Easy Start Guide
Page 11
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright
The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission.
©
11. How to connect and configure a Run Forward or
Run Reverse switch
11.1 Parameters to change for remote Run/Stop
The parameters described in Section 5 enable
Run/Stop operation via the red and green
buttons on the Inverter.
If this is unsuitable for the application, a remote
switch can be used instead.
This section explains how to enable 2-wire
control with Run Forward / Stop / Run Reverse
commands via a single selector switch.
Ensure the Inverter is in “Remote” mode
before continuing.
11.2 Connecting the Switch
A wiring diagram is shown in the illustration
opposite.
A suitable 3 position NO (
)
switch should be installed between terminals 1
(DI1), 2 (DI2) and 5 (COM). The centre position
should remain open circuit.
When a connection is made between terminals
1 (DI1) and 5 (COM), the motor will run
forward. When terminals 2 (DI2) and 5 (COM)
are connected, the motor will run in reverse.
Care should be taken to ensure that terminals
1 (DI1) and 2 (DI2) cannot be connected to 5
(COM) at the same time or to each other.
If motor rotation is the opposite to that
required, simply swap connections 1 and 2.
Terminal 5 (COM) is a common connection for
terminals 1-4, 6 and 8 and has no other
function.
Normally Open
2
1
F
R
3
Switch, 3 Position
Normally Open
“Run Forward / Stop / Run Reverse”
WEG CFW-08 Series Inverter
1 2 3 4 5 6 7 8 9 10 11 12
COM
DI1
Parameter
Description
How to set
P000
Parameter Access
Set to
to allow parameters to be changed
5
P230
Remote Command Selection
Set to
to use the Inverter terminals (as opposed to keypad)
1
P263
Digital input 1 (T1) function
Set to
for Forward Run on T1 (ignore E24 error, will clear when P264, P265, P266 are set)
8
P264
Digital input 2 (T2) function
Set to
for Reverse Run on T2
8
P265
Digital input 3 (T3) function
Set to 1 for reset on T3 (or set to 1, 3, 6, 11, 12, 13 or 15 as required but no other values)
0
P266
Digital input 4 (T4) function
Set to
for run Jog on T4 (or set to 1, 6, 11, 12, 13, 14 or 15 as required but no other values)
3
DI2
1
2
3