CP Series Compatibility and Suitability of Use Guidelines

Addendum (Rev.11042014)

The purpose of this addendum is to sufficiently identify electrical compatibility and predictable emergency light output 
of the LED luminaire when used with the IOTA ILB-LP-CP Series LED emergency drivers. Verification of these operat-
ing traits does not constitute a code-compliant, as-installed emergency egress system. It is still the responsibility of the 
Designer/Specifier to assure appropriate light levels are achieved during emergency operation of the luminaire in ac-
cordance with Federal, state and local municipal codes regarding path of egress illumination. 

1. 

Determining Electrical Compatibility

 

 

1.1 Verify that the Emergency Driver (ILB-LP-CP Series) selected does not exceed the power delivered to the  

 

      LED array (voltage and current) of the normal driver.

 

1.2 Verify that the normal operating point of the LED driver does not exceed 200 Vdc (for ILB-LP-CP20 models)  

 

      or 250 Vdc (for ILB-LP-CP30 models).

2. 

Calculating Lumen Output During Emergency Operation

 

 

2.1 Assess luminaire/fixture data.  

 

 

2.1.1  DESIGNLIGHTS CONSORTIUM  

 

 

 

- Log onto the DesignLights Consortium website (www.designlights.org).

 

 

 

- Click on “search the DLC Qualified Product List” button on the DLC homepage.

       

 

 

-  In the “search by keyword” text window enter: luminaire manufacturer name and part number.

        

 

 

- Click on “Search” tab to open the “Qualified Products List.”

        

 

 

- Determine per “RATED DATA” efficacy shown in lumens per watt - (lm/w).

        

 

 

- Multiply lumens per watt by ILB-LP-CP rated output (example: lm/w x 5 watts). Refer to table  

 

 

 

  “ILB MODEL SPECIFICATION CHART” below for the wattage of the specific ILB-LP-CP   

 

 

 

  model to be used in the luminaire. (lm/w) x (ILB-LP-CP Watts) = Minimum emergency lumens  

 

 

 

  of fixture.

        

 

 

- Determine per “RATED DATA” the “wattage of the luminaire.”

3. 

Determining Adequacy of Means-of-Egress Lighting Levels

 3.1 Follow industry standards by utilizing available .ies files and lighting design software for your dedicated    

      emergency luminaires, with the above calculated emergency lumens, and validate your as-installed              
      plans in accordance with the applicable life safety codes governing your project, typically 1fc on the   
      ground along the full means of egress.

While the ILB-LP-CP series has been found compliant with the requirements of UL Standard 924, it is 

ultimately the responsibility of the Designer/Specifier to assure the as-installed system delivers code-
compliant path of egress illumination in accordance with Federal, State or local municipal requirements. 

ILB MODEL SPECIFICATION CHART

OUTPUT POWER (CONSTANT)

ILB-LP-CP20-HV

20 WATTS

ILB-LP-CP30-HV

30 WATTS

Summary of Contents for ILB-LP-CP-HE-SD-HV

Page 1: ...rting to wattage Refer to Illustration 1 for output voltage per model 13 Equipment should be mounted in a location and at heights where it will not be readily subject to tampering by unauthorized personnel 14 Make sure that the branch circuits are derived from a common phase for both normal lighting LED drivers and the LED Emergency Driver prior to installation 15 When used with a switched fixture...

Page 2: ...ly engage the TSPL Connector to the TSPL Socket Ensure the TSPL Connector is properly seated in the TSPL Socket then mark the TSPL location on the switch box plate with the TSPL Label and apply the SD Status Indicator Sticker INSTALLATION INSTRUCTIONS Refer to the appropriate wiring diagram below Make sure all connections are in accordance with NEC and any other local requirements ILB LP NORMAL DR...

Page 3: ...e ILB LP CP HE SD HV is in the standby charging mode The TSPL will be lit providing a visual indication that the battery is being charged Emergency Mode The A C power fails The ILB LP CP HE SD HV senses the A C power failure and automatically switches to the Emergency Mode The LED Module is illuminated at reduced output for a minimum of 90 minutes When the A C power is restored the ILB LP CP HE SD...

Page 4: ... Testing Manual testing of the ILB LP CP HE SD HV can be performed by pressing and releasing the TSPL test button Table A TSPL Diagnostic Codes CONDITION STATUS INDICATION STEADY GREEN OR STEADY RED NORMAL MODE FLASHING GREEN SELF TESTING OFF EMERGENCY MODE FLASHING RED GREEN INSUFFICIENT CHARGE 1 RED FLASH BATTERY PACK FAILURE 2 RED FLASHES EMERGENCY LAMP FAILURE 3 RED FLASHES FIXTURE DIAGNOSTIC ...

Page 5: ...k on search the DLC Qualified Product List button on the DLC homepage In the search by keyword text window enter luminaire manufacturer name and part number Click on Search tab to open the Qualified Products List Determine per RATED DATA efficacy shown in lumens per watt lm w Multiply lumens per watt by ILB LP CP rated output example lm w x 5 watts Refer to table ILB MODEL SPECIFICATION CHART belo...

Page 6: ... la puissance électrique Reportez vous à l Illustration 1 pour connaître la tension de sortie de chaque modèle 13 Il faut installer cet équipement à un endroit et à une hauteur qui permettent d éviter toute manipulation par des personnes non autorisées 14 Assurez vous que les circuits de branchement sont dérivés d une phase commune pour les pilotes des DEL d éclairage normal et le pilote d urgence...

Page 7: ...t le connecteur de la LTBT dans la douille de la LTBT Assurez vous que le connecteur de la LTBT est bien en place dans sa douille puis marquez son emplacement sur la plaque de la boîte de distribution à l aide de l étiquette TSPL LBTB et apposez l autocollant de l indicateur de statut SD INSTRUCTIONS D INSTALLATION Reportez vous au diagramme de câblage approprié ci dessous Assurez vous que toutes ...

Page 8: ...mode de chargement en veille La LTBT est allumée et indique de manière visuelle que la batterie est en cours de chargement Mode d urgence L alimentation secteur tombe en panne L ILB LP CP HE SD HV détecte la panne de courant et bascule automatiquement en mode d urgence Le module DEL s allume donnant un éclairage réduit pendant un minimum de 90 minutes Lorsque l alimentation secteur se rétablit l I...

Page 9: ...appuyant et en relâchant le bouton de test LTBT Tableau A Codes de diagnostic de la LTBT CONDITION VOYANT D ÉTAT DEMEURE VERT OU ROUGE FIXES MODE NORMAL CLIGNOTEMENT EN VERT TEST D AUTODIAGNOSTIC ÉTEINT MODE D URGENCE CLIGNOTEMENT EN ROUGE VERT CHARGE INSUFFISANTE 1 CLIGNOTEMENT ROUGE PANNE DE BATTERIE 2 CLIGNOTEMENTS ROUGES PANNE DE L ACCESSOIRE DE LAMPE D URGENCE 3 CLIGNOTEMENTS ROUGES PANNE DÉT...

Page 10: ... page d accueil de DLC Dans la fenêtre de texte Recherche par mot clé entrez le nom du fabricant du luminaire et le numéro de pièce Cliquez sur l onglet Recherche pour ouvrir la Liste des produits homologués Déterminez par DONNÉES NOMINALES l efficacité indiquée en lumens par watt lm w Multipliez les lumens par watt par la puissance nominale ILB LP CP exemple lm w x 5 watts Consultez le TABLEAU DE...

Reviews: