background image

440 04 6000 00

3

Specifications  subject to change without notice.

START

UP, ADJUSTMENT, AND SAFETY

CHECK

General

1. Furnace must have a 115-v power supply properly

connected and grounded.

NOTE

:  Proper polarity must be maintained for 115-v wiring.

Control status indicator light flashes rapidly and furnace
does not operate if polarity is incorrect or if the furnace is not
grounded.

2. Thermostat wire connections at terminals R, W, G,

and Y must be made at 24-v terminal block on

furnace control.

3. Natural gas service pressure must not exceed 0.5

psig (14- in. w.c., 1125 Pa), but must be no less than

0.16 psig (4.5-in. w.c., 350 Pa).

4. Blower door must be in place to complete 115-v elec-

trical circuit and supply power to the furnace

components.

UNIT OPERATION HAZARD

Failure to follow this caution may result in intermittent

unit operation or performance satisfaction.
These furnaces are equipped with a manual reset limit

switch in burner assembly.  This switch opens and

shuts off power to the gas valve if an overheat

condition (flame rollout) occurs in the burner

assembly/enclosure.  Correct inadequate

combustion

air supply, improper gas pressure setting,

improper burner or gas orifice positioning, or improper

venting condition before resetting switch.  DO NOT

jumper this switch.

CAUTION

!

Before operating furnace, check flame rollout manual reset

switch for continuity. If necessary, press button to reset

switch.
EAC-1 (115vac) terminal is energized whenever blower

operates. HUM (24vac) terminal is only energized when the

low pressure switch (LPS) is closed on a call for heat.

Prime Condensate Trap with Water

CARBON MONOXIDE POISONING HAZARD

Failure to follow these warnings could result in personal

injury or death.
Failure to use a properly configured trap or NOT

water-priming trap before operating furnace may allow

positive pressure vent gases to enter the structure

through drain tube. Vent gases contain carbon

monoxide which is tasteless and odorless.

!

WARNING

1. Remove upper and middle collector box drain plugs

opposite of the condensate trap.   (See Figure 10.)

2. Connect field-supplied 5/8-in. (16 mm) ID tube with at-

tached funnel (see Figure 10) to upper collector box

drain connection.

3. Pour one quart (liter) of water into funnel/tube. Water

should run through collector box, overfill condensate

trap, and flow into open field drain.

4. Remove funnel; replace collector box drain plug.
5. Connect field-supplied 5/8-in. (16 mm) ID tube to

middle collector box drain port.

6. Pour one quart (liter) of water into funnel/tube. Water

should run through collector box, overfill condensate

trap, and flow into open field drain.

7. Remove funnel and tube from collector box and

replace collector box drain plug.

Purge Gas Lines

If not previously done, purge the lines after all connections

have been made and check for leaks.

FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal

injury, death, and/or property damage.
Never purge a gas line into a combustion chamber.

Never test for gas leaks with an open flame. Use a

commercially available soap solution made

specifically for the detection of leaks to check all

connections.  A fire or explosion may result causing

property damage, personal injury or loss of life.

!

WARNING

Adjustments

FIRE HAZARD

Failure to follow this warning could result in personal

injury, death and/or property damage.
DO NOT bottom out gas valve regulator adjusting

screw. This can result in unregulated manifold

pressure and result in excess overfire and heat

exchanger failures.

!

WARNING

FURNACE DAMAGE HAZARD

Failure to follow this caution may result in reduced

furnace life.
DO NOT redrill orifices. Improper drilling (burrs,

out

of

round holes, etc.) can cause excessive burner

noise and misdirection of burner flames. This can

result in flame impingement of heat exchangers,

causing failures. (See Figure 1.)

CAUTION

!

BURNER 

ORIFICE

A93059

Figure 1 

 

Orifice Hole

For proper operation and long term reliability the furnace

input rate must be /

2  percent of input rate on

furnace rating plate, or as adjusted for altitude.

Summary of Contents for R9MSB0601716A

Page 1: ...used throughout this manual in the following manner CAUTION Signal Words on Product Labeling Signal words are used in combination with colors and or pictures or product labels The signal word WARNING...

Page 2: ...eath WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE...

Page 3: ...ch is tasteless and odorless WARNING 1 Remove upper and middle collector box drain plugs opposite of the condensate trap See Figure 10 2 Connect field supplied 5 8 in 16 mm ID tube with at tached funn...

Page 4: ...rifice hole with a numbered drill bit of correct size Never redrill an orifice A burr free and squarely aligned orifice hole is essential for proper flame characteristics 6 Replace orifice with correc...

Page 5: ...n gas valve g If clocked rate does not match required input from Step 1 increase manifold pressure to increase input or decrease manifold pressure to decrease input Repeat steps b through e of Step 1...

Page 6: ...speed lead s from the other motor leads and relocate it them to HEAT heating blower tap terminal s Reconnect original lead on SPARE terminal Adjust Blower Off Delay Heat Mode If desired the main blow...

Page 7: ...in upflow position and control Main or upper door in upflow position doors are properly installed 5 Verify that the Status LED glows If not check that the power supply is energized and that the blowe...

Page 8: ...290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 9...

Page 9: ...440 04 6000 00 9 Specifications subject to change without notice 338309 201 Rev E A11602 Figure 5 Service Label Information...

Page 10: ...2 42 3 3 42 3 4 915 825 43 3 6 43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3...

Page 11: ...uld result in personal injury death and or property damage The ability to properly perform maintenance on this equipment requires certain knowledge mechanical skills tools and equipment If you do not...

Page 12: ...urnace operation problems Beginning with the word Start answer each question and follow the appropriate arrow to the next item The Guide will help to identify the problem or failed component After rep...

Page 13: ...m exposed electrical components when manually closing this switch for service purposes WARNING 4 For approximately 2 sec short jumper the COM 24v terminal on control to the TEST TWIN 3 16 in 5 mm quic...

Page 14: ...tightness and controls for proper operation each heating season Service as necessary 4 Inspect burner compartment before each heating season for rust corrosion soot or excessive dust If necessary hav...

Page 15: ...emove blower wheel from housing g Clean wheel per instructions on degreaser cleaner Do not get degreaser in motor 8 Reassemble motor and blower wheel by reversing items 7b through 7f Ensure wheel is p...

Page 16: ...assembly 4 Align the orifices in the manifold assembly with the support rings on the end of the burner 5 Insert the orifices in the support rings of the burners NOTE If manifold does not fit flush aga...

Page 17: ...ter 3 Remove control door and set aside 4 Turn electric switch on gas valve to OFF 5 Disconnect external drain from condensate drain elbow or drain extension pipe inside the furnace and set aside 6 Di...

Page 18: ...d flame sensor 10 Turn on gas and electrical supplies to furnace 11 Check furnace operation through 2 complete heat operating cycles Look at burners Burner flames should be clear blue almost transpare...

Page 19: ...condensate pump with clear water to check for proper operation before re starting furnace 14 Propylene glycol need not be removed before re starting furnace 2 1 2 in 64 4 1 1 4 in 31 8 A11405 Figure 8...

Page 20: ...MOTOR WHEEL HUB MOTOR SHAFT FLAT SCREW MOTOR ARM GROMMET SCREW LOCATION BLO HSG ASSY BRACKET BRACKET ENGAGEMENT SEE DETAIL A CAPACITOR OR POWER CHOKE WHEN USED BRACKET SCREW GND BLOWER HSG ASSY MOTOR...

Page 21: ...440 04 6000 00 21 Specifications subject to change without notice FLAME SENSOR BELOW BURNER FLAME ROLLOUT SWITCH BRACKET IGNITER IGNITER BURNER SUPT ASSY BURNER ASSY A11403 Figure 14 Burner Assembly...

Page 22: ...y If the burner flame is proven the blower motor is energized on HEAT speed 25 sec after the gas valve GV is energized Simultaneously the electronic air cleaner terminal EAC 1 is energized and remains...

Page 23: ...flash the status code of the previous fault or status code 11 1 short and 1 long flash if there was no previous fault After the control repeats the code 4 times the control will go through a brief com...

Page 24: ...control will repeat the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected blower off delay Check t...

Page 25: ...440 04 6000 00 25 Specifications subject to change without notice 339236 2 Rev A Figure 16 Wiring Diagram...

Page 26: ...can cause personal injury property damage or death Consult a qualified installer service agency or your local gas supplier for information or assistance The qualified installer or service agency must...

Reviews: