9. How to enable Sensorless Vector Mode

Page 9

This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright

The Inverter

Drive Supermarket and must not be reproduced or altered without prior written permission.

©

The standard operating mode of the CFW-08
Inverter is VxF. This is the simplest form of
operation and controls Volts and Frequency to
vary the speed of a standard Induction Motor.

The CFW-08 can also operate in Sensorless
Vector mode. This can improve motor
performance without requiring a separate
feedback device.

In order to improve performance, Sensorless
Vector builds a “model” of the motor it is
controlling. This is achieved by a “tuning” run
during which the Inverter operates for approx.
2 minutes to gather the necessary motor data.

Note: Sensorless Vector is not suitable
where the motor rating is significantly
lower than the Inverter rating or where
more than one motor is being controlled.
Invoking a “tuning” run in these cases will
not be successful and return an E14 error.

Parameter

Description

How to set

P000

Parameter Access

Set to

to allow parameters to be changed

5

P202

Control Mode

Default is 0 (linear). Set to

to enable Sensorless Vector Control.

2

P408

Run Self-Tuning

Default is 0. Ensure motor is off-load before changing to

to begin self-tuning.

1

The display will flash “auto” whilst

the CFW-08 performs it’s tuning run.

Easy Start Guide

WEG CFW-08 Series Inverter

9.1 Parameters to check and values to set

Summary of Contents for CFW-08

Page 1: ...It should not be used as a replacement for the manual issued by the manufacturer Issue 2 20140223 This product is not a safety device All safety considerations including but not limited to Emergency S...

Page 2: ...otor Connections Star and Delta Parameters Overview Parameters to set before use How to Operate the Inverter from the keypad How to switch from Local keypad control to Remote terminal control and back...

Page 3: ...rame size 2 rating 1 5kW The terminal layout for other sizes and the Wash model is similar The order of the three phases determines the direction the motor turns Important Use screened SY cable betwee...

Page 4: ...odel is similar The order of the three motor phases determines the direction the motor turns The order of the three power phases is unimportant Important Use screened SY cable between the Inverter and...

Page 5: ...sometimes known as two at one side Only two links are required for Star Double up the links if changing from Delta to allow the motor to be changed back in future The order of the three phases determ...

Page 6: ...Hz 50 00 P404 Rated Motor Power Refer to P404 table in manual and set to match motor nameplate eg for 1 5 kW 6 P407 Rated Motor Power Factor Set to match motor if known eg look for cos 0 74 The Invert...

Page 7: ...tter P followed by a three digit number Typically this is P000 as shown in the illustration opposite 6 2 Find the Parameter to change Use the up and down keys to find the required parameter In this ex...

Page 8: ...ed for a standard 50Hz Induction Motor Leave the display showing the speed in Hz See section 6 to learn how to set a parameter value 7 3 Start the motor and change direction Press the green button to...

Page 9: ...pad control When the green indicator lamp next to the Loc Rem button is illuminated the Inverter is in Local mode When in Local mode the motor can be controlled using the integrated keypad The default...

Page 10: ...or builds a model of the motor it is controlling This is achieved by a tuning run during which the Inverter operates for approx 2 minutes to gather the necessary motor data Note Sensorless Vector is n...

Page 11: ...ter can be used instead This provides the benefit of allowing motor speed to be controlled from a more convenient location such as a cabinet door if the CFW 08 is cabinet mounted or on the machine its...

Page 12: ...een terminals 1 DI1 and 5 COM the motor will run forward When terminals 2 DI2 and 5 COM are connected the motor will run in reverse Care should be taken to ensure that terminals 1 DI1 and 2 DI2 cannot...

Page 13: ...eneral Enable link is required between terminals 1 and 5 Note that the Forward Reverse switch only selects the direction of rotation it will not start or stop the motor If the application only require...

Page 14: ...nput 3 T3 function Set to 1 for reset on T3 or set to 1 3 6 11 12 13 or 15 as required but no other values 0 P266 Digital input 4 T4 function Set to for forward reverse selection on T4 0 13 1 Paramete...

Page 15: ...Connect the brake resistor to the BR and UD Terminals on the Inverter The order of the connections is unimportant The braking resistor may get hot during operation Ensure that it is mounted in a suit...

Page 16: ...00 to 5 Press the PROG button again to select the parameter value Use the up and down keys to set this value to 5 Press PROG again to save The display will return to P000 Note setting P000 to 5 allows...

Reviews: