MANUAL DE USUARIO INVERSOR TECA LITIO / USER MANUAL INVERSOR TECA
LITIO
29
Low DC cut off voltage
The default value is 10,0V while the rage is from 10,0V to 12V for 12V systems (*2 @ 24V,
*4 @ 48V).
The increase per click is 0,1V for 12V systems (*2 @ 24V, *4 @ 48V).
93
Frequency range
Special 40-70hz
General 50Hz: 45 -55Hz; 60Hz: 55 – 65Hz
94
Battery type selection
Lithium battery
If selected, the battery charging voltage and the battery
low charging voltage can be set up to 26,27V.
Other battery
If selected, the battery charging voltage can be set to
26,27V.
95
High battery voltage
It happens when the dry contact changes from NC to NO and the battery voltage reached
the set up one. This setting cannot be higher than the fast charging voltage. The setup
range is from 13,0V to 15,5V for 12V (*2@24V, *4@48V). The increase per click is 0,1V for
12V systems (*2@24V, *4@48V).
96
Low battery voltage
It appears when the battery voltage reaches to the setup point and the dry contact changes
from NC to NO. This setting cannot be lower than the low battery voltage cut off point. The
setup range is from 10,5V to 12,5V for 12V (*2@24V, *4@48V). The increase per click is
0,1V for 12V systems (*2@24V, *4@48V).
97
Dry contact control
If the inverter is set in dcd, the dry contact function is disables and 95 and 96 cannot be set
up in the program
If the inverter is set in dce, the dry contact function is enabled, 95 and 06 can be set up in
the program.
98
Low battery alarm
Default value is 10.5V.
The setup range is from 10.5V to 12,5V for 12V (*2@24V, *4@48V). If the shutdown voltage
set by the user is lower than the default one, the new default voltage will be sh
0,5V.
The increase per click is 0,1V for 12V systems (*2@24V, *4@48V).
99
Output voltage setting
The output default voltage is 230V / 120V. The setup range is from 200V/100V to
240V/120V.
FAULT CODES
Warning
code
Event
Icon
03
Battery voltage overcharge.
04
Low
battery voltage.
05
Inverter overtemperature.
07
Overload of the inverter
88
Reversal transformer phase.
89
Frequency is out of range.
97
The inverter fails to connect to the MPPT
controller.
Fault code
Event
Icon
02
Overtemperature on the heats sink.
03
Too high battery voltage.
04
Too low battery voltage.
05
Output short-circuit.
06
Too high or too low output.
07
Overload.
99
Inverter fails to slow start.