Immunity Tests
8.1
Electrostatic Discharge (ESD)
The Optidrive E3 product range has been designed and tested to comply with the limits defined in EN 61800-3:2004+A1-2012. The test
techniques used are as defined in EN 61000-4-2:2009.
Application
Test points
Test Method
Level
Direct
Control Terminals
Contact Discharge
±4kV
Air Discharge
±8kV
Power Terminals
Air Discharge
±8kV
Indirect
Vertical coupling plane
Contact Discharge
±4kV
Horizontal coupling plane
Contact Discharge
±4kV
8.2
Electrical Fast Transient Burst (EFT/B)
The Optidrive E3 product range has been designed and tested to comply with the limits defined in EN 61800-3: 2004+A1-2012. The test
techniques used are as defined in EN 61000-4-4:2004.
Test points
Test Method
Level
Control Terminals
Capacitive clamp
±1kV at 5kHz
Motor Power Terminals
Capacitive clamp
±2kV at 5kHz
1-PH Supply Power Terminals
Coupling Decoupling Network
±2kV at 5kHz
3-PH Supply Power Terminals
Capacitive clamp
±4kV at 5kHz
8.3
Surge
The Optidrive E3 product range has been designed and tested to comply with the limits defined in EN 61800-3: 2004+A1-2012. The test
techniques used are as defined in EN 61000-4-5:2006.
Drive Type
Test Method
Level
200-240V
Line to Line/Neutral
±1kV
Line/Neutral to Earth
±2kV
380-480V
Line to Line
±2kV
Line to Earth
±4kV
8.4
Dielectric strength (Flash)
The Optidrive E3 product range has been designed and tested to comply with the limits defined in EN 61800-5-1: 2007. The test techniques
used are as defined in EN 61800-5-1: 2007.
Drive Type
Level
200-240V
1.5kV
380-480V
2.5kV