6
2.3 Effluent
quality
The required and final tested treated effluent quality according to NSF/ANSI 350-2014 listed in the table
below:
Measure Class
C
requirement
Class C
AQUALOOP Test result NSF approval
Measure Test
Average
Single
Sample
Maximum
Result
Average
Single
Sample Maximum
CBOD (mg/L)
10
25
5
17
TSS (mg/L)
10
30
2
7,8
turbidity (NTU)
2
5
0,57
3,89
E. coli 2 (MPN/100 mL)
2,2
200
1,0
13,0
pH (SU)
6.0 – 9.0
NA1
7,38
NA1
color
MR3 NA MR3 NA
odor
Non offensive
NA
Non offensive
NA
oily film and foam
Non-detectable
Non-detectable
Non-detectable
Non-detectable
1
NA: not applicable.
2
Calculated as geometric mean.
3
MR: measured and reported only.
2.4 Certification NSF/ANSI 350 -2014
Model designations:
AQUALOOP System GW 0300 L
AQUALOOP System GW 0600 L
AQUALOOP System GW 0900 L
AQUALOOP System GW 1200 L
AQUALOOP System GW 1500 L
AQUALOOP System GW 1800 L
The model designations are tested to meet the requirements in NSF/ANSI 350 corresponding to the
designated classification:
Number and Date of NSF/ANSI Standard:
NSF/ANSI 350-2014
Onsite residential and commercial water reuse
treatment Systems
Certificate No.:
C0241944 - 01
Class of grey water input:
Combined, bathing and laundry water effluent
Class of treated water output:
Class C, multi-family and commercial facilities
Performance classification,
(nominal hydraulic
d
aily flow)
AQUALOOP System GW 0300 L = 300 Litres / day
AQUALOOP System GW 0600 L = 600 Litres / day
AQUALOOP System GW 0900 L = 900 Litres / day
AQUALOOP System GW 1200 L = 1200 Litres / day
AQUALOOP System GW 1500 L = 1500 Litres / day
AQUALOOP System GW 1800 L = 1800 Litres / day
NSF Product and Service Listings see link below:
http://info.nsf.org/Certified/Wastewater/Listings.asp?TradeName=&Standard=350