Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-95-
Setting
Function
Description
18
Multi-step speed terminal 3
Note: Multi-step speed 1 is low bit, multi-step speed
4 is high bit.
Multi-step
speed 4
Multi-step
speed 3
Multi-step
speed 2
Multi-step
speed 1
BIT3
BIT2
BIT1
BIT0
19
Multi-step speed terminal 4
20
Multi-step speed pause
Pause multi-step speed selection function to keep the set
value in present state.
21
Acceleration/deceleration time
selection 1
Use these two terminals to select four groups of
acceleration/decoration time.
Terminal
1
Terminal
2
Acceleration or
deceleration time
selection
Corresponding
parameter
OFF
OFF
Acceleration/
deceleration time 1
P00.11/P00.12
ON
OFF
Acceleration/
deceleration time 2
P08.00/P08.01
OFF
ON
Acceleration/
deceleration time 3
P08.02/P08.03
ON
ON
Acceleration/
deceleration time 4
P08.04/P08.05
22
Acceleration/deceleration time
selection 2
23
Simple PLC stop reset
Restart simple PLC process and clear previous PLC
state information.
24
Simple PLC pause
The program pauses during PLC execution, and keeps
running in current speed step. After this function is
cancelled, simple PLC keeps running.
25
PID control pause
PID is ineffective temporarily, and the VFD maintains
current frequency output.
26
Wobbling frequency pause
(stop at current frequency)
The VFD pauses at current output. After this function is
canceled, it continues wobbling-frequency operation at