background image

440 04 6000 00

15

Specifications  subject to change without notice.

Blower Motor and Wheel Maintenance

To ensure long life, economy, and high efficiency, clean

accumulated dirt and grease from blower wheel and motor

annually.
The inducer and blower motors are pre

lubricated and

require no additional lubrication. These motors can be

identified by the absence of oil ports on each end of the

motor.
The following items should be performed by a qualified

service technician. Clean blower motor and wheel as

follows:

1. Turn off electrical supply to furnace.

2. Remove blower door.

3. All factory wires can be left connected, but field

thermostat and accessory wiring may need to be

disconnected depending on their length and routing.

4. If the vent and combustion air pipe passes through

the blower compartment, it will be necessary to

remove the pipes from the blower compartment.

Disconnect the vent  and  combustion air pipe by:

a.  Loosen the clamps on the vent couplings and

combustion air pipe external to the furnace.

b. Separate the pipes from the couplings and move

them aside.

c. Loosen the clamps on the vent couplings and

combustion air pipe located on the blower shelf.

d. Separate the pipes from the blower compartment

and set aside.

e. Remove the couplings from the pipe adapters and

set  aside.

f. After servicing the blower, reverse steps a through

e.

g. Tighten all clamps 15 lb 

in.

See Figure 13 for steps 5 through 14.

5. Remove screws securing blower assembly to blower

shelf and slide blower assembly out of furnace.

Detach ground wire and disconnect blower motor

harness plugs from blower motor.

NOTE

:  Blower wheel is fragile. Use care.

6. Clean blower wheel and motor by using a vacuum

with soft brush attachment. Be careful not to disturb

balance weights (clips) on blower wheel vanes. Do

not bend wheel or blades as balance will be affected.

7. If greasy residue is present on blower wheel, remove

wheel from the blower housing and wash it with an

appropriate degreaser. To remove wheel:
a. Mark blower wheel location on shaft before

disassembly to ensure proper reassembly.

b. Loosen setscrew holding blower wheel on motor

shaft.

NOTE

:  Mark blower mounting arms and blower housing so

each arm is positioned at the same hole location during

reassembly.

c. Mark blower wheel orientation and cutoff plate

location to ensure proper reassembly.

d. Remove screws securing cutoff plate and remove

cutoff plate from housing.

e. Remove bolts holding motor mounts to blower

housing and slide motor and mounts out of housing.

f. Remove blower wheel from housing.

g. Clean wheel per instructions on degreaser cleaner.

Do not get degreaser in motor.

8. Reassemble motor and blower wheel by reversing

items 7b through 7f. Ensure wheel is positioned for

proper rotation.

9. Torque motor mounting bolts to 40 +/

 10 lb

in.  when

reassembling.

10. Torque blower wheel set screw to 160 +/

 20 lb

in.

when reassembling.

11. Verify that blower wheel is centered in blower housing

and set screw contacts the flat portion of the motor

shaft. Loosen set screw on blower wheel and

reposition if necessary.

12. Spin the blower wheel by hand to verify that the wheel

does not rub on the housing.

13. Reinstall blower assembly in furnace.
14. Reinstall 2 screws securing blower assembly to

blower deck.

15. Reconnect blower leads to furnace control. Refer to

furnace wiring diagram, and connect thermostat leads

if previously disconnected.

NOTE

:  Be sure to attach ground wire and reconnect blower

harness plugs to blower motor.

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal

injury or death.
Blower door switch opens 115

v power to control. No

component operation can occur unless switch is closed.

Caution must be taken when manually closing this

switch for service purposes.

!

WARNING

16. Downflow or horizontal furnaces with vent pipe

through furnace only:
a. Install and connect short piece of vent pipe inside

furnace to existing vent.

b. Connect vent connector to vent elbow.

17. Turn on electrical supply. Manually close blower door

switch. Use a piece of tape to hold switch closed.

Check for proper rotation and speed changes

between heating and cooling by jumpering R to G and

R to Y/Y2 on furnace control thermostat terminals. If

outdoor temperature is below 70

_

F (21

_

C), turn off

circuit breaker to outdoor unit before running furnace

in the cooling cycle. Turn outdoor circuit breaker on

after completing cooling cycle. (See Figure 2.)

NOTE

:  If R

W/W1 thermostat terminals are jumpered at the

time blower door switch is closed, blower will run for 90 sec
before beginning a heating cycle.

a. Perform component self

test as shown at the bottom

of the SERVICE label, located on the control door.

b. Verify blower is rotating in the correct direction

18. If furnace is operating properly, RELEASE BLOWER

DOOR SWITCH. Remove any jumpers or reconnect

any disconnected thermostat leads. Replace blower

door.

19. Turn on gas supply and cycle furnace through one

complete heating cycle. Verify the furnace

temperature rise as shown in Adjustments Section.

Adjust temperature rise as shown in Adjustments

Section.

Cleaning Burners and Flame Sensor

The following items must be performed by a qualified

service technician. If the burners develop an accumulation

Summary of Contents for R9MSB0601716A

Page 1: ...used throughout this manual in the following manner CAUTION Signal Words on Product Labeling Signal words are used in combination with colors and or pictures or product labels The signal word WARNING...

Page 2: ...eath WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE...

Page 3: ...ch is tasteless and odorless WARNING 1 Remove upper and middle collector box drain plugs opposite of the condensate trap See Figure 10 2 Connect field supplied 5 8 in 16 mm ID tube with at tached funn...

Page 4: ...rifice hole with a numbered drill bit of correct size Never redrill an orifice A burr free and squarely aligned orifice hole is essential for proper flame characteristics 6 Replace orifice with correc...

Page 5: ...n gas valve g If clocked rate does not match required input from Step 1 increase manifold pressure to increase input or decrease manifold pressure to decrease input Repeat steps b through e of Step 1...

Page 6: ...speed lead s from the other motor leads and relocate it them to HEAT heating blower tap terminal s Reconnect original lead on SPARE terminal Adjust Blower Off Delay Heat Mode If desired the main blow...

Page 7: ...in upflow position and control Main or upper door in upflow position doors are properly installed 5 Verify that the Status LED glows If not check that the power supply is energized and that the blowe...

Page 8: ...290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 9...

Page 9: ...440 04 6000 00 9 Specifications subject to change without notice 338309 201 Rev E A11602 Figure 5 Service Label Information...

Page 10: ...2 42 3 3 42 3 4 915 825 43 3 6 43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3...

Page 11: ...uld result in personal injury death and or property damage The ability to properly perform maintenance on this equipment requires certain knowledge mechanical skills tools and equipment If you do not...

Page 12: ...urnace operation problems Beginning with the word Start answer each question and follow the appropriate arrow to the next item The Guide will help to identify the problem or failed component After rep...

Page 13: ...m exposed electrical components when manually closing this switch for service purposes WARNING 4 For approximately 2 sec short jumper the COM 24v terminal on control to the TEST TWIN 3 16 in 5 mm quic...

Page 14: ...tightness and controls for proper operation each heating season Service as necessary 4 Inspect burner compartment before each heating season for rust corrosion soot or excessive dust If necessary hav...

Page 15: ...emove blower wheel from housing g Clean wheel per instructions on degreaser cleaner Do not get degreaser in motor 8 Reassemble motor and blower wheel by reversing items 7b through 7f Ensure wheel is p...

Page 16: ...assembly 4 Align the orifices in the manifold assembly with the support rings on the end of the burner 5 Insert the orifices in the support rings of the burners NOTE If manifold does not fit flush aga...

Page 17: ...ter 3 Remove control door and set aside 4 Turn electric switch on gas valve to OFF 5 Disconnect external drain from condensate drain elbow or drain extension pipe inside the furnace and set aside 6 Di...

Page 18: ...d flame sensor 10 Turn on gas and electrical supplies to furnace 11 Check furnace operation through 2 complete heat operating cycles Look at burners Burner flames should be clear blue almost transpare...

Page 19: ...condensate pump with clear water to check for proper operation before re starting furnace 14 Propylene glycol need not be removed before re starting furnace 2 1 2 in 64 4 1 1 4 in 31 8 A11405 Figure 8...

Page 20: ...MOTOR WHEEL HUB MOTOR SHAFT FLAT SCREW MOTOR ARM GROMMET SCREW LOCATION BLO HSG ASSY BRACKET BRACKET ENGAGEMENT SEE DETAIL A CAPACITOR OR POWER CHOKE WHEN USED BRACKET SCREW GND BLOWER HSG ASSY MOTOR...

Page 21: ...440 04 6000 00 21 Specifications subject to change without notice FLAME SENSOR BELOW BURNER FLAME ROLLOUT SWITCH BRACKET IGNITER IGNITER BURNER SUPT ASSY BURNER ASSY A11403 Figure 14 Burner Assembly...

Page 22: ...y If the burner flame is proven the blower motor is energized on HEAT speed 25 sec after the gas valve GV is energized Simultaneously the electronic air cleaner terminal EAC 1 is energized and remains...

Page 23: ...flash the status code of the previous fault or status code 11 1 short and 1 long flash if there was no previous fault After the control repeats the code 4 times the control will go through a brief com...

Page 24: ...control will repeat the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected blower off delay Check t...

Page 25: ...440 04 6000 00 25 Specifications subject to change without notice 339236 2 Rev A Figure 16 Wiring Diagram...

Page 26: ...can cause personal injury property damage or death Consult a qualified installer service agency or your local gas supplier for information or assistance The qualified installer or service agency must...

Reviews: