Operating and installation instructions
Operating and installation instructions
Installer information
Installer information
Connection of 100-240VAC
and 12VDC can not be done
simultaneously (Figure N).
NOTE! The integrated all-pole switch S only
functions at 100-240VAC wiring.
NOTE! 12VDC voltage must not
exceed between 10 - 13,6VDC.
NOTE! For 12VDC always use switches
intended for direct current, C.
N.
O.
No 100-240V wiring may pe-
netrate the electronics portion
(Figure O.)
Svara auto:
100-240VAC 50 / 60Hz
Continuous trickle speed ventilation, automatic
boost at elevated humidity levels, and via the
integrated light sensor.
Svara on/off operation through remote
switch:
(Can be combined with backdraft shutter)
100-240VAC 50 / 60Hz
Must be selected via Vent-Axia Connect App.
Start / stop via manual switch L.
Svara humidity controlled:
(Can be combined with backdraft shutter)
100-240VAC 50 / 60Hz
Must be selected via Vent-Axia Connect App.
Trickle setting, automatic start / stop
on changes in humidity levels.
Svara on/off operation through remote
switch, with overrun:
(Can be combined with backdraft shutter)
100-240VAC 50 / 60Hz
Must be selected via Vent-Axia Connect App.
Start / stop via manual switch T.
Svara auto:
12VDC (switch C always)
Continuous trickle ventilation, automatic boost at
elevated humidity levels, and via the integrated
light sensor.
Svara on/off operation through remote
switch:
(Can be combined with backdraft shutters)
12VDC
Must be selected via Vent-Axia Connect App.
Start / stop via manual switch C.
Svara humidity controlled:
(Can be combined with backdraft shutters)
12VDC (switch C always)
Must be selected via Vent-Axia Connect App.
Trickle setting, automatic start / stop
on changes in humidity levels.
ELECTRICAL CONNECTION 100-240VAC
NOTE! Wiring of 100-240VAC must be
performed by a qualified electrician.
ELECTRICAL CONNECTION 12VDC