29
Menu 5: Status overview
(Status Overview: Status 1 to 4)
The overview mode can be viewed at any time. All other activities, such as aeration mode and
pump frequency, continue in the background. All current settings and operating status can
be viewed in this mode.
Status 1:
Number of membranes:
MEM
: 1
Aeration settings (230 + 24V) AIR ON/OFF : 5 / 10 min
Suction overflow:
Overflow
: 1 week
Status 2:
Sludge pump (days/min):
SLP
: 5 / 20
Pressure sensor Pumps:
P(ADr)
: -0,23 bar
Pressure sensor blower:
P(ADg)
: -0,05 bar
Status 3:
Voltage power supply :
Supply
: 23,3 V
Battery voltage:
9V battery
: 9,55 V -L-
Software version:
Firmware
: GWA2.21
Status 4:
Number of current interruptions in 24 V supply):
Supply : 11
Number of current interruptions (24 V) with pump frequency:
during pumping: 0
Aeration 24 V :
24V-OUTPUT: Air
or
filter back flush (24v)
Filter: 60s/ 5d
Menu 6: Setting time
The set time is critical for pump start times T1 and T2. The clock will operate for approx. 3
hours on battery life in the event of a power failure. Thereafter, the capacity of the battery is
exhausted (Display switches off). When the external AC switching power supply comes on
again after a battery run down, the clock must be re-set in order to correctly restart the cycle
times T1 and T2 corresponding to real time.
Note:
A started pumping cycle is terminated independent of the corrected time.
The time can be adjusted at any time.
Menu 7/8: Start time T1 and T2
(Starting time point T1 and T2 for pumping cycle)
Note for selection of start times:
The pump starting times are primarily set according to the times of incoming grey water
being processed in the bioreactor with MBR Filtration. It is recommended to have three hours
for biological treatment before starting with the filtration process.
Example:
If the taking of showers is scheduled mostly in the morning between 7:00-8:00,
then the pump cycle T1 is recommended to be finished before 7:00.
It is important that a pump cycle run time (T1 or T2) is not overlapped with next start time (T2
or T1). If this is the case then the second timed start will not occur as required.