ELECTRICAL CONNECTION
PREPARING FOR INSTALLATION
14
15
sMove controller | Installation instructions
sMove controller | Installation instructions
4.1 Principle sketches: Connection options for ventilation devices
Switching power supply unit
Terminal blocks
Potential-free opener
Ventilation unit
4
Preparing for installation
• Read the "Installation" and "Electrical connection" sections carefully before installation to avoid
installation errors. The installation and connection of the entire ventilation system must be
carried out by qualified and trained personnel.
• Before and during installation, note the safety regulations in order to avoid electrical accidents.
• Check the delivery for completeness and transport damage upon receipt using the delivery
note. Report missing items immediately.
• Only install all ventilation system devices intended for indoors
-
on finished and flat interior walls.
- in rooms which are free from aggressive or corrosive gases and extreme dust exposure.
• The sMove controller is installed on the interior wall via a mounting box.
Recommended installation height: 1.50 m floor to lintel height (reachability for operation)
�
68 mm
s4/s8: 1x, depth 66 mm
s4/s8: 1x, double box
s4 (Alternative): 1x, box, depth min. 90 mm
3.3 Jumpers
Jumper 2 is used to assign the function of the external interface when a potential-free switching
contact is connected (safety device: opener / other sensors: closer) as well as in the case of inte-
gration into a house control system.
The position of the jumper may only be changed in a de-energised state.
Function assignment depending on the switching contact
NO (closer
NC (opener)
Sensor
Position of jumper 2
Function with switch actuation / switching
attached
Normal operation
OFF (chimney func-
tion)
NO contact:
Safety device
(4 Pa)
not
attached
Ventilation
Ventilation level 3
Normal operation
Closer:
Humidistat
CO
2
VOC
Interface as analogue input
i
2
2
2
2
The 2-pin connector for jumper 2 is located on the rear of the operating unit.
Jumper 2 is not plugged in at the factory and is located in the accessory bag of the controller. It
must be plugged in if required. Jumper 1 is used for service settings and must be left in the deliv-
ery state for the controller to function correctly.
If, in the case of an sMove controller being replaced, for example, a pressure sensor (safety
device) with normally open contact is connected, it must be configured as normally closed contact
(switch with changeover contact) or, if this is not possible, it must be replaced with a (pressure)
sensor with normally closed contact.
It is not possible to connect a potential-free switch and an analogue input simultaneously. A
connected analogue input always has priority over a potential-free switching contact. If a safety
device is integrated, it has priority over other connected sensors.
If jumper 2 is not plugged in and the sMove controller is connected to a home control system, the
following DC voltages must be set:
Function
Control voltage [V DC]
Ventilation level 3
0.00 ≤ U ≤ 0.25
Ventilation level 4
0.75 ≤ U ≤ 1.25
Ventilation level 2
1.75 ≤ U ≤ 2.25
Ventilation level 1
2.75 ≤ U ≤ 3.25
OFF
3.75 ≤ U ≤ 4.25
Heat recovery ventilation level 1
4.75 ≤ U ≤ 5.25
Heat recovery ventilation level 2
5.75 ≤ U ≤ 6.25
Heat recovery ventilation level 3
6.75 ≤ U ≤ 7.25
Heat recovery ventilation level 4
7.75 ≤ U ≤ 8.25