11
Tr
oublesh
ooting
Fault
Code
No.
OLED Message
Description
Corrective Action
49
Output Phase Loss
One of the motor output phases is not connected to the drive.
50
Modbus Comms fault
A valid Modbus telegram has not been received within the watchdog time limit set in P5-06.
Check the network master / PLC is still operating.
Check the connection cables.
Increase the value of P5-05 to a suitable level.
51
CAN Open comms trip
A valid CAN open telegram has not been received within the watchdog time limit set in P5-06.
Check the network master / PLC is still operating.
Check the connection cables.
Increase the value of P5-06 to a suitable level.
52
Communications Option
Module Fault
Internal communication to the inserted Communication Option Module has been lost.
Check the module is correctly inserted.
53
IO card comms trip
Internal communication to the inserted Option Module has been lost.
Check the module is correctly inserted.