Page 38
Test Run
Before Test Run
A test run must be performed after the entire
system has been completely installed. Confirm
the following points before performing the test:
a) Indoor and outdoor units are properly
installed.
b) Piping and wiring are properly connected.
c)
No obstacles near the inlet and outlet of
the unit that might cause poor performance
or product malfunction.
d) Refrigeration system does not leak.
e) Drainage system is unimpeded and
draining to a safe location.
f) Heating insulation is properly installed.
g) Grounding wires are properly connected.
h) Length of the piping and additional
refrigerant stow capacity have been
recorded.
i) Power voltage is the correct voltage
for the air conditioner.
Failure to perform the test run may result in
unit damage, property damage, or personal
injury.
Test Run Instructions
1. Open both the liquid and gas stop valves.
2. Turn on the main power switch and allow the
unit to warm up.
3. Set the air conditioner to COOL mode.
4. For the Indoor Unit
a. Ensure the remote control and its buttons
work properly.
b. Ensure the louvers move properly and can
be changed using the remote control.
c. Double check to see if the room
temperature is being registered correctly.
d. Ensure the indicators on the remote
control and the display panel on the indoor
unit work properly.
e. Ensure the manual buttons on the indoor
unit works properly.
f. Check to see that the drainage system is
unimpeded and draining smoothly.
g. Ensure there is no vibration or abnormal
noise during operation.
5. For the Outdoor Unit
a. Check to see if the refrigeration system is
leaking.
b. Make sure there is no vibration or
abnormal noise during operation.
c. Ensure the wind, noise, and water
generated by the unit do not disturb your
neighbors or pose a safety hazard.
6. Drainage Test
a. Ensure the drainpipe flows smoothly. New
buildings should perform this test before
finishing the ceiling.
b. Remove the test cover. Add 2,000ml of
water to the tank through the attached
tube.
c. Turn on the main power switch and run
the air conditioner in COOL mode.
d. Listen to the sound of the drain pump to
see if it makes any unusual noises.
e. Check to see that the water is discharged.
It may take up to one minute before the
unit begins to drain depending on the
drainpipe.
f. Make sure that there are no leaks in any of
the piping.
g. Stop the air conditioner. Turn off the main
power switch and reinstall the test cover.
NOTE:
If malfunction occurs, or the unit does
not operate according to your expectations,
please refer to the Troubleshooting section
of the Owner’s Manual before calling for
customer service.
CAUTION
All the pictures in the manual are for explanatory purposes only. The actual shape of the unit
you purchased may be slightly different, but the operations and functions are the same.
The company may not be held responsible for any misprinted information. The design and
the specifications of the product for reasons, such as product improvement, are subject to
change without any prior notice.
Please consult with the manufacturer at +30 211 300 3300 or with the Sales agency for further
details. Any future updates to the manual will be uploaded to the service website, and it is
advised to always check for the latest version.
Scan here to download the latest version of this manual.
www.inventorairconditioner.com/media-library
Summary of Contents for V5MFI-66
Page 41: ...43 47 1 47 2 47 3 48 49 54 56...
Page 43: ...43 server 8...
Page 44: ...44 3mm...
Page 46: ...46 R32 R290 R32 X m X m 3g 25 UL IEC ISO 14903 Btu h kg m m 48000 3 0 0 6 m 80...
Page 49: ...49 1 2 3 4 5 ON OFF MODE FAN FUNC...
Page 51: ...51 Fan speed Fan speed display LOW 1 MED 2 HIGH 3 AUTO HIGH MED LOW LOW MED HIGH AUTO...
Page 53: ...53 LOCK 5 FUN oder FUN...
Page 54: ...54 40 C 104 F 2...
Page 55: ...55 EC FAN...
Page 56: ...56 ON OFF 3 3 FAN FAN...
Page 57: ...57...
Page 58: ...58 3 3 10 E x P x F x EH xx EL xx EC xx PH xx PL xx PC xx...
Page 60: ...60 MC MC L N 1 2 3 4 5 6...
Page 61: ...61 1 7 8 9 10 2 3 4 5 6 1 2 3 4 5 6 7 10 9 8...
Page 62: ...62 1 o o o o o o 1 c x x x x 5cm 2in 200cm 78 7 in 30cm 11 8in 50cm 19 7 in 50cm 19 7 in...
Page 63: ...63 3 2 1 2 3 4 3 1 2 4 1 2 M8 3 5 1 2 3 6 1 2...
Page 64: ...64 7 1 2 3 8 1 2 65mm 1cm 0 4 67 57 4 67 4...
Page 65: ...65 1 2 PVC 26mm 3 0 03 9mm 4 5 6 3 9 5cm S U 0 5 1cm 0 2 0 4 inch 3 7 3 9cm 3 2cm...
Page 72: ...72 1 2 3 4 90 100 5 1 5 6 1 8in 3mm 7 8 9 10 1 40in 11 12 10 13 14 32ohms 15 16...
Page 74: ...74 b 15cm 6in c d 2 3 4 5 6 2 1 a 15cm 6in b c 2 3 4 5 Abgedeckt Impressum...
Page 75: ...75 76cmHg o o 1 2 3 4 5 15 76cmHG 105Pa 6 7 5 8 9 1 4 5 10 11 12 13 76cmHg...
Page 77: ...77 a b c d e f g h i 1 2 3 4 a b c d e f g 5 a b c 6 a b 2 000ml c d e f g...
Page 78: ...211 300 3300 www inventoraircondition gr media library...
Page 158: ...NOTES...
Page 159: ......