A-12 IRIS OWNER’S GUIDE
SERIES 3000 Version 1.0
Appendix A
A.4 Site Selection
Table A-2 contains a list of guidelines for site selection for your IRIS. Although
site selection is the customer’s responsibility, Silicon Graphics’ representatives
will provide consulting services upon request.
Temperature
50 — 86°F (operating)
32 — 122°F (non-operating)
Relative humidity
20 — 80%
Minimum clearance
3" all sides
Monitor desk space
Nineteen-inch Hz
Fifteen-inch
30" width
30" depth
22" width
22" depth
Cabinet space
24" width
33" depth
33" height
System Power Requirement
single phase
line, neutral, ground
115 VAC Configuration
Operating Range
220 VAC Configuration
Operating Range
93-132 V AC
47-63 Hz
186-264 V AC
47-63 Hz
System Power Consumption Cabinet 1250 VA/1000 W
Nineteen-inch 60 Hz Monitor 225 VA/150 W
Fifteen-inch Monitor 185 VA/100 W
Nineteen-inch 33 Hz Monitor 170 VA/116 W
Heat dissipation
Cabinet 3412 BTU/hr
Nineteen-inch 60 Hz Monitor 512 BTU/hr
Fifteen-inch Monitor 341 BTU/hr
Nineteen-inch 33 Hz Monitor 395 BTU/hr
Card Slots
20
Table A-2: IRIS Environmental Specifications