background image

 

- 8 - 

 

2.3

 

ELECTRICAL CONNECTIONS  

1.

 

Verify/configure the input power.  The input power requirement is listed on the tag on 
the transmitter enclosure.  Be sure the input power source to be used is properly selected 
in  the  unit.  Unless  specifically  ordered  otherwise,  the  input  power  requirements  are 
24±2Vdc @ 0.25A typical.  

Do not apply power to the instrument until all connections 

are made and all enclosure covers are in place. 

 

!!  CAUTION

: Use supply wires suitable for 10̊C above ambient. 

!!  CAUTION

: The output signal is isolated from the power ground.  If you 

are connecting the 4-20 mA output to an isolated input device, it may be 
advisable to ground the incoming signal at the input device. Refer to the input 
device manufacturer’s recommendations. 

 
2.  Check  the  analog  output  configuration  of  the  transmitter  and  your  input  device.  

Typically  the  4-20  mA  output  is  configured  to  actively  supply  the  loop  current.    If 
another  output  type  has  been  ordered  it  will  be  listed  in  SECTION  6.3  -  SPECIAL 
INSTRUCTIONS.  (Active: current to the loop is sourced by transmitter.  Passive: output 
receiver sources the current.) 

 
3.  Pull wires through the conduit. Wire for the power connection must be no smaller than 

22 gauge or as required by applicable local or company wiring codes.  After pulling the 
wire, pot the conduit or wires near the enclosure if there is any possibility of water from 
condensation or spray entering the enclosure through the conduit.  With the “blind” 
option, a single cable that contains two internal twisted-shielded pairs is included and is 
used for both the input power and the output signal. 

 

!! WARNING

:  The transmitter unit is not protected against condensed liquid water 

inside the enclosure.  Be sure conduit interfaces are dry or sealed at the instrument to 
prevent condensation that may be present in conduit lines from entering the enclosure. 

 

4.  Make wiring connections.  

Power should be off at this time

.   

 

!! WARNING

:  Verify the wiring.  The equipment can be permanently damaged if not 

wired as instructed in this manual.   Applicable code requirements should also be met 
when connecting the conduit to the enclosure. 

 

5.  Secure the enclosure cover(s).  Make sure it is tight enough to make a good seal against the 

gasket if supplied, and ensure all other enclosure openings are completely watertight 

 

6.  Connect  functional  ground.  To assure EMC  compliance, ground the sensor and the 

windowed enclosure (if applicable) to earth ground using 3/8" wide ground straps or 
equivalent.  EMC compliance testing has been successfully completed using these straps 
and ungrounded tubing. However, if the flow tubing and electrical conduits are reliably 
grounded by other means, these straps may not be necessary.  These straps may also be 
required  to  supply  a  reliable  or  redundant  ground  path  for  operation  in  hazardous 
locations.  Consult your plant’s safety engineer. 

Summary of Contents for Rheotherm 210

Page 1: ...TION 9 3 3 OPERATIONAL INTERFACES 9 3 4 OUTPUT CURVE 10 4 MAINTENANCE 11 4 1 GENERAL MAINTENANCE 11 4 2 FLOW CALIBRATION ADJUSTMENT 11 4 3 SPARE PARTS 11 4 4 TROUBLESHOOTING 11 5 CUSTOMER SERVICE 13 5...

Page 2: ...have been thus defective this warranty being expressly in lieu of all other warranties express or implied and all other obligation or liabilities on Intek s part The purchaser will assume all respons...

Page 3: ...truments are Nonintrusive flow measurement For pipe sizes from 1 16 to 1 4 inch flow sensing can be done from outside the flow tube Chemical compatibility The wetted surface s can be any of a number o...

Page 4: ...on notation indicates that failure to execute the accompanying instructions may cause the instrument or external equipment to malfunction WARNING A warning indicates that failure to execute the accomp...

Page 5: ...ent short term for the sensor and adjacent line See SECTION 2 INSTALLATION These instructions cover installation calibration and maintenance of Rheotherm meters in standard configurations Any special...

Page 6: ...langes whichever is appropriate Care must be taken not to transmit a twisting force through the sensor s midsection The TU and TUL sensors whether flanged or not must not be used to pull other piping...

Page 7: ...on the screen The cover should only be opened in safe environments In this configuration the Flow Controller outputs a calibrated analog flow rate signal 0 5V 0 10V 4 20mA over the blue and white wir...

Page 8: ...ure if there is any possibility of water from condensation or spray entering the enclosure through the conduit With the blind option a single cable that contains two internal twisted shielded pairs is...

Page 9: ...changed a factory recalibration will be required 3 3 OPERATIONAL INTERFACES By default Rheotherm Flow Controllers include a 4 20 mA analog output flow signal When used in the optional external setpoin...

Page 10: ...l up or down Instruments with an FCE in the serial number use a 0 5v analog input to control the setpoint This signal is sent over the blue and white wires with blue as ground and white as the signal...

Page 11: ...ock from sensor place a wrench on the sensor endcap hex This will ensure torsion is not transmitted down the flow tube Placing stress on the flow tube can cause damage 4 2 FLOW CALIBRATION ADJUSTMENT...

Page 12: ...r Low range Flow indication varies with flow setpoint but is not stable 1 Fluid temperature not stable 2 Fluid mixture not properly blended 3 Gas mixed with liquid 4 Flow not fully developed 1 Tune te...

Page 13: ...vide as complete a description as possible of the problems encountered 5 3 FACTORY AND FIELD SERVICE If you request field service Intek has experienced engineers available to meet your needs Many of t...

Page 14: ...14 6 CUSTOM INFORMATION 6 1 UNIT IDENTIFICATION 6 2 CONFIGURATION 6 3 SPECIAL INSTRUCTIONS...

Reviews: