background image

Page 3

4.0

SYSTEM PROPERTIES:

Introduction:

GAS-CHECK SF6 is a portable, mains-independent instrument for leak 

detection

 and

leak 

measurement

 of SF6 gas. Although designed for SF6, other gases with a high

affinity for electrons, such as refrigerant R12 may also be detected.

Although designed for operation without training, we recommend that this manual be
read before use. This manual and the instrument have been designed to be understood
by users whose first language is not English. Please advise us of any changes, which will
make this easier.

Two modes of operation are available, volume loss/time cc/sec (leak-detection) and
(ppm) concentration of SF6 in air.

All controls and displays required for 

detection

 are found in the hand unit. Accurate and

clear 

measurement

 is achieved from the console 

touch screen

 display.

Measurements can be stored in the instrument and later transferred to a printer or
computer. A battery-powered printer is available. Results may also be downloaded to a
computer via the RS2323 link.

The only item, which needs to be replaced in normal use, is the ‘

Smart Sensor

’ probe.

Smart Sensors contain a microchip programmed with specific sensor information. At
Switch ON, the console automatically reads sensor information.

Smart Sensors are not radioactive and contain nothing harmful. Life is approximately
200hours

. Sensors are changed by switching OFF the instrument and plugging in a

replacement

.  Three (3) are supplied and available as exchange items.

The operation of the instrument and sensor require permanent and precise control by
software. Any faults give immediate error messages, which are then displayed on the
touch screen. This in conjunction with the sample flow monitoring function, ensures the
instrument reliably determines and displays all fault conditions.

All vital user parameters are password protected against unauthorised entry.

Access to the touch-screen is required for set-up only. If used outside or in difficult
conditions the transparent cover over touch-screen can be left locked.

4.1

CONSOLE CONTROLS:

1

Touch-screen for numeric leak rate display and parameter entry.

Two red on/off buttons located at the front and right side panel. Both are lit when the
instrument is on. White light combines mains supply and battery charge control. This
flashes while on charge and is permanently on when the battery is full.

A Key allows the transparent front cover to be locked during use.

Summary of Contents for GAS-CHECK SF6

Page 1: ...INSTRUCTION MANUAL GAS CHECK SF6 AN INSTRUMENT FOR THE LOCATION AND MEASUREMENT OF LEAKS IN SF6 FILLED ELECTRICAL SWITCHGEAR User Manual iss 01 Software Version V1 39BB...

Page 2: ...ion 6 7 3 Low flow error 7 7 4 Flare stall 7 7 3 Low battery voltage 7 7 5 Switching OFF 7 8 0 Switching OFF in case of fault 7 8 1 User setup 8 8 2 Set volume Contrast 8 9 0 Open Operator Level 8 9 1...

Page 3: ...p after fuse has been removed 15 16 3 Pre set passwords on delivery 15 16 4 Settings on despatch 16 16 5 Citizen printer 16 16 6 Spares and consummables 16 3 0 GENERAL This manual is addressed to thos...

Page 4: ...contain a microchip programmed with specific sensor information At Switch ON the console automatically reads sensor information Smart Sensors are not radioactive and contain nothing harmful Life is ap...

Page 5: ...may confidently measure This is OFF whenever the instrument is in standby or programming mode error condition or the actual reading is above 20 of the alarm level Red 2 NOT READY This light is on whe...

Page 6: ...used at any time During the short zero time the lights change from RED to GREEN Do not leak test during this time During normal use it is recommended to press the CIRCLE key occasionally to zero the d...

Page 7: ...for you press Exit Should this not be the case please refer to paragraphs Possible Fault Conditions During Operation and Switching Off in Case of Fault in this manual 7 1 MEASURING OPERATION The GAS C...

Page 8: ...entration of SF6 many times above the measuring range 2 High vacuum in the probe caused by a partially blocked or aged sensor The instrument will attempt to compensate for these until a level is reach...

Page 9: ...the present value of a parameter will already be entered You may then confirm or delete and re enter 8 2 Set volume Contrast Using the three slider type controls on this screen select contrast for be...

Page 10: ...vel alerts the ALARM LED in the handgun Only the alarm level corresponding to the chosen mode ml sec or ppm can be entered Valid alarm levels are for leak rates 0 5 E 6 5 E 7 ml s to 20 E 6 200 E 7 ml...

Page 11: ...be assigned for 6 different operators please refer to Changing Passwords section 10 4 10 3 Access codes 10 4 CHANGING PASSWORDS Use one of the eight buttons to select the password you wish to change t...

Page 12: ...Air is measured first which takes 4 seconds A time bar is displayed along with an audible bleep The display then instructs the operator to put the probe to the reference leak When this is done the fi...

Page 13: ...when the STORE key is pressed Pressing either the STORE or CLEAR buttons resets this 12 3 Display units The touch screen display and alarm level entries as well as reference leak values will operate...

Page 14: ...e following will occur The touch screen screen contrast sensor and sample flow regulation are switched off Vacuum is released Lifetime of all major components is saved If POWER DOWN is selected the in...

Page 15: ...r operation The main function of the filter is to block out short wave noise Filter Count represents the number of measuring cycles over which the signal must be continuously above or below the averag...

Page 16: ...ew sensor and sets these values in the console memory this may take 10 50 seconds 15 2 Changing the Probe To change the sensor You Must Power Down Never unplug the probe while the red lights on the co...

Page 17: ...er set up ALL 4 SWITCHES MUST BE IN THE OFF POSITION Switch the printer ON using the side mounted slide switch The POWER and SEL green lights should be lit Press SEL to turn OFF the light and use LF t...