Analogue Input No.1
+
-
Analogue Input No.2
+
-
Analogue Input No.3
+
-
+
-
+
-
+
-
+
-
+
Note 1.
This configuration reverses the logic so when
the PLC digital output is off, the 2100-A
16
is on.
Note 2.
With 1k resistor, up to four 2100-A
16
can be
connected in this configuration, provided the
open collector outputs can handle the load.
Note 3.
Each digital input draws 10mA at 24Vdc.
Note 4.
All cables must be screened, and the screens
earthed at one end only.
Note 5.
For Clock/Reset Channel Selection DO NOT
connect PLC outputs 3 and 4 to DI 3 and DI 4
of the 2100-A
16
.
Important:
Do not use the 2100-A
16
power supply to
power up any transmitter or other equipment. An external
power supply must be used for this purpose. The 20V
supply is for the 2100A
16
Digital Inputs/Outputs only.
* For PLC RTX, CLOCK & RESET Channel Selection
refer to Section D, Mode 3.
* For PLC RTX, Bin Channel Selection refer to Section
D, Mode 4.
24Vdc Regulated
Power Supply
PLC
Output
Module
(Note 5)
Open Collector
Output No.1
Open Collector
Output No.2
Open Collector
Output No.3
Open Collector
Output No.4
PLC Input
Module
2100-A
16
Used as an Intelligent Multiplexer.
Connection Example 3.
Connection of a 2100-A
16
to a PLC with open collectors commoned to 0V of an external power supply.
1k
1k
1k
1k
Note 1.
This configuration reverses the logic so when
the PLC digital output is off, the 2100-A
16
is on.
Note 2.
For Clock/Reset Channel Selection the
resistors = 1k . Up to four 2100-A
16
can be
connected in this configuration provided the
open collectors can handle the load. For
Binary Channel Selection the resistor =
2.2k . Up to two 2100-A
16
can be connected
in this configuration provided the open
collectors can handle the load.
Note 3.
All cables must be screened, and the screens
earthed at one end only.
Note 4.
For Clock/Reset Channel Selection DO NOT
connect PLC outputs 3 and 4 to DI 3 and DI 4
of the 2100-A
16
.
Important:
Do not use the 2100-A
16
power supply to power
up any transmitter or other equipment. An external power
supply must be used for this purpose. The 20V supply is
for the 2100A
16
Digital Inputs/Outputs only.
* For PLC RTX, CLOCK & RESET Channel Selection
refer to Section D, Mode 3.
* For PLC RTX, Bin Channel Selection refer to Section
D, Mode 4.
PLC Input
Module
-
Analogue Input No.1
+
-
Analogue Input No.2
+
-
Analogue Input No.3
+
-
+
-
+
-
+
-
+
PLC
Output
Module
(Note 4)
Open Collector
Output No.1
Open Collector
Output No.2
Open Collector
Output No.3
Open Collector
Output No.4
2.2k
2.2k
2.2k
2.2k
Resistor Values refer Note 2.
Connection Example 4.
Connection of a 2100-A
16
to a PLC with open collectors, commoned to the COM of the first 2100-A
16
.
First
2100-A
16
60 AO COM
61 AO 1
54 DI COM
55 DI 1
56 DI 2
57 DI 3
58 DI 4
Second
2100-A
16
60 AO COM
61 AO 1
54 DI COM
55 DI 1
56 DI 2
57 DI 3
58 DI 4
Third
2100-A
16
60 AO COM
61 AO 1
54 DI COM
55 DI 1
56 DI 2
57 DI 3
58 DI 4
First
2100-A
16
49 20V
60 AO COM
61 AO 1
54 DI COM
55 DI 1
56 DI 2
57 DI 3
58 DI 4
Second
2100-A
16
60 AO COM
61 AO 1
54 DI COM
55 DI 1
56 DI 2
57 DI 3
58 DI 4
Third
2100-A
16
60 AO COM
61 AO 1
54 DI COM
55 DI 1
56 DI 2
57 DI 3
58 DI 4
14.02-19