auger is then fully primed.  

It will take 10 to 15 minutes to prime the auger.

4.  Once the auger is primed, press the "STOP" button to turn off the auger 

(LED will go off).

Starting Your Pellet Stove

1.  Make sure the auger is primed (see 

Pre-Lighting Instructions

 on this 

page), then simply push the "START" button on the control board to 

activate the Fastfire™ igniter.

2.  While the pellets will ignite on any heat output setting, it is recommended 

that the "HEAT OUTPUT" button be set to position #3. Pellets will start 

feeding into the UltraGrate and should begin to ignite in approximately 

three to seven minutes. The Fastfire igniter will automatically shut off 

after 8 minutes.

3. After the pellets are burning well, press the "HEAT OUTPUT" selector 

to the desired setting.  Combustion air and the pellet fuel feed rate will 

adjust automatically as the "HEAT OUTPUT" button is pressed.  The 

flame should be bright yellow in color and there should be no evidence 

of soot formation at the top of the flame.  Press the "BLOWER" speed 

button to increase or decrease the blower speed to the desired level

4. If operating your stove with the wall thermostat, adjust the "HEAT 

OUTPUT" button to the desired demand mode (#1 through #5 on the 

"HEAT OUTPUT" button).  Next, adjust the wall mounted thermostat 

to the desired room temperature and your stove will automatically 

switch between a demand mode and stand-by mode.

NOTES:

Cold Start

 - When the "START" button is pressed when the appliance 

is cold, voltage will  bypass its normal circuit through the low limit 

thermal switch (for 20 minutes to allow adequate time for the low limit 

thermal switch to heat [140° F min.] which will close the circuit). The 

combustion and convection blowers will start at maximum speed. 

After approximately 10 seconds both blowers will default to settings 

they were at after the last shut down was completed (indicated by 

LED's #1 to #5). The Fastfire igniter will operate for approximately 8 

minutes. The auger will turn continuously for a predetermined dura

-

tion at the respective Heat Output Settings, followed by the normal 

operating mode.

Re-Fueling While in Operation

1. Open hopper lid and fill hopper with pellets.

2. Make sure the hopper lid is completely closed.

3. Check to make sure the stove remains lit.

4. If the flame goes out, press the "start" button on the control panel to 

re-ignite.

CAUTION: Failure to ensure pellets in the UltraGrate remain 

burning after re-fueling may result in smoke escaping from 

the unit.

General Operating Considerations

Proper Burn Characteristics:  Your flame should be bright yellow under 

normal operations.  If your flame becomes reddish/orange, your stove 

probably needs routine maintenance.  Excessive amounts of fly-ash build-

up in the UltraGrate, clinkers in the UltraGrate, or leakage of air if the 

UltraGrate is not properly seated, will starve the fire for air.  (See 

Routine 

Maintenance

  for information on cleaning the stove).  If the problem per-

sists, review the troubleshooting section at the end of this manual.

Manual and Automatic Operation

Your pellet stove can be operated in either the manual or automatic mode.  

The manual mode is used when operating without a wall thermostat. The 

automatic mode is used when utilizing a wall thermostat.  When utilizing the 

thermostat capability, the burn time can be extended dramatically depending 

on thermostat setting. 

NOTE:

 

It is normal for some ash to build up on the 

inner glass surface at the lower Heat Output settings.

Manual Operation

Pressing the "START" button will initiate the start-up cycle. The auger 

LED will be green to indicate the “on” status.  The blower speeds and 

pellet feeds are fixed during this time to provide appropriate ignition.  

The Fastfire igniter system will light the pellets fed to the UltraGrate, after 

about 3 minutes.  After the start-up cycle, your stove will be in the run 

mode.  At this point the stove will operate with the heat output ("HEAT 

OUTPUT" button) and blower settings ("BLOWER" button) selected.  These 

settings can be selected either during or after the start-up cycle.  Pressing 

the "STOP" button during the run mode will initiate the shut down cycle 

(feeding LED will go off).  The pellets will stop feeding and the blowers 

will run at a fixed speed for approximately 10 minutes.  At this point your 

stove is safely shut down.  The stove can be restarted by pressing the 

"START" button during the shut down cycle.

Automatic Operation

Your stove is capable of running in an automatic mode with the use of 

a wall thermostat. 

For the wall thermostat to control the operation of the stove, set it to a 

temperature that will put it in the demand mode (calling for heat).  The 

thermostat will establish either a demand mode or a stand-by mode.  

The thermostat should be set for the desired room temperature.  If the 

room temperature drops below the level on the thermostat the stove 

will automatically begin the start-up cycle, as explained in the 

Manual 

Operation

 section.  

Once the start-up cycle is completed the stove will operate at whatever 

heat and blower setting you have selected.  For best operation under 

thermostat control, the medium or high settings are recommended.  When 

the desired room temperature is reached the stove will automatically go 

into the shut down cycle.  The pellet feed will stop and the blowers will 

continue for a controlled time allowing safe shut down of your stove.  All 

lights will remain on when the thermostat is open.  The "HEAT OUTPUT" 

and "BLOWER" settings can be changed at any time, but only take affect 

during the run mode.  When the temperature in the room drops to the 

level set at the thermostat, the stove will again begin the start-up cycle 

and resume automatic operation in the demand mode.

NOTE: 

If the "START" button is pressed while the thermostat is in the 

standby mode the stove will not restart until the thermostat closes (call-

ing for heat).

Summary of Contents for 32FS

Page 1: ...for continuous use as a primary heat source A French manual is available upon request Order P N 900117 00 Ce manuel d installation est disponible en francais simplement en faire la demande Numéro de la pièce 900117 00 This appliance must be properly installed and operated in order to prevent the possibil ity of a house fire Please read this entire manual before installation and use of this pellet ...

Page 2: ...HP dealer for more information on approved pellet fuels 12 CONTINUOUS OPERATION When operated correctly this appliance cannot be overfired Continuous operation at a maximum burn can however shorten the life of the electri cal components blowers motors and electronic controls and is not recommended Typical approved operation would includerunningatthelowtomidrangesettingwithoccasional running on the...

Page 3: ... room heater The safety listing label is located on an inside hopper surface of the pelletstove Pleasereadthissafetylabelcarefully Itcontainsimportant information about installation and operation of this appliance This appliance is tested and listed for residential and commercial installation according to current national and local building codes as A Free Standing Room Heater A Manufactured Home ...

Page 4: ... any home we recommend installing smoke detectors If possible install the smoke detector in a hallway adjacent to the room to reduce the possibility of occasional false activation from the heat produced by these appliances If your local code requires a smoke detector be installed within the same room you must follow the requirements of your local code Check with your local building department for ...

Page 5: ... this appliance must be met within the space where it will be installed Ventilation is essential when using a solid fuel burning heater In well insulated and weather tight homes it may inhibit the rate the exhaust flows through the venting system caused by a shortage of air in the home The lack of air is caused by many common household appliances which exhaust air from the home such as a furnace h...

Page 6: ...t 4 102 mm B Back wall to unit 2 51 mm C Side wall to unit Corner 1 25 mm D Max Depth of Alcove u 24 610 mm E Flue to Wall v 3 76mm u Minimum Alcove Measurements Height 48 1220 mm x Width 31 788 mm x Maximum Depth 24 610 mm v See vent manufacturer to verify clearances Table 1 Combustible Rear Wall or Alcove Clearance to Combustibles Figure 3 Corner Clearance to Combustibles B A E D A E C C Combust...

Page 7: ...PIPE With listed termination kit If installation requires in excess of 11 of pipe it is recommended a 4 diameter pipe be used MANUFACTURED HOME Requires outside air for com bustion Use a galvanized or stainless steel pipe for duct Minimum duct size 1 5 8 dia CLEARANCES TO COMBUSTIBLES Ensure all clearances are main tained in accordance to instruc tions contained on product safety label and in comp...

Page 8: ...n standards CSA C22 1 latest edition in Canada as well as any local codes SeePages11through17foradditionalinformationonventingrequire ments WARNING DO NOT INSTALL THIS STOVE IN A SLEEPING ROOM IN A MANUFACTURED HOME CAUTION THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FLOOR WALLS CEILING ROOF MUST BE MAINTAINED Figure 4A Manufactured Home Installation Manufactured Home Exhaust Vent Pipe Insta...

Page 9: ...DETAIL B DETAIL B SEE DETAIL C DETAIL C Rear Pallet Bracket Rear Lag Screw Front Lag Screw Figure 5A Front Lag Screw Figure 5B Rear Lag Screw and Pallet Bracket Installation Check List It is strongly recommended that you have an IHP dealer install your stove If you install your stove yourself you should review your installation plan with an IHP dealer Check list Check off each item as you proceed ...

Page 10: ...ector locations After you have begun operation of your appliance q Review the routine cleaning maintenance information q Enjoy the warmth from your new IHP pellet stove Damper Location and Adjustment Damper Air Control Located behind the right side panel on model Montage 32FS Adjustment Procedure Using a 1 4 nut driver or socket loosen the damper setscrew see Figure 6 Adjust in 1 4 increments unti...

Page 11: ...tside of pipe unlessotherwisespecifiedbyventmanufacturer alldiameters 3 75 mm and 4 100 mm A support bracket must be installed every 4 feet 1 2 m of pellet vent pipe on the exterior wall of the house unless otherwise specified by vent manufacturer It is not recommended to terminate exhaust vent on the prevailing wind side of the house In Canada where the venting may pass through a wall or partitio...

Page 12: ...rmitted From Eave Vertical Terminal Vertical Terminal Fixed Closed Able To Open A A B B B B C D E F G H J K L M N 24 610mm B Air Supply Inlet 24 610mm Figure 9 D The distance from the bottom of termination to grade is 12 305 mm minimum unless otherwise specified by the vent manufacturer This is conditional upon plants and nature of grade surface Be careful to choose alocationfortheventterminationw...

Page 13: ...als for additional requirements for your area To pass inspection in nearly any jurisdiction the chimney must meet both safety and exhaust flow requirements The 3 by 2 by 10 rule applies to both masonry and factory built chimneys Ref USA National Standard NFPA 211 latest edition and Canada National Standard CSA B365 01 latest edition Vents installed with a listed cap shall terminate in accordance w...

Page 14: ...Degree Elbow B 1 Horizontal Pipe C 45 Degree Elbow D Standoff Braces E 8 Vertical Pipe F 2 Horizontal Pipe G 90 Degree Tee H Wall Thimble NOTE All equivalent pipe styles shown for model Montage 32FS Type of Pipe of Elbows or Feet of pipe Equivalent Feet Total Equivalent Feet 90 Elbows Tee A G x 5 Feet 1 5 m 45 Elbows C x 3 Feet 1 m Horizontal B F x 1 Feet 3 m Vertical E x 5 Feet 15 m Table 3 Sampl...

Page 15: ...ble Do not position the back of the stove closer than 2 51 mm from the wall see Clearances Page 6 4 Install listed type PL 45 degree elbow with rodent screen or cap on outside end of pipe The Inlet shall remain free of obstruction while unit is in operation and constructed in a manner so as to prevent material from dropping into the inlet or into the area beneath the dwelling The inlet shall also ...

Page 16: ... Minimum Hearth Pad Floor Protection 45 Degree Elbow 2 51 mm Minimum Figure 17 Montage 32FS Parallel Through the Wall Wall Outdoors Standard Horizontal Installation Configurations Montage 32FS NOTE Horizontal run of pipe requires 1 4 7 mm rise per foot Figure 16 Montage 32FS Corner Through the Wall u Refer to vent manufacturer s installation instructions for minimum vent clearance Ne pas installer...

Page 17: ...ical pipe promotes natural draft and with the chimney inside the dwelling the flue gases stay warm thus rising at a consistent rate NOTE See Pages 11 and 12 for Vent Termination Requirements Clean Out Tee Flashing Listed Rain Cap Extend Pipe to the Top if Existing Chimney is Corroded or Damaged Pipe Increaser Existing Chimney Pipe Optional Clean Out Access Door Optional Complete Liner and Listed T...

Page 18: ...e fuel will pile up in the UltraGrate see Page 10 If the damper is too far outward the flame might be extinguished because of too much combustion air See Page 20 for further instructions on adjusting damper using thermostat vs manual modes No 7a Followthetroubleshooting section in this manual Contact your IHP dealer for further assistance 10 Thank you for purchasing an IHP Pellet Stove END Does th...

Page 19: ...wer IMPORTANT NOTE If the fuel feed trim or combustion air trim needs to be adjusted contact your dealer or qualified technician to calibrate internal software The trim controls should only be adjusted for the proper flame if all other options did not achieve proper adjustment It is recommended that the damper be used to fine tune your stove to your particular fuel and installation configuration s...

Page 20: ...ur flame should be bright yellow under normal operations If your flame becomes reddish orange your stove probablyneedsroutinemaintenance Excessiveamountsoffly ashbuild up in the UltraGrate clinkers in the UltraGrate or leakage of air if the UltraGrate is not properly seated will starve the fire for air See Routine Maintenance for information on cleaning the stove If the problem per sists review th...

Page 21: ...smoky or red orange flame excessive ash or soot excessive buildup on glass fuel may pile up Contributing factors High Altitude Lack of oxygen Restrictive Venting elbows horizontal runs cold external chimneys etc Dirty Poor Quality Fuel Lack of Maintenance NOTE Excessiveamountsoffly ashbuilt upintheUltraGrate clinkers in the UltraGrate or leakage of air if the grate is not properly seated will star...

Page 22: ...wood pellets in a dry place to prevent them from absorb ing excess moisture Do Not store your wood pellets within the clearance zone of the stove Do Not store your wood pellets in a place that would block removal of the ash pan or block access to refueling the hopper FUEL CAUTION The use of unapproved dirty wet and or high salt content fuel will void the warranty ROUTINE MAINTENANCE Wood pellets m...

Page 23: ...le plate to the left until the screw heads clear the open end of the key hole slots Remove the baffle plate diagonally through door opening The tube scraper rod can now be pulled in a more horizontal manner which allows the scraper to move more freely NOTE The baffle plate should be removed at least once a year to allow for a thorough cleaning Figure 24B Removing Baffle Plate Figure 25 Clean Behin...

Page 24: ...mplete combustion such as occurs during startup shutdown or incorrect operation of the room heater will lead to some soot formation which will collect in the exhaustventingsystem Theexhaustventingsystemshouldbeinspected at least once every year to determine if cleaning is necessary Burningfuelwithahighashcontentoranimproperlyadjusteddamper may require more frequent cleaning and stove maintenance F...

Page 25: ... expelled moisture to form creosote The creosote vapors condense in the relatively cool chimney flue of a slow burning fire As a result creosote residue accumulates on the flue lining Whenignitedthiscreosotemakesanextremelyhotfire Thechimneycon nector and chimney should be inspected at least once every two months duringtheheatingseasontodetermineifacreosotebuilduphasoccurred If creosote has accumu...

Page 26: ...LACED BEFORE HEATER CAN BE SAFELY OPERATED USE ONLY COMPONENTS PROVIDEDBYTHEMANUFACTURERASREPLACEMENTPARTS Small Area Paint Touch up The stove body is painted with a quality high temperature stove paint Use only model TSPK B Stove Paint Catalog H8159 Do not touch up your stove with any other paint Using one small piece of 320 grit sand paper and lightly sand the blem ish so that the edges are feat...

Page 27: ...imations only 25 1 4 Approved for Manufactured Home Installations Optional Kits Available Decorative trim kits log set window screen and 3 and 4 Quick Discon nect kits The burn grate is designed with advanced UltraGrate technology uIn Canada floor protection is required directly underneath and 2 from the sides of the flue or chimneyadaptor ThisisrecommendedintheUS vBurn times hopper capacity and B...

Page 28: ...at in the ashpan area This switch is located on the firebox base behind the convection jacket directly above the ashpan This switch is most easily accessed by removing the ashpan ThermalSwitch LowLimit Ceramic F140 20F N O G This proof of fire switch will close at 140 F and will not open until it reaches a temperature of 120 F This switch is located on the combustion blower behind the right side p...

Page 29: ...ER DIRECTLY ABOVE ASHPAN 2 BLK IGN 08 2302 MATERIAL SPECIFICATIONS MATERIAL WHITE POLYESTER 740 2 MIL PRINT TREATED ADHESIVE PERMANENT ACRYLIC ADHESIVE MATERIAL SIZE 4 X 10 TEXT BLACK DIELINE WILL NOT PRINT SUPPLIER INTERNATIONAL GRAPHICS NAMEPLATE INC 14413 NE 10TH AVE SU C VANCOUVER WA 98685 800 458 3355 REV DATE ALTERATIONS PREPARED BY CHKR NC 06 04 2008 T 3654 New Release MSJ JB JSH CRZ TOLERA...

Page 30: ...f fuel E The proof of fire switch is opening disconnecting power to the auger motor A Refill hopper B See Pelletswill not feed thisPage C Allowthe appliance to cool for 1 hour then re light Ifthestove hasbeen operating at a medium to high burn rate withtheroomair blower adjusted to low there maynot be enough air flowtodissipate the heat On higher feed rates adjust the blower speedtoahigher setting...

Page 31: ... leak the fine particles of ash into the home Clean the stove with an approved ash vacuum ONLY 6 Stovewillnotlight A The igniter element may have failed B There is not enough pellets in the UltraGrate A Check igniter element fuse in rear stove compartment Call your IHP dealer See Lighting Procedure Without Igniter Page 20 B Prime the feed system see Pre lighting Instruc tions Page 20 7 Fault A The...

Page 32: ...ket 1 per pkg 36 H7063 Hopper Lid Switch 1 per pkg 26 H7065 High Limit Auto Reset Reverse Flow Snap Switch Assembly L250 30F N C 1 per pkg on firebox base behind convection jacket above the ash pan 28 12147705 High Limit Auto Snap Switch L250 30F N C 3 per pkg on convection jacket 37 H5887 Low Limit Auto Proof of Fire Snap Switch Assembly F140 30F N O 1 per pkg 57601 Item Cat No Description 27 121...

Page 33: ...NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE 33 REPLACEMENT PARTS Montage 32FS 13 46 19 14 33 47 12 49 5 11 15 17 50 9 21 16 18 20 4 10 52 34 38 Includes 20 feet of thermostat wire 8 6 1 7 3 2 51 ...

Page 34: ...34 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE 26 27 28 31 32 33 31 57 REPLACEMENT PARTS Montage 32FS 24 28 28 37 27 40 56 44 36 30 29 34 41 23 26 45 25 22 43 54 35 55 53 42 32 ...

Page 35: ...Log Set 775077M 6 H8159 TSPK B Touch up Paint Black 7 12050093 QDPC 3 Quick Disconnect Pipe Connector 3 ref Form 506033 02 7 14M81 QDPC 4 Quick Disconnect Pipe Connector 4 ref Form 506033 02 8 H8974 RC S STAT AC Remote T Stat Alternating Current RCVR 9 H8865 RC S TOUCH Remote Touch Screen Thermostat On Off 10 H8861 RC S STAT Remote LCD Stat Thermostat On Off 11 H8860 RC S 1 Remote Two Button Timer...

Page 36: ...36 NOTES ...

Page 37: ...roduct IHP will not be responsible for a damages caused by normal wear and tear accident riot fire flood or acts of God b damages caused by abuse negligence misuse or unauthorized alteration or repair of the Product affecting its stability or performance The Product must be subjected to normal use The use of fuels other than those outlined in the operation manual provided with the Product will voi...

Page 38: ...al File it with your other documents for future refer ence Product reference information We recommend that you record the following important information about your fireplace Please contact your IHP dealer for any questions or concerns Replacement parts See Page 32 through 34 for a complete replacement parts list Use only parts supplied from the manufacturer Normally all parts should be ordered th...

Reviews: