Easy Start Guide

7. How to operate the Inverter from the keypad

Page 7

This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright

The Inverter

Drive Supermarket and must not be reproduced or altered without prior written permission.

©

7.1 Ensure the Inverter is in “Local” control mode.

Press the “Loc/Rem” button repeatedly until the green indicator lamp
next to the “Loc/Rem” button is illuminated.

See section 8 for further information on Local and Remote modes.

7.2 Set Parameter P121 to the required speed

Set parameter P121 (Keypad Reference) to the desired speed. In this
example, 25.00Hz is half the rated speed for a standard 50Hz
Induction Motor. Leave the display showing the speed in Hz.

See section 6 to learn how to set a parameter value.

7.3 Start the motor and change direction

Press the green button to start the motor. The motor will accelerate to
the required speed in the time specified by parameter P100. Use the
up and down keys to change the speed as required.
Pressing the direction button (see illustration opposite) will first
decelerate the motor to zero speed before accelerating up to the
current speed in the opposite direction. Parameters P100 and P101
control the acceleration and deceleration time in seconds. The lamps
on the left indicate direction; green = forward, red = reverse.

WEG CFW-08 Series Inverter

7.4 Stop the motor

Press the red button to stop the motor. The motor will decelerate to a
stop in the time specified by parameter P101.

Once stopped, the display will show “rdy” (ready).

Summary of Contents for CFW-08

Page 1: ...It should not be used as a replacement for the manual issued by the manufacturer Issue 2 20140223 This product is not a safety device All safety considerations including but not limited to Emergency S...

Page 2: ...otor Connections Star and Delta Parameters Overview Parameters to set before use How to Operate the Inverter from the keypad How to switch from Local keypad control to Remote terminal control and back...

Page 3: ...rame size 2 rating 1 5kW The terminal layout for other sizes and the Wash model is similar The order of the three phases determines the direction the motor turns Important Use screened SY cable betwee...

Page 4: ...odel is similar The order of the three motor phases determines the direction the motor turns The order of the three power phases is unimportant Important Use screened SY cable between the Inverter and...

Page 5: ...sometimes known as two at one side Only two links are required for Star Double up the links if changing from Delta to allow the motor to be changed back in future The order of the three phases determ...

Page 6: ...Hz 50 00 P404 Rated Motor Power Refer to P404 table in manual and set to match motor nameplate eg for 1 5 kW 6 P407 Rated Motor Power Factor Set to match motor if known eg look for cos 0 74 The Invert...

Page 7: ...tter P followed by a three digit number Typically this is P000 as shown in the illustration opposite 6 2 Find the Parameter to change Use the up and down keys to find the required parameter In this ex...

Page 8: ...ed for a standard 50Hz Induction Motor Leave the display showing the speed in Hz See section 6 to learn how to set a parameter value 7 3 Start the motor and change direction Press the green button to...

Page 9: ...pad control When the green indicator lamp next to the Loc Rem button is illuminated the Inverter is in Local mode When in Local mode the motor can be controlled using the integrated keypad The default...

Page 10: ...or builds a model of the motor it is controlling This is achieved by a tuning run during which the Inverter operates for approx 2 minutes to gather the necessary motor data Note Sensorless Vector is n...

Page 11: ...ter can be used instead This provides the benefit of allowing motor speed to be controlled from a more convenient location such as a cabinet door if the CFW 08 is cabinet mounted or on the machine its...

Page 12: ...een terminals 1 DI1 and 5 COM the motor will run forward When terminals 2 DI2 and 5 COM are connected the motor will run in reverse Care should be taken to ensure that terminals 1 DI1 and 2 DI2 cannot...

Page 13: ...eneral Enable link is required between terminals 1 and 5 Note that the Forward Reverse switch only selects the direction of rotation it will not start or stop the motor If the application only require...

Page 14: ...nput 3 T3 function Set to 1 for reset on T3 or set to 1 3 6 11 12 13 or 15 as required but no other values 0 P266 Digital input 4 T4 function Set to for forward reverse selection on T4 0 13 1 Paramete...

Page 15: ...Connect the brake resistor to the BR and UD Terminals on the Inverter The order of the connections is unimportant The braking resistor may get hot during operation Ensure that it is mounted in a suit...

Page 16: ...00 to 5 Press the PROG button again to select the parameter value Use the up and down keys to set this value to 5 Press PROG again to save The display will return to P000 Note setting P000 to 5 allows...

Reviews: