31
7.2.5.2.3.3. Output mode
Function
-
selection of binary output mode
Data type
- selection
list
List
-
Monostable
binary output is set for time given by Pulse duration
parameter
Bistable
state of output is defined by user
Default
value
-
Monostable
Comments
- n/a
7.2.5.2.3.4. Pulse duration
Function
-
defines length (in seconds) of impulse on binary output in
monostable output mode
Data type
- number
Range
- 0…360.00
Default
value
- 0.10
Comments
- n/a
7.2.5.2.4. Analogue inputs A1…A8
Modules
MT-304
and
MT-301
are equipped with respectively one and two analogue
inputs operating in 4-20mA standard.
Number of analogue inputs of MT-301 can be multiplied up to eight by using external
analogue inputs multiplexer.
7.2.5.2.4.1. Name
Function
-
Enables entering friendly name of input e.g. connected to
the function performed. The name is displayed on terminals
list.
Data type
- text
Range
-
letters and numerals, max.16 characters
Default
value
-
Name of resource (A1, A2, A3(MUX), …, A8(MUX))
Comments
-
Using friendly names facilitates recognition of destination
and appropriate settings.
7.2.5.2.4.2. Operation mode
Function
-
defines analogue inputs operating mode
Data type
- selection
list
Range
-
Analogue input
the input operates as 4-20 mA standard input
Default
value
-
Analogue input
Comments
-
Parameter preserved for legacy support, not important for
operating analogue inputs