Easy Start Guide
Page 5
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright
The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission.
©
4. Parameters - overview
Parameter
Description
How to set
P000
Parameter Access
Set to
to allow parameters to be changed
5
P100
Acceleration Time (seconds)
Default is
Increase or decrease if required.
5.0
P101
Deceleration Time (seconds)
Default is
Increase or decrease if required.
10.0
P133
Minimum Frequency (Hz)
Default is 3.00. Set to
for most applications.
5.00
P134
Maximum Frequency (Hz)
Default is 55.00 or 66.00. Set to
for most applications.
50.00
P202
Control Mode
Default is
(linear). Can be set to 1 (quadratic) if the motor is driving a Fan or Pump.
0
P399
Rated Motor Efficiency
Set to match motor if known - eg.
%)
71.00 (
P400
Rated Motor Voltage
Set to match motor nameplate - eg.
230
P401
Rated Motor Current
Set to match motor nameplate - eg.
(Amps)
3.34
P402
Rated Motor Speed
Set to match motor nameplate - eg.
(rpm, look for min -1)
1430
P403
Rated Motor Frequency
Set to match motor nameplate - eg.
(Hz)
50.00
P404
Rated Motor Power
Refer to P404 table in manual and set to match motor nameplate - eg.
(for 1.5 kW)
6
P407
Rated Motor Power Factor
Set to match motor if known - eg.
look for cos )
0.74 (
φ
The Inverter contains a number of settings
which can be changed to tailor it for use with a
wide range of motor ratings and applications.
These settings are known as parameters.
Parameters are typically referred to by code or
number (eg. P401 = Rated Motor Current) with
a description available in the manual.
The parameters contain critical information
essential to the correct operation of the
Inverter. Therefore, they should at least be
checked by the installer before the Inverter is
operated for the first time.
The parameters listed in section 5 are intended
to provide a starting point to allow for basic
operation of the CFW-08 Inverter.
5. Parameters to set before use
See section 6 to learn how to set a parameter value.
Set the following parameters to allow the
CFW-08 to control a motor with Run, Stop and
Speed Control from the keypad.
If any of the parameters have been changed
previously, follow the procedure in section 15
to reset the Inverter to Factory Defaults.
5.1 Parameters to check and values to set
WEG CFW-08 Series Inverter
Note: Although some parameters are only used in Sensorless Vector Mode (see Section 9), we recommend that all the above are set.