background image

 

- 6 - 

 

2

 

INSTALLATION 

2.1

 

SENSOR  

!!  CAUTION:

  All sensors have a directional arrow on the tag and/or 

etched into a metal part. All flow controllers are assembled with the valve 
on the downstream side. Before installing a sensor, please note proper 
flow direction.  This is critical to instrument performance. 

 
The sensor style supplied with your meter is listed in the model code number in SECTION 6.  Proper 
installation  of  the  sensor  is  necessary  for  achieving  accuracy  and  repeatability.    Installation 
suggestions for each type of standard sensor are given here and instrument detail drawings may be 
included in the appendix.  For custom sensor installations, refer to CUSTOM INFORMATION — 
SECTION 6. 
 
Be sure wetted surfaces are clean before installing.  If cleaning is needed, use non-residue solvent 
and wipe dry.  Some sensor terminations are enclosed in an aluminum housing and if it is not sealed 
properly can easily be damaged by moisture and corrosion.  Make sure the lid is tightly sealed and 
the gasket, if supplied, is in place. 

 

TU or TUL (nonintrusive) — capillary (C), 

1

/

16

, and 

1

/

8

 TU or TUL sensors particularly require 

special care in handling and installing to avoid damage to sensor tube and tube stubs.

 

 
!!  WARNING:

  TU and TUL sensors are made with thin-walled tubing — use care 

when installing. 
 
All TU and TUL sensors should have a straight line input sections, typically 20 pipe diameters.  If 
installed vertically, the direction of flow should be up through the sensor.  Connection in the line is 
via compression fittings, hose with clamp, threaded fittings or flanges, whichever is appropriate.  
Care must be taken not to transmit a twisting force through the sensor’s midsection.  The TU and 
TUL sensors, whether flanged or not, must not be used to pull other piping together or to make up 
angular mismatch of fittings.  The sensor mounted enclosure should never be rotated for any reason. 
 
TU and TUL sensors 1/16 or smaller may be sleeved with a tube for added support.  Connection 
should always be made to the flow tube, as there is no assured seal between the flow tube and the 
sleeve. 
 
Fluid temperatures other than ambient require special attention.  Thermal gradients from one end of 
the  sensor  to  the  other,  as  well  as  along  the  radius  of  the  connection  pipe,  are  undesirable.  
Therefore, effective insulation should be installed around the  inlet  and outlet  straight line runs.  
Gradients which may exist in the line further up stream can be removed if an insulated elbow is 
installed in the line prior to entering the straight line portion of the plumbing.  Metallic support 
braces for the sensor or adjoining plumbing can act as a heat sink and cause indication errors in high 
temperature applications.  The support braces should be thermally isolated from the line to avoid 
heat loss effects. The adjustable valve is attached to the downstream side of the sensor. It generates 
heat when used and should not be insulated. 
 
Flow stream conditioning must also be considered to maximize meter performance.  Avoid upstream 
protrusions and short distance straight runs. Flow pulsations, such as those created by  metering 
pumps, may cause the instrument to differ from the factory calibration. Furthermore, if the flow is 
varied by stroke and by pump speed adjustment, the indication will most likely be non-repeatable.  If 

Summary of Contents for Rheotherm 210

Page 1: ...TION 9 3 3 OPERATIONAL INTERFACES 9 3 4 OUTPUT CURVE 10 4 MAINTENANCE 11 4 1 GENERAL MAINTENANCE 11 4 2 FLOW CALIBRATION ADJUSTMENT 11 4 3 SPARE PARTS 11 4 4 TROUBLESHOOTING 11 5 CUSTOMER SERVICE 13 5...

Page 2: ...have been thus defective this warranty being expressly in lieu of all other warranties express or implied and all other obligation or liabilities on Intek s part The purchaser will assume all respons...

Page 3: ...truments are Nonintrusive flow measurement For pipe sizes from 1 16 to 1 4 inch flow sensing can be done from outside the flow tube Chemical compatibility The wetted surface s can be any of a number o...

Page 4: ...on notation indicates that failure to execute the accompanying instructions may cause the instrument or external equipment to malfunction WARNING A warning indicates that failure to execute the accomp...

Page 5: ...ent short term for the sensor and adjacent line See SECTION 2 INSTALLATION These instructions cover installation calibration and maintenance of Rheotherm meters in standard configurations Any special...

Page 6: ...langes whichever is appropriate Care must be taken not to transmit a twisting force through the sensor s midsection The TU and TUL sensors whether flanged or not must not be used to pull other piping...

Page 7: ...on the screen The cover should only be opened in safe environments In this configuration the Flow Controller outputs a calibrated analog flow rate signal 0 5V 0 10V 4 20mA over the blue and white wir...

Page 8: ...ure if there is any possibility of water from condensation or spray entering the enclosure through the conduit With the blind option a single cable that contains two internal twisted shielded pairs is...

Page 9: ...changed a factory recalibration will be required 3 3 OPERATIONAL INTERFACES By default Rheotherm Flow Controllers include a 4 20 mA analog output flow signal When used in the optional external setpoin...

Page 10: ...l up or down Instruments with an FCE in the serial number use a 0 5v analog input to control the setpoint This signal is sent over the blue and white wires with blue as ground and white as the signal...

Page 11: ...ock from sensor place a wrench on the sensor endcap hex This will ensure torsion is not transmitted down the flow tube Placing stress on the flow tube can cause damage 4 2 FLOW CALIBRATION ADJUSTMENT...

Page 12: ...r Low range Flow indication varies with flow setpoint but is not stable 1 Fluid temperature not stable 2 Fluid mixture not properly blended 3 Gas mixed with liquid 4 Flow not fully developed 1 Tune te...

Page 13: ...vide as complete a description as possible of the problems encountered 5 3 FACTORY AND FIELD SERVICE If you request field service Intek has experienced engineers available to meet your needs Many of t...

Page 14: ...14 6 CUSTOM INFORMATION 6 1 UNIT IDENTIFICATION 6 2 CONFIGURATION 6 3 SPECIAL INSTRUCTIONS...

Reviews: