12
INS-1500 & INS-2000 • 5403646 • REV F • 04/19
1. On arrival, do a full inspection by checking all packages and crates in the shipment for damage.
2.
If damage is found, sign for the damage or refuse the shipment. Contact the carrier immediately and file a shipping damage
claim with the carrier.
3. Check to ensure all components are contained and no visible damage has occurred during shipping.
•
Nitrogen Cabinet
•
IntelliGen
™
Display
•
Tank Mounted Air Compressor
•
Nitrogen Tank
4. Each nitrogen generator requires a minimum of one Nitrogen Air Maintenance Device (NAMD) and one Nitrogen Purge
Valve per sprinkler system. Check to see these components have arrived.
•
Nitrogen Air Maintenance Device (one per riser) (NAMD #1119660)
•
Nitrogen Purge Valve (NGP-SPV #1119784) or (INS-PV #1119478)
•
Portable Nitrogen Analyzer (one per job) (PNA #1119504)
5. Find a location for the nitrogen generator to be installed meeting these requirements:
•
Dry, clean and well-ventilated
•
Dimensions 70” X 31” X 13” (H x W x D) for cabinet, 53” X 20” (H x W) for nitrogen tank and 74” X 37” X 24" (H x
W x D) for tank mounted air compressor.
•
Ambient temperatures above 50º F at all times
•
Access to front for service
• Conveniently located near fire sprinkler system connections
•
Conveniently located near a drain
•
Near a dedicated electrical circuit with an electrical disconnect switch
Installation of the Nitrogen Generator
Fig. 6
6. Typical installation layout of the INS-1500/2000. See Fig. 6.
7.5HP AIR COMPRESSOR
IntelliGen DISPLAY
MAIN POWER OFF/ON
1/2" OR 3/4" ELECTRICAL
CONDUIT CONNECTION
1/2" KNOCKOUT FOR
P-LINK AND NETWORK
CABLE CONNECTION
NITROGEN AIR
MAINTENENCE DEVICE
60 GALLON
NITROGEN STORAGE TANK
DRAIN CONNECTION
PIPE TO FLOOR DRAIN USING PROVIDED
3/8" OD X 10' PUSH TO CONNECT TUBE
12" LONG FLEXIBLE
STAINLESS STEEL HOSE
1/2" MNPT COMPRESSED AIR
OUTLET CONNECTION
DRAIN CONNECTION
PIPE TO FLOOR DRAIN USING PROVIDED
1/4" OD X 10' PUSH TO CONNECT TUBE