Potter IntelliGen
™
Nitrogen Generators are designed to provide maintenance alerts that ensure the long life of the nitrogen
generator. These alerts also ensure that the unit runs at peak efficiency. The IntelliGen
™
Nitrogen Generator has an internal
maintenance timer that monitors how long the unit has been operating since it has been serviced. Normal scheduled maintenance
should be done every 1,000 compressor operating hours, or during the annual inspection of the unit, whichever comes first.
When the system needs maintenance, the amber maintenance light on the IntelliGen
™
Display will turn on. If connected to
the internet, you will receive an e-mail notification as well. If maintenance on the nitrogen generator is not done within 250
compressor operating hours, the nitrogen generator will show a trouble condition.
To reset the maintenance timer and get the maintenance alert to reset, go to the IntelliGen
™
Display.
1. Press "MAINT" on the IntelliGen
™
Display keypad.
2. Enter passcode "0000".
3. Select “Std. Nitrogen Maintenance” by moving the cursor and pressing "ENTER".
4. The menu will then display the count down hour log on the Maintenance Timer. Press "ENTER" on the keypad to clear
Maintenance Timer.
5. The amber Maintenance LED will turn off.
• Replace the activated carbon and coalescing filter elements.
•
Clean the air tank blow-down strainer screen.
• Replace the air compressor intake filter elements.
•
Change compressor oil (SAE-30).
•
Change Compressor oil (SAE-30)
• Check activated carbon and coalescing filter elements. Replace if necessary.
•
Check for unusual noise or vibration.
•
Clean all external parts of the compressor and motor.
•
Manually test safety relief valves.
•
Inspect system for leaks.
• Tighten fittings, nuts and screws as required.
•
Check the pressure settings.
•
Check the nitrogen purity using Portable Nitrogen Analyzer. It should be 98.0% or greater.
Maintenance and Part Replacements
CAUTION
All pressure must be relieved from the entire nitrogen generator system BEFORE servicing. To avoid system damage
and/or personal injury, the nitrogen generator should be isolated from the sprinkler system and the generator system fully
depressurized before any maintenance or service is performed. All maintenance and troubleshooting activities for the Potter
Nitrogen Generator should be performed by qualified personnel using reasonable care. Before servicing, isolate all risers by
closing all Nitrogen Air Maintenance Device valves and relieving all system pressure from the Potter Nitrogen Generator.
Failure to do so could result in serious injury or death. Ensure power is turned off at the electrical disconnect.
Scheduled Maintenance - 1,000 Compressor Operating Hours:
Break In Oil Change - First 100 Hours:
Annual Inspection:
Part Number
Description
0090207
KIT-FILTER ELEMENT REPLACEMENT INS-1500/2000
0090212
KIT-MAINTENANCE OIL / AIR FILTER COMPRESSOR INTAKE INS-1500/2000
1119504
PORTABLE NITROGEN ANALYZER
1119590
MEMBRANE SEPARATOR-INS 1000/1500
1119594
MEMBRANE SEPARATOR-INS 2000
1119601
COMPRESSOR-7 1/2 HP, 200-208VAC 3PH 60HZ (INS-1500/2000)
1119602
COMPRESSOR-7 1/2 HP, 230-240VAC 3PH 60HZ (INS-1500/2000)
1119603
COMPRESSOR-7 1/2 HP, 460-480VAC 3 PH 60HZ (INS-1500/2000)