background image

Optidrive E2 Single Phase Output User Guide V3.10 

21 

www.invertekdrives.com 

 

 

Pa

ra

m

e

ter

6

 

Par. 

Description 

Minimum 

Maximum 

Default 

Units 

When P-44 = 0, this parameter sets the preset digital reference (setpoint) used for the PI Controller 

P-46 

PI Feedback Source Select 

0 : Analog Input 2

 (Terminal 4) 

1 : Analog Input 1

 (Terminal 6) 

2 : Motor Current

 

3 : DC Bus Voltage

 Scaled 0 – 1000 Volts = 0 – 100% 

4 : Analog 1 – Analog 2

. The value of Analog Input 2 is subtracted from Analog 1 to give a differential signal. The value is limited to 0. 

5 : Largest (Analog 1, Analog 2)

. The largest of the two analog input values is always used for PI feedback 

P-47 

Analog Input 2 Signal Format 

N/A 

N/A 

N/A 

U0-10 



 = 0 to 10 Volt Signal 



 = 0 to 20mA Signal 



 =  4 to 20mA Signal, the Optidrive will trip and show the fault code 



 if the signal level falls below 3mA 



 = 4 to 20mA Signal, the Optidrive will ramp to stop if the signal level falls below 3mA 



 = 20 to 4mA Signal, the Optidrive will trip and show the fault code 



 if the signal level falls below 3mA 



 = 20 to 4mA Signal, the Optidrive will ramp to stop if the signal level falls below 3mA 

P-48 

Standby Mode Timer 

0.0 

250.0 

0.0 

When standby mode is enabled, the drive will enter standby mode following a period of operating at minimum speed (P-02) for the 
time set in P-48. When in Standby Mode, the drive display shows 



, and the output to the motor is disabled. 

Standby mode can be disabled by setting P-48 = 0.0 

P-49 

PI Control Wake Up Error Level 

0.0 

100.0 

0.0 

When the drive is operating in PI Control Mode (P-12 = 5 or 6), and Standby Mode is enabled (P-48 > 0.0), P-49 can be used to define 
the PI Error Level (E.g. difference between the setpoint and feedback) for which the drive will remain in Standby Mode. This allows 
the drive to ignore small feedback errors and remain in Standby mode until the feedback drops sufficiently. 

P-50 

Thermal Overload Value Retention 

0 : Disabled. 
1 : Enabled

. All Optidrives feature electronic thermal overload protection for the connected motor, designed to protect the motor 

against damage. An internal overload accumulator monitors the motor output current over time, and will trip the drive if the usage 
exceeds the thermal limit. When P-50 is disabled, removing the power supply from the drive and re-applying will reset the value of 
the accumulator. When P-50 is enabled, the value is retained during power off. 

 

 

6.3.

 

Adjusting the Voltage / Frequency (V/f) characteristics 

Volt

age

 

 

The V/f characteristic is defined by several parameters as follows :- 
P-07 : Motor Rated Voltage 
P-09 : Motor Rated Frequency 
The voltage set in parameter P-07 is applied to the motor at the frequency set Under 
normal operating conditions, the voltage is linearly reduced at any point below the 
motor rated frequency to maintain a constant motor torque output as shown by the 
line ‘A’ on the graph. 
By using parameters P-28 and P-29, the voltage to be applied at a particular frequency 
can be directly set by the user, thereby altering the V/F characteristic. 
Reducing the voltage at a particular frequency reduces the current in the motor and 
hence the torque and power, hence this function can be used in fan and pump 
applications where a variable torque output is desired by setting the parameters as 
follows :- 
P-28 = P-07 / 4 
P-29 = P-09 / 2 
This function can also be useful if motor instability is experienced at certain 
frequencies, if this is the case increase or decrease the voltage (P-28) at the speed of 
instability (P-29). 

 

Frequency 

 
 

 

 

Summary of Contents for ODE-2-11005-1H012-01

Page 1: ...ase Output User Guide V3 10 User Guide Single Phase Output AC Variable Speed Drive for PSC Shaded Pole Single Phase Motors 0 37 1 1kW 0 5 1 5HP IP20 Open IP66 Nema 4X Enclosed Units Installation and O...

Page 2: ...gs out of the box 1 Connect a START STOP switch from Terminal 1 to 2 Close the contact START enable the drive Open the contact STOP the drive 2 Connect a 10k potentiometer on terminal 5 6 7 to vary th...

Page 3: ...h is set to the REV position set parameter value in P 15 Check page 15 for configuring the FWD REV switch for Local Remote Hand off Auto applications Local Power Isolator with Lock off provision Fuses...

Page 4: ...motor switching frequency motor cable lengths and installation methods adopted Note For shielded motor cable lengths greater than 100m and up to 200m an output dv dt filter must be used please refer t...

Page 5: ...Wiring 13 4 7 Connection Diagram IP20 Open IP66 Nema 4X Non Switched Units 14 4 8 Connection Diagram IP66 Nema 4X Switched Units 14 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 15 4...

Page 6: ...Do not carry out any work on the drive control cables whilst power is applied to the drive or to the external control circuits Within the European Union all machinery in which this product is used mu...

Page 7: ...0 1 Phase Input kW Model Number kW HP Model Number HP Output Current A Frame Size With Filter Without Filter With Filter Without Filter ODE 2 12037 1KB12 01 ODE 2 12037 1K012 01 0 37 ODE 2 12005 1HB12...

Page 8: ...162 6 38 5 0 20 123 4 84 82 3 23 50 1 97 5 5 0 22 10 0 39 1 2 2 2 221 8 70 207 8 15 137 5 39 209 8 23 5 3 0 21 150 5 91 109 4 29 63 2 48 5 5 0 22 10 0 39 1 7 3 8 Mounting Bolts All Frame Sizes 4 x M4...

Page 9: ...s 1 Nm 8 85 lb in 3 7 Guidelines for mounting IP66 Units Before mounting the drive ensure that the chosen location meets the environmental condition requirements for the drive shown in section 9 1 The...

Page 10: ...pe For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for rigid conduit system Power Isolator Lock Off On the switched...

Page 11: ...t 3 11 1 IP66 Nema 4X Switched Unit 3 11 2 IP66 Nema 4X Non Switched Unit Drive LED Display Keypad Local Speed Potentiometer A REV 0 FWD Selector Switch B Local Power Isolator Removable Cover Control...

Page 12: ...must comply with national and local industrial safety regulations and or electrical codes Motor Ground The motor ground must be connected to one of the ground terminals on the drive Ground Fault Monit...

Page 13: ...operation with a variable speed drive then there is no preventative measures required however if the quality of insulation is unknown then the motor manufacturer should be consulted and preventative m...

Page 14: ...2 Default No Function 4 Digital Input 3 Default Analog Preset Speed 5 10 Volt Output 6 Analog Input 1 Default 0 10 Volt 7 0 Volt 8 Analog Output Default 0 10 Volts 9 0 Volt 10 Relay Output Default Dri...

Page 15: ...I Control 5 1 In Speed Control the speed is controlled from the Local POT In PI Control Local POT controls PI set point Run in Preset Speed Control STOP Run in PI Control 5 0 2 4 5 8 12 In Preset Spee...

Page 16: ...will show 4 Close the control switch terminals 1 2 The drive is now enabled and the output frequency speed are controlled by the potentiometer The display shows zero speed in Hz with the potentiometer...

Page 17: ...et the Boost Period Duration P 33 to the maximum allowed value of 150 seconds 5 Start the drive and display the motor current press the Navigate button until the display shows x x where x is the motor...

Page 18: ...en set to the default value of zero all speed related parameters are displayed in Hz and the slip compensation for the motor is disabled Entering the value from the motor nameplate enables the slip co...

Page 19: ...pm P 22 Preset Frequency Speed 3 P 02 P 01 0 0 Hz Rpm P 23 Preset Frequency Speed 4 P 02 P 01 0 0 Hz Rpm Preset Speeds Frequencies selected by digital inputs depending on the setting of P 15 If P 10 0...

Page 20: ...a 0 10V signal and the scaling factor is set to 200 0 a 5 volt input will result in the drive running at maximum frequency speed P 01 P 36 Serial Communications Configuration See Below This parameter...

Page 21: ...nce between the setpoint and feedback for which the drive will remain in Standby Mode This allows the drive to ignore small feedback errors and remain in Standby mode until the feedback drops sufficie...

Page 22: ...uency This value maybe lower than the selected frequency in P 17 if the drive is too hot The drive will automatically reduce the switching frequency to prevent an over temperature trip and maintain op...

Page 23: ...ence Connect external motor thermistor PTC type or similar to digital input 3 7 Open Stop disable Closed Run enable Open Run Closed Fast Stop External trip input Open Trip Closed Run Analog input 1 re...

Page 24: ...orward Run Open Run Closed Fast Stop External trip input Open Trip Closed Run Open Keypad speed ref 24V Preset speed 1 Close digital input 3 to carry out a fast stop P 24 provided P 05 0 Example Wirin...

Page 25: ...Run Enable Run Enable Run Enable PI Preset Speed 1 PI Local Hand PI Preset Speed 1 PI Feedback PI Feedback External Trip 10 Volt Local Hand Ref PI Feedback 0 Volt 0 Volt 0 Volt Remote closed loop PI f...

Page 26: ...ress 2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2 nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Checksum 2 Bytes CRC Ch...

Page 27: ...s for 230 Volt rated units 10 variation allowed 240 Volt RMS Maximum Imbalance Maximum 3 voltage variation between phase phase voltages allowed All Optidrive E2 units have phase imbalance monitoring A...

Page 28: ...eration time reduce load inertia or add further brake resistors in parallel Ensure minimum resistance values form the rating tables are observed Internal power stage fault Check wiring to motor look f...

Reviews: