Goodrive350-19 series VFD for crane
Function parameter list
-246-
Function
code
Name
Description
Default
Modify
47: C_RO4 from PLC (Set P27.00 to 1.)
48: Contactor output
50: Brake output
50: Ready to release the brake
51: Ready to close the brake
52: The upward limit position is reached.
53: The downward limit position is reached.
54: Low voltage protection
55: Overload protection
56: Brake detection reminding
57: Brake failure alarm
58: Input phase loss alarm
59: Loose rope status (FWD loose rope
protection, REV loose rope alarm or fault)
60: In motor 1 state
61: In motor 2 state
62: In motor 3 state
63: PT100 temperature alarm
64: PT1000 temperature alarm
65: Boosting the speed with light load
66: Frequency decrease with voltage
67: Weighing alarm
68: AI detected temperature alarm
69: 216 communication virtual terminal output
P06.05
Output terminal
polarity selection
Used to set the polarity of output terminals.
When a bit is 0, the input terminal is positive;
when a bit is 1, the input terminal is negative.
BIT3
BIT2
BIT1
BIT0
RO2
RO1
HDO
Y
Setting range: 0x0
–0xF
00
○
P06.06
Y1 switch-on
delay
Used to specify the delay time corresponding to
the electrical level changes when the
programmable output terminals switch on or
switch off.
0.000s
○
P06.07
Y1 switch-off
delay
0.000s
○
P06.08
HDO switch-on
delay
0.000s
○
P06.09
HDO switch-off
0.000s
○