Goodrive350A series high-performance multifunction VFD
Safety precautions
-4-
Note:
Do not switch on or switch off input power sources of the VFD frequently.
If the VFD has been stored for a long time without being used, set the capacitance (see
"Maintenance" and carry out inspection and pilot run on the VFD before use.
Close the front cover before running; otherwise, electric shock may occur.
1.4.3 Maintenance and component replacement
Only trained and qualified professionals are allowed to perform maintenance,
inspection, and component replacement on the VFD.
Disconnect all the power sources applied to the VFD before terminal wiring, and
wait for at least the time designated on the VFD after disconnecting the power
sources.
Take measures to prevent screws, cables and other conductive matters from
falling into the VFD during maintenance and component replacement.
Note:
Use proper torque to tighten the screws.
Keep the VFD and its parts and components away from combustible materials during
maintenance and component replacement.
Do not carry out insulation voltage-endurance test on the VFD, or measure the control circuits of
the VFD with megameter.
Take proper anti-static measures on the VFD and its internal parts during maintenance and
component replacement.
1.4.4 What to do after scrapping
The heavy metals inside the VFD should be treated as industrial effluent.
When the life cycle ends, the product should enter the recycling system. Dispose
of it separately at an appropriate collection point but not place it in the normal
waste stream.