Optidrive
ODV
‐
2
User
Guide
Revision
1.00
www.invertek.co.uk
30
P0
‐
24
Operating
Time
Accumulated
With
Ambient
Temperature
Above
80°C
Minimum
0
Maximum
‐
Units
HH:MM:SS
Default
‐
Two
entry
display:
First
display
shows
hours.
Second
display
shows
minutes
and
seconds
Displays
the
amount
of
time
in
hours
and
minutes
that
the
Optidrive
has
operated
for
during
its
lifetime
with
an
ambient
temperature
in
excess
of
80°C.
This
parameter
is
used
by
the
Optidrive
for
various
internal
protection
and
monitoring
functions.
P0
‐
25
Rotor
Speed
(Estimated)
Minimum
‐
Maximum
‐
Units
Hz
Default
‐
Displays
the
estimated
rotor
speed
of
the
motor.
P0
‐
26
Energy
Consumption
kWh
Meter
Minimum
0
Maximum
999.9
Units
kWh
Default
‐
Two
entry
display:
First
display
shows
user
resettable
meter
(reset
with
P6
‐
23).
Second
display
shows
none
resettable
value.
Displays
the
amount
of
energy
consumed
by
the
drive
in
kWh.
When
the
value
reaches
1000,
it
is
reset
back
to
0.0,
and
the
value
of
P0
‐
27
(MWh
meter)
is
increased.
P0
‐
27
Energy
Consumption
MWh
Meter
Minimum
0
Maximum
65535
Units
MWh
Default
‐
Two
entry
display:
First
display
shows
user
resettable
meter
(reset
with
P6
‐
23).
Second
display
shows
none
resettable
value.
Displays
the
amount
of
energy
consumed
by
the
drive
in
MWh.
P0
‐
28
Software
Version
and
Checksum
Minimum
‐
Maximum
‐
Units
‐
Default
‐
Displays
the
software
version
of
the
drive
Four
entry
display:
First
display
–
IO
Version
Second
display
–
IO
Checksum
Third
display
–
DSP
Version
Fourth
display
–
DSP
Checksum
P0
‐
29
Drive
Type
Minimum
‐
Maximum
‐
Units
‐
Default
‐
Displays
the
type
details
of
the
drive
Three
entry
display:
First
display
–
Frame
size
and
input
voltage
level
Second
display
–
Power
rating
Third
display
–
Output
Phase
Count
P0
‐
30
Drive
Serial
Number
Minimum
‐
Maximum
‐
Units
‐
Default
‐
Displays
the
unique
serial
number
of
the
drive.
Dual
entry
display:
First
display
–
Serial
number
(MSB)
Second
display
–
Serial
number
(LMSB)
P0
‐
31
Drive
Lifetime
Operating
Time
Minimum
0
Maximum
‐
Units
HH:MM:SS
Default
‐
Two
entry
display:
First
display
shows
hours.
Second
display
shows
minutes
and
seconds
Displays
the
total
operating
time
of
the
drive.
P0
‐
32
Drive
Run
Time
Since
Last
Trip
(1)
Minimum
0
Maximum
99999H
Units
HH:MM:SS
Default
‐
Two
entry
display:
First
display
shows
hours.
Second
display
shows
minutes
and
seconds
Displays
the
total
operating
time
of
the
drive
since
the
last
fault
occurred.
Run
‐
time
clock
stopped
by
drive
disable
(or
trip),
reset
on
next
enable
only
if
a
trip
occurred.
Reset
also
on
next
enable
after
a
drive
power
down.
P0
‐
33
Drive
Run
Time
Since
Last
Trip
(2)
Minimum
0
Maximum
99999H
Units
HH:MM:SS
Default
‐
Two
entry
display:
First
display
shows
hours.
Second
display
shows
minutes
and
seconds
Displays
the
total
operating
time
of
the
drive
since
the
last
fault
occurred.
Run
‐
time
clock
stopped
by
drive
disable
(or
trip),
reset
on
next
enable
only
if
a
trip
occurred
(under
‐
volts
not
considered
a
trip)
–
not
reset
by
power
down
/
power
up
cycling
unless
a
trip
occurred
prior
to
power
down.
P0
‐
34
Drive
Run
Time
Since
Last
Disable
Minimum
0
Maximum
99999H
Units
HH:MM:SS
Default
‐
Two
entry
display:
First
display
shows
hours.
Second
display
shows
minutes
and
seconds
Displays
the
total
operating
time
of
the
drive
since
the
last
Run
command
was
received.
P0
‐
35
Drive
Internal
Cooling
Fan
Total
Operating
Time
Minimum
0
Maximum
99999H
Units
HH:MM:SS
Default
‐
Displays
the
total
operating
time
of
the
Optidrive
internal
cooling
fans.
Two
entry
display:
First
display
shows
user
resettable
time
(reset
with
P6
‐
22).
Second
display
shows
none
resettable
time.
This
is
used
for
scheduled
maintenance
information
P0
‐
36
DC
Bus
Voltage
Log
(256ms)
Minimum
‐
Maximum
‐
Units
‐
Default
‐
Diagnostic
log
for
DC
bus
voltage.
Values
logged
every
256mS
with
8
samples
total.
Logging
suspended
on
drive
trip.
P0
‐
37
DC
Bus
Voltage
Ripple
Log
(20ms)
Minimum
‐
Maximum
‐
Units
‐
Default
‐
Diagnostic
log
for
DC
bus
voltage
ripple.
Values
logged
every
20mS
with
8
samples
total.
Logging
suspended
on
drive
trip.