9. How to enable Sensorless Vector Mode
Page 9
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright
The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission.
©
The standard operating mode of the CFW-08
Inverter is VxF. This is the simplest form of
operation and controls Volts and Frequency to
vary the speed of a standard Induction Motor.
The CFW-08 can also operate in Sensorless
Vector mode. This can improve motor
performance without requiring a separate
feedback device.
In order to improve performance, Sensorless
Vector builds a “model” of the motor it is
controlling. This is achieved by a “tuning” run
during which the Inverter operates for approx.
2 minutes to gather the necessary motor data.
Note: Sensorless Vector is not suitable
where the motor rating is significantly
lower than the Inverter rating or where
more than one motor is being controlled.
Invoking a “tuning” run in these cases will
not be successful and return an E14 error.
Parameter
Description
How to set
P000
Parameter Access
Set to
to allow parameters to be changed
5
P202
Control Mode
Default is 0 (linear). Set to
to enable Sensorless Vector Control.
2
P408
Run Self-Tuning
Default is 0. Ensure motor is off-load before changing to
to begin self-tuning.
1
The display will flash “auto” whilst
the CFW-08 performs it’s tuning run.
Easy Start Guide
WEG CFW-08 Series Inverter
9.1 Parameters to check and values to set