Chapter 3: Calibration and setup
72
FlexZone™ Product Guide
5. Save the UCM file and download the configuration data to the processor.
6. Repeat this procedure for the B Side sensor cable.
Figure 72: Defining the end point of detecting cable
Setting individual cable segment thresholds
In addition to the threshold for the full length of cable, you can also set
independent thresholds for the defined cable segments. Cable segment
thresholds are used for any high risk, or low threat, areas, as well as any areas
that may be subject to a higher NAR such as an open stretch of fencing that is
exposed to strong winds. Lowering the threshold in high risk areas will increase
the Pd in that area. However, a lower threshold can also lead to an increased
nuisance alarm rate. For an area where the threat is considered low, you can
raise the threshold, which will reduce the chances of nuisance alarms occurring,
while still providing an acceptable Pd.
No Zone label for the segment beyond
2
4
3
the end point of detecting cable (Zone 0)
No Threshold for the segment beyond
the end point