background image

TROUBLE SHOOTING 

 

IMPORTANT:  Only qualified personnel should service TUACA unit and 
components. 

 

WARNING:  To avoid personal injury and or property damage, always disconnect electrical power, 
before starting any repairs.  If repairs are to be made to the TUACA unit, drain TUACA unit before 
proceeding. 

COOLING UNIT 

Trouble  

Probable 

Cause 

 

Remedy 

Cooling or 
condensing unit 
non- 
operational 

1. 

 

2. 

 

3. 

 

4. 
5. 
6. 

 

7. 

 

No electrical power. 
 
Improper voltage/amperage 
 
Loss of refrigerant. 
 
Bad overload and relay. 
Compressor bad. 
Restriction (pinched or crimped 
line). 
Condenser Dirty 

1. 

 

2. 

 

3. 

 

4. 
5. 
6. 

 

7. 

Plug power cord into electrical 
box. 
Check for proper 
voltage/amperage. 
Repair leak and replenish 
refrigerant. 
Replace overload and relay 
Replace compressor. 
Repair, straighten or replace 
defective line. 
Clean condenser unit w/vacuum 
cleaner. 

Condenser fan 
motor not 
operating 

1. 

 
 

2. 
3. 

Electrical cord loose or 
disconnected from condenser fan 
motor or compressor terminals. 
Fan blade obstructed. 
Inoperative condenser fan motor. 

1. 

 
 

2. 
3. 

 

 

Tighten connections or replace 
cord. 
 
Remove obstruction. 
Replace condenser fan motor. 

Compressor 
does not 
operate 

1. 
2. 

 

3. 

 

4. 

 

5. 

 

6. 

No power source. 
Electrical power to cooling unit 
turned off. 
Low voltage. 
 
Loose, disconnected, or broken 
wire. 
Inoperative overload protector or 
start relay. 
Inoperative compressor. 

1. 
2. 

 

3. 

 

4. 

 

5. 

 

6. 

Plug power cord to electrical box.  
Check line voltage. 
 
Voltage must be at least 110 V at 
compressor terminals at start. 
Tighten connection or replace 
broken wiring. 
Replace defective part. 
 
Replace compressor. 

Note:  During overload protector shut off condenser fan motor will continue to work.   Otherwise, 
troubleshooting condenser fan motor problems is the same as “Compressor does not operate”, 
paragraph in addition to the following.   

Condenser fan 
motor not 
operating 

1. 

 
 

2. 
3. 

Electrical cord loose or 
disconnected from condenser fan 
motor or compressor terminals. 
Fan blade obstructed. 
Inoperative condenser fan motor. 

1. 

 
 

2. 
3. 

 

 

Tighten connections or replace 
cord. 
 
Remove obstruction. 
Replace condenser fan motor. 

 
 
 
 
 
 
 

16 

Summary of Contents for TUACA

Page 1: ...CI INTERNATIONAL CARBONIC INC 16630 Koala Rd Adelanto California 92301 800 854 1177 Installation and Service Manual 3 22 05 TUACA PUSH HERE...

Page 2: ...ling operating servicing and maintaining this equipment Refer to Table of Contents for page location of detailed information to answer questions that arise during installation operating service and ma...

Page 3: ...NSPECTION 8 SELECTING LOCATION 8 LOCATION RECOMMENDATIONS 8 ELECTRICAL REQUIREMENTS 8 TUACA UNIT INSTALLATION INSTRUCTIONS 9 FLOW PLAN BOTTLE MOUNT 11 CHAPTER III OPERATORS INSTRUCTIONS 12 DAILY PRE O...

Page 4: ...ater to 100 saturation We developed the first patented dispensing valve to dispense bulk beverage with carbonation equal to or in excess of bottled beverages A valve with three flavors and soda was an...

Page 5: ...nt of highly chilled 1oz servings of TUACA and lime Essentially the TUACA unit is designed to plug and play For proper function the TUACA unit must have 120 volt electrical supply and proper space aro...

Page 6: ...ill dispense a chilled shot below 32 degrees When the Push Switch is pushed the incoming TUACA is routed to a peristaltic pump and then through a cooling coil that is positioned next to the refrigerat...

Page 7: ...BY CHK BY APPR BY ICI CHILL SHOT TUACA GLW 58 57 59 60 51 45 44 46 47 41 42 43 14 8 4 7 9 27 10 28 29 30 31 40 36 34 32 56 50 52 53 55 62 63 65 64 66 67 61 35 26 8 8 48 33 37 38 49 5 1 2 3 6 39 8 11...

Page 8: ...AP BUSHING 14 8 S1335 TERMINAL SPACER 15 1 S1850 LED BRACKET 16 1 S1851 LOGO BRACKET 17 2 A0060 SCREW 6 32 X 1 4 FLAT HEAD 18 1 S1229 9 MERCHANDISER LIGHT BASE BACK 19 1 S0952 BALLAST 20 1 S0958 START...

Page 9: ...H PUMP HOUSING BODY PPM 48 1 S1741 CS PPM CONTROL 49 4 S1318 CUSHIONED FEET 50 1 S0276 A TRANSFORMER 51 1 S1837 CONTROL BOX 52 1 S1309 TERMINAL BOARD 53 1 S1840 CONTROL BOX COVER ONLY 54 1 S0766 ROCK...

Page 10: ...3 1 C S R M S 1 FAN MOTOR COMPRESSOR CONDENSING UNIT GROUND TERMINAL SCREW IN CONTROL BOX 110 VOLT LAMP LED LIQUOR MOTOR GREEN WHITE BLACK FO5 PP 1 2 3 4 5 6 6 6 5 5 5 4 4 4 3 3 3 2 2 2 1 1 1 6 A B C...

Page 11: ...TANT Ambient temperature for cooling unit should not exceed 100 degrees F Operation of cooling unit in ambient above 100 degrees F can and will contribute to early failure of condensing unit and poor...

Page 12: ...tely contact Sentry BevCon at 800 661 3003 Do not discard the shipping carton or any shipping materials in the event a freight claim must be filed 1 The following parts are included with this Shippmen...

Page 13: ...ling coils are filled Dispense 6 8 ounces in order to flush unit DO NOT REUSE 10 In approximately 15 minutes the unit will dispense ice cold TUACA shots 11 Your unit is equipped with an on off switch...

Page 14: ...l Sleeve on to Bottle Cap Assembly 4 Install Bottle Cap Assembly with Sleeve onto the liquor bottle to be served 5 Locate Reserve Strainer and place into the Bottle Reserve Assembly 6 Carefully turn l...

Page 15: ...clean This may be accomplished by one of three methods One method is use of a condenser brush a longhaired soft bristle brush to gently sweep fins of condenser clean Second method is to use a strong...

Page 16: ...odically To accomplish this task shut off the condensing unit at condensing unit on off switch located under the control box on the lower right hand side Flush all liquor out of liquor coil and into a...

Page 17: ...if dirty clean with soft bristle brush Clean exteriors of nozzle tubes with a soft clothe and warm water Replace valve nozzle then go to step 3 3 Fill bottle reserve with a caustic based low sudsing n...

Page 18: ...ance that must be performed A Yes again depending on usage your peristaltic pump tubing will have to be changed Q How often must this tubing be changed A Again depending on the usage approximately eve...

Page 19: ...motor or compressor terminals Fan blade obstructed Inoperative condenser fan motor 1 2 3 Tighten connections or replace cord Remove obstruction Replace condenser fan motor Compressor does not operate...

Page 20: ...______________________________ ____________________________ __________________________________ ____________________________ _____________________________________ __________________________________ ___...

Reviews: