ILB-CP-HE-SD WITH TBTS TEST ACCESSORY

ILBCP_TBTS_SD.EPS

AC (NORMAL) 

DRIVER

IOTA ILB-CP-HE-SD

EMERGENCY DRIVER

LED

LOAD

WHITE

WHITE

BLACK

BLK/WHT

COMMON

UNSWITCHED 

24/7 POWER

BLK/ORG (120 TO 277V, 50/60HZ)

AC INPUT (120 TO 277V)

SWITCHED OR
UNSWITCHED 

HOT

TBTS

TEST ACCESSORY

RED (+)

BLUE (-)

RED/WHT (+)

BLUE/WHT (-)

 LED INPUT(+)

 LED INPUT (-)

 LED OUTPUT (+)

 LED OUTPUT (-)

UNIT

CONNECTOR

WHT/RED

RED/BLK (+)

ATTENTION: DO NOT MATE UNIT CONNECTOR UNTIL 
INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED.

TEST ACCESSORY LEADS-OBSERVE PROPER
POLARITY WIRING.

MATE UNIT CONNECTOR AFTER INSTALLATION IS 
COMPLETE AND AC POWER IS SUPPLIED

Illustration 3: Typical Wiring Diagram          

5. LABELS

Attach the appropriate labels adjacent to the 

TBTS. 

Annotate Replacement Label with identical manufacturer part

number(s). The Caution and the Replacement labels must be on the fixture in a readily visible location to anyone

attempting to service the fixture.

6. WIRING THE A.C. INPUT

A. The 

ILB-CP20-HE-SD-A

 and A.C. 

driver

 

MUST 

be on the same branch circuit.

B. The 

ILB-CP20-HE-SD-A

 requires an 

unswitched

 A.C. power source of 120 to 277 VAC, 50/60Hz; therefore

when used with switched fixtures, the ILB input must be wired ahead of the switch.

C. Refer to the wiring diagram for proper wiring. For wiring diagrams not shown, consult our customer service.

7. COMPLETING INSTALLATION

When the installation is complete, switch the A.C. power on and join the 

ILB-CP20-HE-SD-A

 unit connector

(remove the protective red boot, if present). NOTE: If the battery has been fully discharged, the TBTS indicator
may remain OFF for a few minutes until the battery has achieved sufficient charge for functional testing.

OPERATION

Normal Mode

 – A.C. power is present. The A.C. driver operates the LED load as intended. The 

ILB-CP20-HE-SD-A

 is 

in the standby charging mode. The 

TBTS 

will be 

flashing green

 providing a visual indication that the battery is being 

charged, or 

solid green

 if the battery is fully charged.

Emergency Mode

 – The A.C. power fails. The 

ILB-CP20-HE-SD-A

 senses the A.C. power failure and automatically 

switches to the 

Emergency Mode

. The designated LED arrays are illuminated, for a minimum of 90 minutes. When the 

A.C. power is restored, the 

ILB-CP20-HE-SD-A

 switches the system back to the 

Normal Mode

 and resumes battery

charging. See page 1 of the Instruction Manual.

TESTING & MAINTENANCE

The 

ILB-CP20-HE-SD-A

 is designed to automatically conduct 30-second tests at regular intervals every 28 to 30 days, 

and a 90 minute test anually. Automatic testing will 

not

 begin until at least 24 hours after the 

ILB-CP20-HE-SD-A

 

unit 

connector is joined. 

Load Calibration - 

48 hours after the unit connector is joined, the 

ILB-CP20-HE-SD-A

 

will conduct a 

Load Calibra-

tion

.  Note: after the Load Calibration is complete, any changes to the LED load that will affect its nominal input voltage 

will necessitate a new Load Calibration

 

(see table below for the sequence of button presses to conduct a manual Load 

Calibration).  Automatic Testing will proceed in the following schedule: