Optidrive E2 Single Phase Output User Guide V3.10

 

 

www.invertekdrives.com 

20

 

 

Pa
ra

m

e

ter

6

 

Par. 

Description 

Minimum 

Maximum 

Default 

Units 

P-30 

Terminal Mode Restart function 

N/A 

N/A 

Auto-0 

Defines the behaviour of the drive relating to the enable digital input and also configures the Automatic Restart function. 



 : Following Power on or reset, the drive will not start if Digital Input 1 remains closed. The Input must be closed after a power 

on or reset to start the drive. 



 : Following a Power On or Reset, the drive will automatically start if Digital Input 1 is closed. 



 to 



 : Following a trip, the drive will make up to 5 attempts to restart at 20 second intervals. The drive must be 

powered down to reset the counter

The numbers of restart attempts are counted, and if the drive fails to start on the final attempt, 

the drive will fault with, and will require the user to manually reset the fault. 

P-31 

Keypad / Modbus Mode Restart Function 

This parameter is active only when operating in Keypad Control Mode (P-12 = 1 or 2) or Modbus Mode (P-12 = 3 or 4). When settings 
0 or 1 are used, the Keypad Start and Stop keys are active, and control terminals 1 and 2 must be linked together. Settings 2 and 3 
allow the drive to be started from the control terminals directly, and the keypad Start and Stop keys are ignored. 
Settings 0 and 2 : The drive will always start at the Minimum Frequency / Speed (P-02) 
Settings 1 and 3 : The drive will always start at the last operating Frequency / Speed 

0 : Minimum Speed, Keypad Start 
1 : Previous Speed, Keypad Start 
2 : Minimum Speed, Terminal Enable 
3 : Previous Speed, Terminal Enable

 

P-32 

Starting Boost Frequency 

0.0 

P-09 

P-09 

Hz 

Sets the frequency used during the starting boost phase of operation refer to section 0 for further information. 

P-33 

Boost Period Duration 

0.0 

150 

5.0 

Time for which the start-up boost period is applied.  During this period, the output frequency is set to P-32 and the voltage increases 
linearly from P-11 to P-07.  Setting P-33 to zero disables boost. See section 0 for additional information. 

P-34 

Brake Chopper Enable 

0 : Disabled 
1 : Enabled With Software Protection

. Enables the internal brake chopper with software protection for a 200W continuous rated 

resistor 

2 : Enabled Without Software Protection

. Enables the internal brake chopper without software protection. An external thermal 

protection device should be fitted. 

P-35 

Analog Input 1 Scaling 

0.0 

500.0 

100.0 

Scales the analog input by this factor, e.g. if P-16 is set for a 0 – 10V signal , and the scaling factor is set to 200.0%, a 5 volt input will 
result in the drive running at maximum frequency / speed (P-01) 

P-36 

Serial Communications Configuration 

See Below 

This parameter has three sub settings used to configure the Modbus RTU Serial Communications. The Sub Parameters are 

1st Index : Drive Address

 : Range 



 0 - 63 

2

nd

 Index : Protocol & Baud Rate

 : Setting 



 (factory default setting) disables Modbus communications, and allows the Optistick 

to be used with the drive. Selecting a baud rate between 9.6kbps to 115.2kbps allows Modbus communication, but disables the 
operation of the Optistick. 

3

rd

 Index : Watchdog Timeout

 : Defines the time for which the drive will operate without receiving a valid command telegram to 

Register 1 (Drive Control Word) after the drive has been enabled. Setting 0 disables the Watchdog timer. Setting a value of 30, 100, 
1000, or 3000 defines the time limit in milliseconds for operation. A ‘

’ suffix selects trip on loss of communication. An ‘

’ suffix 

means that the drive will coast stop (output immediately disabled) but will not trip. 

P-37 

Access Code Definition 

9999 

101 

Defines the access code which must be entered in P-14 to access parameters above P-14 

P-38 

Parameter Access Lock 

0 : Unlocked

. All parameters can be accessed and changed 

1 : Locked

. Parameter values can be displayed, but cannot be changed 

P-39 

Analog Input 1 Offset 

-500.0 

500.0 

0.0 

Sets an offset, as a percentage of the full scale range of the input, which is applied to the analog input signal 

P-40 

Display Speed Scaling Factor 

0.000 

6.000 

0.000 

Allows the user to program the Optidrive to display an alternative output unit scaled from the output frequency or speed, e.g. to 
display conveyer speed in metres per second. This function is disabled if P-40 = 0.00 

P-41 

PI Controller Proportional Gain 

0.0 

30.0 

1.0 

PI Controller Proportional Gain. Higher values provide a greater change in the drive output frequency in response to small changes in 
the feedback signal. Too high a value can cause instability 

P-42 

PI Controller Integral Time 

0.0 

30.0 

1.0 

PI Controller Integral Time. Larger values provide a more damped response for systems where the overall process responds slowly 

P-43 

PI Controller Operating Mode 

0 : Direct Operation

. Use this mode if an increase in the motor speed should result in an increase in the feedback signal 

1 : Inverse Operation

. Use this mode if an increase in the motor speed should result in a decrease in the feedback signal 

P-44 

PI Reference (Setpoint) Source Select 

Selects the source for the PID Reference / Setpoint 

0 : Digital Preset Setpoint

. P-45 is used 

1 : Analog Input 1 Setpoint 
 

P-45 

PI Digital Setpoint 

0.0 

100.0 

0.0 

Summary of Contents for ODE-2-11005-1H012-01

Page 1: ...ase Output User Guide V3 10 User Guide Single Phase Output AC Variable Speed Drive for PSC Shaded Pole Single Phase Motors 0 37 1 1kW 0 5 1 5HP IP20 Open IP66 Nema 4X Enclosed Units Installation and O...

Page 2: ...gs out of the box 1 Connect a START STOP switch from Terminal 1 to 2 Close the contact START enable the drive Open the contact STOP the drive 2 Connect a 10k potentiometer on terminal 5 6 7 to vary th...

Page 3: ...h is set to the REV position set parameter value in P 15 Check page 15 for configuring the FWD REV switch for Local Remote Hand off Auto applications Local Power Isolator with Lock off provision Fuses...

Page 4: ...motor switching frequency motor cable lengths and installation methods adopted Note For shielded motor cable lengths greater than 100m and up to 200m an output dv dt filter must be used please refer t...

Page 5: ...Wiring 13 4 7 Connection Diagram IP20 Open IP66 Nema 4X Non Switched Units 14 4 8 Connection Diagram IP66 Nema 4X Switched Units 14 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 15 4...

Page 6: ...Do not carry out any work on the drive control cables whilst power is applied to the drive or to the external control circuits Within the European Union all machinery in which this product is used mu...

Page 7: ...0 1 Phase Input kW Model Number kW HP Model Number HP Output Current A Frame Size With Filter Without Filter With Filter Without Filter ODE 2 12037 1KB12 01 ODE 2 12037 1K012 01 0 37 ODE 2 12005 1HB12...

Page 8: ...162 6 38 5 0 20 123 4 84 82 3 23 50 1 97 5 5 0 22 10 0 39 1 2 2 2 221 8 70 207 8 15 137 5 39 209 8 23 5 3 0 21 150 5 91 109 4 29 63 2 48 5 5 0 22 10 0 39 1 7 3 8 Mounting Bolts All Frame Sizes 4 x M4...

Page 9: ...s 1 Nm 8 85 lb in 3 7 Guidelines for mounting IP66 Units Before mounting the drive ensure that the chosen location meets the environmental condition requirements for the drive shown in section 9 1 The...

Page 10: ...pe For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for rigid conduit system Power Isolator Lock Off On the switched...

Page 11: ...t 3 11 1 IP66 Nema 4X Switched Unit 3 11 2 IP66 Nema 4X Non Switched Unit Drive LED Display Keypad Local Speed Potentiometer A REV 0 FWD Selector Switch B Local Power Isolator Removable Cover Control...

Page 12: ...must comply with national and local industrial safety regulations and or electrical codes Motor Ground The motor ground must be connected to one of the ground terminals on the drive Ground Fault Monit...

Page 13: ...operation with a variable speed drive then there is no preventative measures required however if the quality of insulation is unknown then the motor manufacturer should be consulted and preventative m...

Page 14: ...2 Default No Function 4 Digital Input 3 Default Analog Preset Speed 5 10 Volt Output 6 Analog Input 1 Default 0 10 Volt 7 0 Volt 8 Analog Output Default 0 10 Volts 9 0 Volt 10 Relay Output Default Dri...

Page 15: ...I Control 5 1 In Speed Control the speed is controlled from the Local POT In PI Control Local POT controls PI set point Run in Preset Speed Control STOP Run in PI Control 5 0 2 4 5 8 12 In Preset Spee...

Page 16: ...will show 4 Close the control switch terminals 1 2 The drive is now enabled and the output frequency speed are controlled by the potentiometer The display shows zero speed in Hz with the potentiometer...

Page 17: ...et the Boost Period Duration P 33 to the maximum allowed value of 150 seconds 5 Start the drive and display the motor current press the Navigate button until the display shows x x where x is the motor...

Page 18: ...en set to the default value of zero all speed related parameters are displayed in Hz and the slip compensation for the motor is disabled Entering the value from the motor nameplate enables the slip co...

Page 19: ...pm P 22 Preset Frequency Speed 3 P 02 P 01 0 0 Hz Rpm P 23 Preset Frequency Speed 4 P 02 P 01 0 0 Hz Rpm Preset Speeds Frequencies selected by digital inputs depending on the setting of P 15 If P 10 0...

Page 20: ...a 0 10V signal and the scaling factor is set to 200 0 a 5 volt input will result in the drive running at maximum frequency speed P 01 P 36 Serial Communications Configuration See Below This parameter...

Page 21: ...nce between the setpoint and feedback for which the drive will remain in Standby Mode This allows the drive to ignore small feedback errors and remain in Standby mode until the feedback drops sufficie...

Page 22: ...uency This value maybe lower than the selected frequency in P 17 if the drive is too hot The drive will automatically reduce the switching frequency to prevent an over temperature trip and maintain op...

Page 23: ...ence Connect external motor thermistor PTC type or similar to digital input 3 7 Open Stop disable Closed Run enable Open Run Closed Fast Stop External trip input Open Trip Closed Run Analog input 1 re...

Page 24: ...orward Run Open Run Closed Fast Stop External trip input Open Trip Closed Run Open Keypad speed ref 24V Preset speed 1 Close digital input 3 to carry out a fast stop P 24 provided P 05 0 Example Wirin...

Page 25: ...Run Enable Run Enable Run Enable PI Preset Speed 1 PI Local Hand PI Preset Speed 1 PI Feedback PI Feedback External Trip 10 Volt Local Hand Ref PI Feedback 0 Volt 0 Volt 0 Volt Remote closed loop PI f...

Page 26: ...ress 2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2 nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Checksum 2 Bytes CRC Ch...

Page 27: ...s for 230 Volt rated units 10 variation allowed 240 Volt RMS Maximum Imbalance Maximum 3 voltage variation between phase phase voltages allowed All Optidrive E2 units have phase imbalance monitoring A...

Page 28: ...eration time reduce load inertia or add further brake resistors in parallel Ensure minimum resistance values form the rating tables are observed Internal power stage fault Check wiring to motor look f...

Reviews: