1485 Jacobs Rd.
Deland, FL 32724
386.738.7307
P/N 53-00549-100 Rev. C 032619
www.intellitec.com
Intellitec
SERVICE MANUAL
SMART EMS
TM
PLACEMENT
The EMS should be installed in a convenient location where it can get air
circulation to keep it from over heating. There should be a minimum of 7" of depth
behind the mounting surface to provide enough room for the box and wiring.
A hole should be cut in the mounting panel as shown.
This opening must be cut carefully to be sure the mounting screws will have
enough wood to hold, and there is enough clearance around the box for the front
cover screws.
The wiring to the box should be routed through the holes in the back and secured
using approved cable connectors. The wires should be copper conductors
with the appropriate size and insulation to meet N.E.C.
The 10 gauge main cable should be brought through the large hole in the lower center of the box. The remaining wires
should be routed through the remaining holes in the back of the box.
The wires should be stripped and the ground wire of each cable connected to the GROUND bar, terminal strip. The white
or neutral wires should all be connected to the NEUTRAL bar terminal strip.
(See the box drawing.)
If removed during installation, the white jumper wire should be re-installed between the NEUTRAL bar and J1, terminal 1 of
the EMS module. (See box drawing, page 6.)
The Black or "hot" lead should be routed through the hole in the current sensor and then to the screw terminal on the 30
Amp Main breaker.
The black or "hot" leads of all the uncontrolled loads should be connected to their associated breakers.
To connect the 120 volt controlled loads, jumper wires should be connected from the respective circuit breakers to the
associated screw terminals on the EMS control module. The black wires to the controlled loads should be connected to
the proper screw terminals on the EMS module. Be sure these wires are under the screw terminals and they are tight.
- 7 terminal block - Will accept up to 12 GA or 14 GA copper wire ONLY.
1
Neutral
2
From Circuit Breaker 3
3
Output of Relay 3
4
From Circuit Breaker 2
5
Output of Relay 2
ONLY,
Each terminal screw should be tightened
to 16in.-lb. of torque.
J5
Terminal
Function