Quick
Setup
Overview:
•
Set
Basic
parameters
P1
‐
01
to
P1
‐
10.
Energy
Optimiser
P1
‐
06
must
remain
disabled.
•
Set
Parameter
P1
‐
14=
101
to
allow
access
to
extended
parameters
•
In
Menu
3,
Configure
parameters
for
the
PID
Control
•
If
drive
relay
2
is
used
as
part
of
the
slave
DOL
cascade
then
set
P2
‐
18
=
8
•
Set
parameter
P8
‐
14=1
to
enable
the
Pump
staging
–
DOL
cascade
function
•
Set
the
number
of
DOL
slave
pumps
available
in
the
system
(not
including
Master
VFD
pump)
in
P8
‐
15
•
Set
Optidrive
HVAC
operating
speed
limits
used
to
activate
/
deactivate
DOL
slave
pumps
as
follows:
o
P8
‐
17:
Pump
Staging
DOL
Switch
In
Speed
–
Threshold
to
bring
in
DOL
Slave
pump
o
P8
‐
18:
Pump
Staging
DOL
Switch
Out
Speed
–
Threshold
to
switch
out
DOL
Slave
pump
•
Set
a
pump
staging
settle
time
(minimum
10
seconds)
in
P8
‐
19.
The
time
entered
in
P8
‐
19
must
be
sufficient
for
the
PID
feedback
signal
from
the
system
output
sensor
to
settle
to
a
steady
level.
•
If
the
duty
run
times
between
DOL
slave
pumps
are
to
be
balanced
then
the
maximum
permissible
difference
in
hours
should
be
entered
in
P8
‐
16.
13.2.
Pump
Staging
–
Multiple
Drive
Cascade
Summary:
The
below
illustration
shows
the
use
of
a
Optidrive
HVAC
units
as
the
controllers
in
a
variable
speed
pump
staging
system.
All
pumps
in
this
configuration
are
controlled
the
Optidrive
HVAC
units
in
variable
speed
mode
with
co
‐
ordination
and
communication
carried
out
over
the
built
in
RS485
communications
link
as
shown
below.
Drives
can
be
connected
using
the
RJ45
data
cables
and
the
RS485
Data
Cable
Splitter
as
shown
above
up
to
a
maximum
of
5
drives.
Part
numbers
are
as
follows:
Product
Code
Description
OPT
‐
RJ45SP
RJ45
Splitter
Box
1
– 2
Way
OPT
‐
J4505
RJ45
to
RJ45
RS485
Data
Cable,
0.5m
OPT
‐
J4510
RJ45
to
RJ45
RS485
Data
Cable,
1m
OPT
‐
J4530
RJ45
to
RJ45
RS485
Data
Cable,
3m
Each
motor
/
pump
in
this
configuration
is
controlled
by
a
dedicated
HVAC
drive
(one
drive
per
pump).
All
drives
run
in
variable
speed
mode
with
the
speed
reference
passed
across
the
communications
network.
One
drive
in
the
system
is
denoted
the
‘Network
Master’.
The
Network
Master
has
the
Feedback
sensor
input
connected
to
it
along
with
the
input
set
‐
point
control,
and
uses
its
PID
function
to
generate
the
operating
speed
for
the
system.
The
‘Network
Master’
provides
an
enable
status
and
speed
reference
to
the
other
drives
on
the
network.
Operational
Overview:
The
pump
staging
with
multiple
drive
cascade
function
is
enabled
by
setting
parameter
P8
‐
14=2
(Pump
staging
function
select)
on
the
network
master
drive
only
.
All
drives
other
than
the
network
master
drive
must
be
set
to
communications
slaves
by
setting
parameter
P1
‐
12=
5
‘slave
mode).