![Invertek Drives Optidrive HVAC Series User Manual Download Page 22](http://html1.mh-extra.com/html/invertek-drives/optidrive-hvac-series/optidrive-hvac-series_user-manual_2085076022.webp)
Optidrive
ODV
‐
2
User
Guide
Revision
1.00
www.invertek.co.uk
22
P2
‐
15
User
Relay
1
Output
(Terminals
14,
15
&
16)
Function
select
Minimum
0
Maximum
7
Units
‐
Default
1
Selects
the
function
assigned
to
Relay
Output
1.
The
relay
has
normally
open
and
normally
closed
contacts.
Logic
1
indicates
the
relay
is
active,
and
therefore
the
normally
open
contact
is
closed
(terminals
14
and
15
will
be
linked
together)
and
the
normally
closed
contact
is
opened
(terminals
14
and
16
will
no
longer
be
connected
together).
0
:
Drive
Enabled
(Running)
.
Logic
1
when
the
motor
is
enabled
1
:
Drive
Healthy
.
Logic
1
when
power
is
applied
to
the
drive
and
no
fault
exists
2
:
At
Target
Frequency
(Speed)
.
Logic
1
when
the
output
frequency
matches
the
set
‐
point
frequency
3
:
Output
Frequency
>
0.0
Hz
.
Logic
1
when
the
drive
output
frequency
to
the
motor
is
exceeds
0.0Hz
4
:
Output
Frequency
>=
Limit
.
Logic
1
when
the
motor
speed
exceeds
the
adjustable
limit
5
:
Output
Current
>=
Limit
.
Logic
1
when
the
motor
current
exceeds
the
adjustable
limit
6
:
Reserved
.
No
Function
7
:
Analog
Input
2
Signal
Level
>=
Limit
.
Logic
1
when
the
signal
applied
to
the
Analog
Input
2
exceeds
the
adjustable
limit
8
:
Reserved.
No
Function
9
:
Fire
Mode
Active.
Logic
1
when
the
drive
in
running
in
Fire
Mode
(Fire
Mode
input
is
active).
10
:
Maintenance
Due.
Logic
1
when
Maintenance
Timer
expires
indicating
that
Maintenance
is
now
due.
11
:
Drive
Available.
Logic
1
when
drive
is
in
Auto
‐
mode,
no
trips
are
present,
and
the
safety
circuit
is
enabled
indicating
that
drive
is
ready
for
automatic
control.
Note:
When
using
settings
4
–
7,
parameters
P2
‐
16
and
P2
‐
17
are
used
to
control
the
output
behaviour.
The
output
will
switch
to
Logic
1
when
the
selected
signal
exceeds
the
value
programmed
in
P2
‐
16,
and
return
to
Logic
0
when
the
signal
falls
below
the
value
programmed
in
P2
‐
17.
P2
‐
16
Adjustable
Threshold
1
Upper
Limit
(Analog
Output
1
/
Relay
Output
1)
Minimum
P2
‐
17
Maximum
200
Units
%
Default
100.0
P2
‐
17
Adjustable
Threshold
1
Lower
Limit
(Analog
Output
1
/
Relay
Output
1)
Minimum
0
Maximum
P2
‐
16
Units
%
Default
0.0
Note:
P2
‐
16
and
P2
‐
17
are
used
in
conjunction
with
settings
4
–
7
of
Parameters
P2
‐
11
&
P2
‐
15.
P2
‐
18
User
Relay
2
Output
(Terminals
17
&
18)
Function
select
Minimum
0
Maximum
8
Units
‐
Default
0
Selects
the
function
assigned
to
Relay
Output
2.
The
relay
has
two
output
terminals,
Logic
1
indicates
the
relay
is
active,
and
therefore
terminals
17
and
18
will
be
linked
together.
0
:
Drive
Enabled
(Running)
.
Logic
1
when
the
motor
is
enabled
1
:
Drive
Healthy
.
Logic
1
when
power
is
applied
to
the
drive
and
no
fault
exists
2
:
At
Target
Frequency
(Speed)
.
Logic
1
when
the
output
frequency
matches
the
set
‐
point
frequency
3:
Output
Frequency
>
0.0
Hz
.
Logic
1
when
the
drive
output
frequency
to
the
motor
is
exceeds
0.0Hz
4
:
Output
Frequency
>=
Limit
.
Logic
1
when
the
motor
speed
exceeds
the
adjustable
limit
5
:
Output
Current
>=
Limit
.
Logic
1
when
the
motor
current
exceeds
the
adjustable
limit
6
:
Reserved
.
No
Function
7
:
Analog
Input
2
Signal
Level
>=
Limit
.
Logic
1
when
the
signal
applied
to
the
Analog
Input
2
exceeds
the
adjustable
limit
8
:
Assist
Pump
1
Control
(DOL1)
.
See
section
13.1,
Pump
staging
–DOL
Cascade.
9
:
Fire
Mode
Active.
Logic
1
when
the
drive
in
running
in
Fire
Mode
(Fire
Mode
input
is
active).
10
:
Maintenance
Due.
Logic
1
when
Maintenance
Timer
expires
indicating
that
Maintenance
is
now
due.
11
:
Drive
Available.
Logic
1
when
drive
is
in
Auto
‐
mode,
no
trips
are
present,
and
the
safety
circuit
is
enabled
indicating
that
drive
is
ready
for
automatic
control.
Note:
When
using
settings
4
–
7,
parameters
P2
‐
19
and
P2
‐
20
are
used
to
control
the
output
behaviour.
The
output
will
switch
to
Logic
1
when
the
selected
signal
exceeds
the
value
programmed
in
P2
‐
19,
and
return
to
Logic
0
when
the
signal
falls
below
the
value
programmed
in
P2
‐
20.
P2
‐
19
Adjustable
Threshold
1
Upper
Limit
(Analog
Output
2
/
Relay
Output
2)
Minimum
P2
‐
20
Maximum
200
Units
%
Default
100.0
P2
‐
20
Adjustable
Threshold
1
Lower
Limit
(Analog
Output
2
/
Relay
Output
2)
Minimum
0
Maximum
P2
‐
19
Units
%
Default
0.0
Note:
P2
‐
19
and
P2
‐
20
are
used
in
conjunction
with
settings
4
–
7
of
Parameters
P2
‐
11
&
P2
‐
15.
P2
‐
21
Display
Scaling
Factor
Minimum
0.000
Maximum
30.000
Units
‐
Default
0.000
P2
‐
22
Display
Scaling
Source
Minimum
0
Maximum
2
Units
‐
Default
0
Source
value
used
when
custom
units
are
to
be
shown
on
the
drive
display.
0:
Motor
Speed
1:
Motor
Current
2:
Analog
Input
2
Note:
P2
‐
21
&
P2
‐
22
allow
the
user
to
program
the
Optidrive
display
to
show
an
alternative
output
unit
scaled
from
an
existing
parameter
(for
example,
to
display
conveyer
speed
in
metres
per
second
based
on
the
output
frequency).
This
function
is
disabled
if
P2
‐
21
is
set
to
0.
If
P2
‐
21
is
set
>0,
the
variable
selected
in
P2
‐
22
is
multiplied
by
the
factor
entered
in
P2
‐
21,
and
is
shown
on
the
drive
display
whilst
the
drive
is
running.
P2
‐
23
Zero
Speed
Holding
Time
Minimum
0.0
Maximum
60.0
Units
Seconds
Default
0.2
Determines
the
time
for
which
the
drive
output
frequency
is
held
at
zero
when
stopping,
before
the
drive
output
is
disabled
Summary of Contents for Optidrive HVAC Series
Page 1: ......