11
STEP #5
CUT & INSTALL TUBING OVER THE LOW
VOLTAGE ACCESSORY WIRES AND/OR CORDS
1.
The installation of the corrugated tubing kit (part
of mechanism), Part Number 156PA12927A is
necessary in order to create a double barrier of
insulation between the low voltage accessory wires
and high voltage line and load wires.
2.
Secure the tubing using the cable ties and self-
adhesive retainers supplied with the tubing kit.
Example #1
Shutter Bushing
Retainer and Cable
Tie Location
Freeze Sensor
Cable
Firemen Switch
Wires
STEP #9
Setting The Cool Down Time
(Fireman Switch)
NOTE
The cool down time is a time defined by the programmer.
It’s used in conjunction with a pool heater, (See Fig. #1
for heater hookup), and it’s defined as the additional
time the pump will run over and beyond the desired
pump OFF time with the Fireman switch open. If a time is
programmed,the cool down cycle will occur in all cases,
even if the user turns off the pump. To override the cool
down time, simply press and release the ON/OFF key a
second time
during the cool down cycle.
NOTE:
The
cool down feature applies to circuit #1, only in modes
1/3/5/6. In modes 2/4/7 either circuit #1, or circuit #2 will
activate the cool down feature.
1.
Use the
PROG
key to advance to the
Cool Down
setting.
2. The default cool down time is zero. Use the arrow
keys to modify the cool down time. The range is zero
to fifteen minutes. Use the Enter key or Program key
to either save and exit, or save and advance to the
next programming feature.
30