background image

ELECTRONIC CLIMATE CONTROL II 

SERVICE MANUAL Part No’s. 00-00855-000 / 00-00856-000 

 

 

 

Intellitec 

1485 Jacobs Rd.

Deland, FL 32724

386.738.7307

www.Intellitec.com 

- 5 - 

P/N 53-00855-856 Rev. C 080819

 

VDC) wiring.  The Control Module uses 

high-side switching

 to operate the corresponding relays.  One side of each of the 

relay coils is connected together.  This ”common” lead is connected to ground through the Control Module and 

should not

 

be grounded anywhere else.  The other side of each of the coils is brought out to one of three separate leads.  These 
leads are connected to the Control Module via a four-pin connector: J2 for the A/C1 unit and J3 for the A/C2 unit.  The 
corresponding pigtail connectors, PC2 and PC3, are supplied with the system.  PC3, the A/C2 connector, is marked in red 
in order to differentiate it from PC2.   

 
THE ECC LINE VOLTAGE SENSOR: 

 
The ECC line voltage sensor is used by the system to detect when line voltage is available.  When the line voltage is 
present, the sensor outputs a DC voltage to the control module.  When the line voltage is not present, the system goes to 
sleep, turning off unnecessary parasitic loads to conserve battery power.  The sensor is connected to J7 during normal 
operations (i.e., not during HI-POT testing).  This sensor should be disconnected and J7 shorted with a jumper to conduct 
the HI-POT test. 
 
The following table indicates the connection and control states: 
 

MODULE 

CONN PIN 

PIGTAIL 

WIRE 

COLOR 

FUNCTION “ON” 

VOLTAGE 

“OFF” 

VOLTAGE 

J2-1 

BLU 

COMMON 

<1 VDC 

<1 VDC 

J2-2 

GRY 

LOW FAN 

+12 VDC 

<1 VDC 

J2-3 

GRN 

HIGH FAN 

+12 VDC 

<1 VDC 

J2-4 

YEL 

COMPRESSOR 

+12 VDC 

<1 VDC 

J3-1 

BLU 

COMMON 

<1 VDC 

<1 VDC 

J3-2 

GRY 

LOW FAN 

+12 VDC 

<1 VDC 

J3-3 

GRN 

HIGH FAN 

+12 VDC 

<1 VDC 

J3-4 

YEL 

COMPRESSOR 

+12 VDC 

<1 VDC 

 

NOTE:

  The PC2 (J2) and PC3 (J3) pigtail wire colors are included 

for reference only

 to identify the function of the wires 

emanating from the control module.  The wire colors emanating from the A/C1 and A/C2 units may, or may not agree with 
these colors.

  Always refer to the installation manual supplied with the A/C unit,

 or see

 “Identifying control lead functions 

on the A/C unit”,

 in order to match the wire color/functions with those on the control module. 

 

TEST SWITCH: 

 
The control module incorporates a three-position test switch located between J2 and J3 to verify the operation and wiring 
of each A/C unit only.   
 
Sliding the test switch towards J2 

bypasses

 the control module completely and operates the high fan and compressor for 

A/C 1 by connecting J2-3 and J2-4 to +12V.  If the air conditioner fails to operate in this position, the problem is with the 
air conditioner or wiring between the control module and the air conditioner.  Sliding the test switch towards J3 operates 
the high fan and compressor for A/C 2 by connecting J2-3 and J2-4 to +12V.   
 
The test switch must be placed in the 

CENTER

 or 

OFF

 position for normal operation. 

 
The test switch can be used to temporarily operate the air conditioners in the event of a control module or thermostat 
failure. 

 
IPX INDICATORS: 

 
The communication wires connecting the thermostat to the control module are protected from short circuits.  However if 

Summary of Contents for 00-00855-000

Page 1: ...andard wall mount thermostats In either the LOW COOL or HIGH COOL modes the air conditioner fans run continuously at the selected speed and the compressors are controlled to maintain the set point temperature When in the AUTO mode the unit automatically controls the compressors and selects the appropriate air conditioner fan speed based on the difference between the set point temperature and the a...

Page 2: ...IMATE CONTROL ELECTRONIC CLIMATE CONTROL 75 70 TEMPERATURE SET TEMPERATURE SET There is a single function switch that controls the functions of the two air conditioner A C1 and A C2 systems The potentiometer allows the user to select a desired temperature for the system in the range of 50 to 90 degrees Fahrenheit Moving the controls down lowers the set point temperature The seven position function...

Page 3: ...t temperature goes 2 degrees above the set point temperature When the ambient temperature drops to within 1 degree of the set point the fan switches to low speed When the temperature drops to the set point the compressor turns off When the temperature drops 2 degrees below set point the fans will shut off As the ambient temperature rises the reverse procedure happens Load shedding is active INDICA...

Page 4: ...and the contacts for the rear furnace are connected to pins 4 and 5 of the same connector The relay contacts are electrically isolated from all other circuitry on the Control Module The contacts are functionally equivalent to the contacts on a wall mounted thermostat and are wired to the blue and black thermostat leads from each furnace The coach may be equipped with one or two furnaces On coaches...

Page 5: ...FF VOLTAGE J2 1 BLU COMMON 1 VDC 1 VDC J2 2 GRY LOW FAN 12 VDC 1 VDC J2 3 GRN HIGH FAN 12 VDC 1 VDC J2 4 YEL COMPRESSOR 12 VDC 1 VDC J3 1 BLU COMMON 1 VDC 1 VDC J3 2 GRY LOW FAN 12 VDC 1 VDC J3 3 GRN HIGH FAN 12 VDC 1 VDC J3 4 YEL COMPRESSOR 12 VDC 1 VDC NOTE The PC2 J2 and PC3 J3 pigtail wire colors are included for reference only to identify the function of the wires emanating from the control m...

Page 6: ...Module shuts down the associated A C compressor during the shedding sequence 2 If the 120 VAC line voltage sensed by the Line Voltage Sensor goes off This will occur during an interruption of power if the generator is not running or if the shore power cord is not plugged in 3 If the unit is recovering from load shedding the Control Module will signal the ECC Thermostat to alternately flash the red...

Page 7: ...esponding voltage A functional current sensor has a resistance of approximately 15 40 Ohms and produces an AC voltage of 0 1 VAC per Amp of current passing through the core 10 Amps 1 0 VAC The current sensor should be mounted in one of the knockouts in the 120 VAC box so that the donut shaped head is inside the box The black wire feeding the 30 Amp main breaker in the 120 VAC panel should pass thr...

Page 8: ...COOL HI COOL HI COOL AUTO COOL AUTO COOL FRONT BOTH REAR FRONT BOTH REAR FURNACES FURNACES SHED SHED AC 1 AC 1 ON ON SHED SHED AC 2 AC 2 ON ON ELECTRONIC CLIMATE CONTROL ELECTRONIC CLIMATE CONTROL 75 70 TEMPERATURE SET TEMPERATURE SET RELAY CONTROLLED AIR CONDITIONER A C2 LOW VOLTAGE WIRING TRANSFER RELAY DELAY 00 00568 000 5 0kW GENERATOR LOW VOLTAGE WIRING ECC CONTROL MODULE 00 00855 000 30 AMP ...

Page 9: ...ke sure that the pigtail keying matches connector keying 3 Check voltage at the line sensor input J7 It should be greater than 11 volts 4 Measure the DC voltage between the Power J1 4 IPX SIG J1 8 and IPX GND J1 7 pins on the control module There should be approximately 12 volts from IPX GND to Power and 9 volts from IPX GND to IPX SIG The same voltages should appear at the Thermostat If not repai...

Page 10: ...s are reversed 2 Check the continuity of the Comp Relay lead between the control module and the front A C unit B Slide the test switch on the control module towards J3 A C2 compressor and high fan should turn on If NOT 1 Check to make sure that the leads on PC3 are connected to their corresponding function at the A C2 unit The wire colors may or may not match It is likely that the common and high ...

Page 11: ...Replace the control module C Disconnect plug PC4 from the control module Placing a shorting jumper between PC4 pins 1 and 2 should cause the front furnace to energize Placing a shorting jumper between PC4 pins 4 and 5 should cause the rear furnace to energize If NOT Check the wiring between PC4 and the furnace ON indicator is lit air conditioners won t function properly SHORT indicator on the cont...

Page 12: ...DE VIC E 120 VAC N EU TR AL 2003 ECC MASTER P N 00 00855 000 HIGH H IGH LOW LOW COMP C OMP A C 2 U NIT A C1 UN IT RE LAYS BU ILT INTO A C U NIT R EL AYS B UILT IN TO A C UN IT WH ITE WHITE R ED 12 V OLT POWER BROWN YELL OW WHT BLU B LU WHT BLK BL K TO FR ON T FUR NAC E TO R EAR FUR NA CE BL AC K PWR GR ND 1 20 VA C Line Sens or P N 8 7 0 10 01 01 2 B LK BL K w W H T Stripe C OMMON BL U COMMON BLU ...

Page 13: ...0026 Dual Furnace Thermostat 00 00856 _00 Control Module 11k 13 5k BTU air conditioner 00 00855 000 F97 00XX Current Sensor 01 00703 200 F93 2000 Temp Sensors 2 00 00569 000 F93 2021 Temp Probe Cables 2 10 ft 11 00417 010 F07 9713 Temp Probe Cables 2 31 ft 11 00417 031 F07 9711 Temp Probe Cables 2 50 ft 11 00417 050 F07 9712 Temp Probe Cables 2 65 ft 11 00417 065 F07 9714 Transfer Relay Delay 00 0...

Page 14: ...ELECTRONIC CLIMATE CONTROL II SERVICE MANUAL Part No s 00 00855 000 00 00856 000 Intellitec 1485 Jacobs Rd Deland FL 32724 386 738 7307 www Intellitec com 14 P N 53 00855 856 Rev C 080819 ...

Reviews: