Only use median sponge to entwine the wiring interface of the gas pipe and heat preservation
sheath of the gas collection tube.
G
、
Drainage hose
1. Install the drain hose
☆
The diameter of the drain hose should be equal or bigger than the connection pipe’s. ( The
diameter of polythene pipe: Outer diameter 25mm Surface thickness
≥
1.5mm)
☆
Drain hose should be short and drooping gradient should at less 1/100 to prevent the formation of
air bubble.
☆
If drain hose cannot has enough drooping gradient, drain raising pipe should be added.
☆
To prevent bent of the drain hose, the distance between hoisting stand should is 1 to 1.5m.
×
(wrong)
○
(Correct) 1/100 or more gradient
1-1.5m
☆
Use the drain hose and clamp attached. Insert
the drain hose to the drain vent, and then tighten
the clamp.
Below 4mm
Sponge(attachment)
Clamp(attachment)
Clamp
Drain hose
Sponge (gray)
☆
Entwine the big sponge on the clamp of drain
hose to insulate heat.
☆
Heat insulation should be done to indoor drain
hose.
●
Note of drain step up pipe
☆
The install height of the drain raising pipe should less than 280mm.
☆
The drain raising pipe should form a right angle with the unit, and distance to unit should not
beyond 300mm.
43
Summary of Contents for ICI-12
Page 1: ...66129903850 ICI 18 ICI 24 ICI 36 ICI 45 ICI 50 Casette Unit ICI 12...
Page 3: ...1 Names and functions of parts 1 ULS 12 ULS 18 ULS 24 ICI 18 ICI 24 ICI 12...
Page 4: ...2 ULS 36 ICI 36 ULT 36 ICI 36 ULT 45 ICI 45 ULT 50 ICI 50...
Page 22: ...TIMER operation procedure 20...
Page 24: ...How to inser t batteries 22...
Page 35: ...6 Optimum operation 33...
Page 37: ...The following are not troubles 35...
Page 38: ...8 Installation notes This should be done by professional 36...
Page 39: ...9 Care and maintenance Please cut off the power supply after you used the air conditioner 37...
Page 63: ......