“Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”

SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL. 

Consult Customer Service or visit www.iotaengineering.com for current warranty information.

TESTING & MAINTENANCE

WIRING DIAGRAM

Maintenance

 

When performing maintenance the 

ILB-LP-CP-HE-SD-HV 

must be completely powered down by removing AC power and 

performing one of the following steps:

 

1) Pressing and holding the TSPL button for approximately five seconds until the LED Module shuts off. This function can only 
be performed during the first 30 seconds of Emergency Mode.

 

2) Unplugging the TSPL in Emergency Mode.

Automatic Testing

 

The 

ILB-LP-CP-HE-SD-HV 

is designed to automatically test the emergency function for five minutes each month, and 90 

minutes every 12 months.

 

Self-testing works in conjunction with the TSPL assembly. Any detected failures will be indicated by flashing of the bi-color 
LED. See Table A below for diagnosis: 

Manual Testing

 

Manual testing of the 

ILB-LP-CP-HE-SD-HV 

can be performed by pressing and releasing the TSPL test button.

Table A: 

TSPL Diagnostic Codes

CONDITION

STATUS INDICATION

STEADY GREEN OR STEADY RED

NORMAL MODE

FLASHING GREEN

SELF-TESTING

OFF

EMERGENCY MODE

FLASHING RED/GREEN

INSUFFICIENT CHARGE

1 RED FLASH

BATTERY PACK FAILURE

2 RED FLASHES

EMERGENCY LAMP FAILURE

3 RED FLASHES

FIXTURE DIAGNOSTIC FAILURE DETECTED

4 RED FLASHES

TEMPERATURE OUT OF RANGE

ILB-LP WITH TSPL TEST ACCESSORY

AC (NORMAL) 

DRIVER

IOTA ILB-LP

EMERGENCY DRIVER

LED

LOAD

WHITE

WHITE

WHT/RED

NEUTRAL

UNSWITCHED 

24/7 POWER

BLACK (120 TO 277V, 50/60HZ)

AC INPUT (120 TO 277V)

SWITCHED OR
UNSWITCHED 

HOT

TSPL

TEST ACCESSORY

RED (+)
BLUE (-)

VIOLET/WHITE (+)

 LED INPUT(-)

 LED INPUT (+)

 LED OUTPUT (+)

 LED OUTPUT (-)

ATTENTION:

 DO NOT CONNECT THE TSPL CONNECTOR UNTIL 

INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED.

CONNECT TSPL AFTER INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED

YELLOW
BROWN

GROUND

LEDCODE (+)
LEDCODE (-)

Refer to the diagram below for the appropriate wiring of the LED load and driver. Install in accordance with the National Electrical 
Code and local regulations. For additional wiring diagrams consult Customer Service.

!

Cap LEDCODE wires 
if unused

Summary of Contents for ILB-LP-CP-HE-SD-HV

Page 1: ...rting to wattage Refer to Illustration 1 for output voltage per model 13 Equipment should be mounted in a location and at heights where it will not be readily subject to tampering by unauthorized personnel 14 Make sure that the branch circuits are derived from a common phase for both normal lighting LED drivers and the LED Emergency Driver prior to installation 15 When used with a switched fixture...

Page 2: ...ly engage the TSPL Connector to the TSPL Socket Ensure the TSPL Connector is properly seated in the TSPL Socket then mark the TSPL location on the switch box plate with the TSPL Label and apply the SD Status Indicator Sticker INSTALLATION INSTRUCTIONS Refer to the appropriate wiring diagram below Make sure all connections are in accordance with NEC and any other local requirements ILB LP NORMAL DR...

Page 3: ...e ILB LP CP HE SD HV is in the standby charging mode The TSPL will be lit providing a visual indication that the battery is being charged Emergency Mode The A C power fails The ILB LP CP HE SD HV senses the A C power failure and automatically switches to the Emergency Mode The LED Module is illuminated at reduced output for a minimum of 90 minutes When the A C power is restored the ILB LP CP HE SD...

Page 4: ... Testing Manual testing of the ILB LP CP HE SD HV can be performed by pressing and releasing the TSPL test button Table A TSPL Diagnostic Codes CONDITION STATUS INDICATION STEADY GREEN OR STEADY RED NORMAL MODE FLASHING GREEN SELF TESTING OFF EMERGENCY MODE FLASHING RED GREEN INSUFFICIENT CHARGE 1 RED FLASH BATTERY PACK FAILURE 2 RED FLASHES EMERGENCY LAMP FAILURE 3 RED FLASHES FIXTURE DIAGNOSTIC ...

Page 5: ...k on search the DLC Qualified Product List button on the DLC homepage In the search by keyword text window enter luminaire manufacturer name and part number Click on Search tab to open the Qualified Products List Determine per RATED DATA efficacy shown in lumens per watt lm w Multiply lumens per watt by ILB LP CP rated output example lm w x 5 watts Refer to table ILB MODEL SPECIFICATION CHART belo...

Page 6: ... la puissance électrique Reportez vous à l Illustration 1 pour connaître la tension de sortie de chaque modèle 13 Il faut installer cet équipement à un endroit et à une hauteur qui permettent d éviter toute manipulation par des personnes non autorisées 14 Assurez vous que les circuits de branchement sont dérivés d une phase commune pour les pilotes des DEL d éclairage normal et le pilote d urgence...

Page 7: ...t le connecteur de la LTBT dans la douille de la LTBT Assurez vous que le connecteur de la LTBT est bien en place dans sa douille puis marquez son emplacement sur la plaque de la boîte de distribution à l aide de l étiquette TSPL LBTB et apposez l autocollant de l indicateur de statut SD INSTRUCTIONS D INSTALLATION Reportez vous au diagramme de câblage approprié ci dessous Assurez vous que toutes ...

Page 8: ...mode de chargement en veille La LTBT est allumée et indique de manière visuelle que la batterie est en cours de chargement Mode d urgence L alimentation secteur tombe en panne L ILB LP CP HE SD HV détecte la panne de courant et bascule automatiquement en mode d urgence Le module DEL s allume donnant un éclairage réduit pendant un minimum de 90 minutes Lorsque l alimentation secteur se rétablit l I...

Page 9: ...appuyant et en relâchant le bouton de test LTBT Tableau A Codes de diagnostic de la LTBT CONDITION VOYANT D ÉTAT DEMEURE VERT OU ROUGE FIXES MODE NORMAL CLIGNOTEMENT EN VERT TEST D AUTODIAGNOSTIC ÉTEINT MODE D URGENCE CLIGNOTEMENT EN ROUGE VERT CHARGE INSUFFISANTE 1 CLIGNOTEMENT ROUGE PANNE DE BATTERIE 2 CLIGNOTEMENTS ROUGES PANNE DE L ACCESSOIRE DE LAMPE D URGENCE 3 CLIGNOTEMENTS ROUGES PANNE DÉT...

Page 10: ... page d accueil de DLC Dans la fenêtre de texte Recherche par mot clé entrez le nom du fabricant du luminaire et le numéro de pièce Cliquez sur l onglet Recherche pour ouvrir la Liste des produits homologués Déterminez par DONNÉES NOMINALES l efficacité indiquée en lumens par watt lm w Multipliez les lumens par watt par la puissance nominale ILB LP CP exemple lm w x 5 watts Consultez le TABLEAU DE...

Reviews: