SEPAMAT F-SC_Manual_Vers.1.0e_en
16
Code
LED-
Display
Function
Description
Range
Default
setting
F12
Pressure sensor
operating range
Setting for the operating
range of the pressure
sensor
10..20 bar
Each step:
0.5 bar
16 bar
F13
Proportional
P.I.D.
Factor
Setting for proportional
factor in P.I.D.
(Proportional-Integral-
Derivative) for pressure
control
0..6000
Each step: 300
3000
F14
Integral P.I.D.
Factor
Setting for integral factor in
P.I.D. (Proportional-Integral-
Derivative) for pressure
control
0..4000
Each step: 200
1000
F15
Minimum flow
time delay
Setting for time delay on the
minimum flow condition
before stopping pump.
2..20 sec
Each step:
1 sec
12 sec
F16
Dry running
time delay
Setting for time delay on the
dry running condition before
stopping pump.
10..100 sec
Each step:
5 sec
40 sec
F17
Master-Slave
group
communication
Operating mode with 1, 2 or
3 pumps with Bluetooth
connection, factory setting
for 2 pump system that also
functions for single pump
mode
1: one pump
2: two pumps
MASTER/SLAV
E
3: three pumps
MASTER/SLAV
E
2
F18
Setting check
Refers to the graph of the
power consumption
0: theoretical
curve
1: self-
initialization
2: tested curve
1
F19
Measurements
Measures of different
parameters
0: Pressure
(0..10)
1: Frequency
(15..55)
2: Current
(0..10)
3: Voltage (200-
.240)
4: T [°C]
(70..90)
5: Last alarm
6: Motor
Δ
T[°C](0..100)
0
F20
Frequency
transmission
Frequency of transmission/
reception of the radio
communication between 2
or 3 controllers
780 .. 820 MHz
Each step: 1
MHz
800 MHz