14.02-14

OUTSTATION LAYOUT.

OUTSTATION LAYOUT.

2-Wire RS485 Serial Connections.

4-Wire RS422 Serial Connections.

4
6
3
9
5

Shimaden FP21

with RS422 option

4
6
3
9
5

Shimaden SR25/253

with RS422 option

25
24
23
22
21

Shimaden SR53/54

with RS422 option

5
4
3
2
1

Shimaden SR73A/74A

with RS422 option

To other INTECH MICRO Remote

Stations & Shimaden Controllers etc.

End of Data

Hi-way

Junction Box.

TWISTED

P

AIR

IN-2000-AI

Remote Station.

2100-AO

Remote Station.

IN-2000-DI

Remote Station.

2100-A

4

Remote Station.

21

20

23

22

36

35

38

37

70

71

72

73

74

2100-D

Remote Station.

70

71

72

73

74

IN-2000-DO

Remote Station.

26

25

28

27

21
22

1

Shimaden SD20

with RS485 option.

23
22

21

Shimaden SR53/54
with RS485 option.

3
2

1

Shimaden SR73A/74A

with RS485 option.

To other INTECH MICRO

Remote Stations &

Shimaden Controllers etc.

Resistor = 1k .

2100-A

16

Remote Station.

2100-A

4

Remote Station.

2100-AO

Remote Station.

70

71

74

70

71

74

70

71

74

Notes:
(i) RS485 can only be used with software release Ver. 4.02 onwards.
(ii) RS485 Data Hi-way is not compatible with RS422 Data Hi-way devices

such as IN-2000-AI, IN-2000-AO, IN-2000-DI, IN-2000-DO, FP21,
SR25, etc. Use a 2100-4S to interface an RS485 Data Hi-way to an
existing RS422 Data Hi-way

RS232:

2100-IS convertor is not required to connect the 2100-232
directly to a PC. Use the RS232 kit to connect the 2100-232
directly to a PC. The PC requires one RS232 port per 2100.

RS485:

If the outstation is using RS485, it cannot be connected to the same
data hi-way as an outstations using RS422. In the ‘programming’
box, set the ‘TX  delay’ box to 20. Set the Dip switches on the
2100-IS and the jumpers on the 2100 for RS485 operation.

24
23
21
22
1

Shimaden SD20

with RS422 option

3
9

5

Shimaden SR253

with RS485 option.

2100-A

16

Remote Station.

70

71

72

73

74

IMPORTANT:
(i) All cables must be

screened.

(ii) All screens must

be connected
together.

(iii) The screen must

not be earthed at
any point.

IMPORTANT:
(i) All cables must be

screened.

(ii) All screens must

be connected
together.

(iii) The screen must

not be earthed at
any point.

2100-D

Remote Station.

70

71

74

70

71

72

73

74

DO NOT GUESS TX OR RX CONNECTIONS. FOLLOW THE TERMINAL NUMBERS IN THE SERIAL CONNECTION DIAGRAMS EXACTLY.

 

-

 +

SG

Shimaden SR80 Series

with RS485 option.

Shimaden SR90 Series

with RS485 option.

SR82

18

17

16

SR83

25

24

23

SR84

22

21

1

 

-

 +

SG

SR91

12

11

1

SR92,93,94

3

2

1

Resistor = 1k .

TWISTED

P

AIR

TWISTED

P

AIR

TWISTED

P

AIR

TWISTED

P

AIR

TWISTED

P

AIR

End of Data

Hi-way

Junction Box.

74           71  70

Terminal Numbers

COM

                TX+   TX-

RS485 DATA HI-WAY.

CABLE POLARITY

MUST BE OBSERVED

RS422 DATA HI-WAY.

CABLE POLARITY

MUST BE OBSERVED

RS485 DATA HI-WAY.

CABLE POLARITY

MUST BE OBSERVED

RS422 DATA HI-WAY.

CABLE POLARITY

MUST BE OBSERVED

74 73 72 71 70

Terminal Numbers

com 

  RX+   RX-   TX+    TX-

74           71  70

COM

                TX+   TX-

74 73 72 71 70

com 

  RX+   RX-   TX+    TX-

2100-NET

10/100 Ethernet to
RS422/485 Converter.

COMPUTER

PLC

2100-IS/NS

RS232 to RS422/485

Converter/Isolator.

2100-NET

10/100 Ethernet to
RS422/485 Converter.

RS232

ETHERNET

COMPUTER

PLC

2100-IS/NS

RS232 to RS422/485

Converter/Isolator.

The 2100-IS and 2100-NET are

designed to connect to seperate data

hi-ways and connect to the same

SCADA PC as per the diagram.

RS232

ETHERNET

The 2100-IS and 2100-NET are

designed to connect to seperate data

hi-ways and connect to the same

SCADA PC as per the diagram.

70
71
72
73
74

2100-4S RS422

to RS485 Converter

70
71

74

RS485

Only one converter to be

connected to any one data hiway.

OR

Only one converter to be

connected to any one data hiway.

OR

Summary of Contents for 2100-A16

Page 1: ...INTECH Micro 2100 A16 REV 1 3 Installation Guide 14 01 1 TECHNOLOGY QUALITY A W A RD ISO9001 E G ISTE R RE D M ANU A T U R E R C F Z985...

Page 2: ...nnection Page 12 2100 ME Memory Expansion Page 12 2100 R2 Relay Expansion Page 13 RS485 Serial Connection Page 14 RS422 Serial Connection Page 14 RS232 Serial Connection Page 15 RS232 Radio Modem Seri...

Page 3: ...asy to Install z z z z z Compact DIN Rail Mount Enclosure Ordering Information 2100 A16 Rev1 X Standard Unit Analogue Inputs Pt100 0 100C Analogue Outputs 4 20mA RS485 Comms 85 264Vac dc Power Supply...

Page 4: ...t note 3 Mineral Insulated Thermocouples With Isolated Junction Essential Cold Junction Comp 0 60C CJC Drift 0 03C C Typical for Input 1 Refer to notes under 2100 A16 Input Connection Diagram for T C...

Page 5: ...for 1min General Specifications Unless otherwise stated in other input specifications Accurate to 0 1 FSO Typical Linearity Repeatability 0 1 FSO Typical Channel Separation 0 1 FSO Typical Ambient Dri...

Page 6: ...B A B B A B B A B B A B B A B B A B B AO COM AO 1 AO 2 Relay COM Relay 1 Relay 2 DI COM DI 1 DI 2 DI 3 DI 4 H3 EXPANSION CONNECTOR J9 J10 J11 J12 J13 J14 J15 J16 J1 J2 J3 J4 J5 J6 J7 J8 H1 SUPPLY VOL...

Page 7: ...i e c e r s i n o i t a t S n e h w e v i t c A X T a t a d l a i r e s g n i t t i m s n a r t s i n o i t a t S n e h w y l n o e v i t c A E X T a t a d t i m s n a r t o t y d a e r s i n o i t a...

Page 8: ...sing a clean voltage free field contact Note 4 All cables must be screened and the screens earthed at one end only Note 5 Voltage free contact values must be brought in through tags in the Scada Softw...

Page 9: ...6 The mounting orientation of the 2100 A16 eg vertical or horizontal affects the CJC accuracy of different inputs The affects are more noticeable on small temperature ranges For example mounting the 2...

Page 10: ...relay can be configured for a Normally ON or Normally OFF output state E g for fail safe operation The Normally ON OFF settings are retained in software on power down but the relays are de energized...

Page 11: ...1 61 AO 2 62 2 1 5 4 8 7 Fourth 2100 M 51 COM 53 Iout 60 CS COM 61 RESET 62 CLOCK 11 10 EXPO 3 26 COM 28 Iout 29 CS COM 30 RESET 31 CLOCK OR The analogue output mode is set in the Station Advanced Di...

Page 12: ...Protective enclosure only to be opened by qualified personnel Remove ALL power sources before removing protective cover 14 02 12 2100 A16 Connection Example Diagram for Using the 2100 RL2 2 Relay Slav...

Page 13: ...nt device Both units must be powered and unpowered at the same time to prevent indeterminate relay states 2100 A16 Rev1 3 Relay Output Expansion Using 2100 R2 Relay Expansion Output relay expansion is...

Page 14: ...ration 24 23 21 22 1 Shimaden SD20 with RS422 option 3 9 5 Shimaden SR253 with RS485 option 2100 A16 Remote Station 70 71 72 73 74 IMPORTANT i All cables must be screened ii All screens must be connec...

Page 15: ...me a unique station number before using the programme setup button in the Scada Software Requires Microscan Version 4 02 onwards For detailed programming info refer to Programming 2100 Series Remote S...

Page 16: ...TX delay is zero the data is sent immediately upon receiving a command RX The period is specified in TXE units of 2 5ms i e 10units 25ms TX TXE delay TX delay 2100 A16 Delay Settings Table Mode 3 210...

Page 17: ...e Scada COMMS allowing a PLC to read back data that the Scada will be showing Note 8 Digital inputs and digital outputs are not available in this mode 2100 A16 58 57 56 55 54 62 61 60 48 49 Bin SWITCH...

Page 18: ...as an Intelligent Multiplexer Connection Example 1 Connection of a 2100 A16 to a PLC with open collectors commoned to 24V of an external power supply PLC Input Module Analogue Input No 1 Analogue Inp...

Page 19: ...can be connected in this configuration provided the open collectors can handle the load For Binary Channel Selection the resistor 2 2k Up to two 2100 A16 can be connected in this configuration provid...

Page 20: ...ithout notification 2100 A16 Rev 1 PLC RTX Fail Safe System The PLC uses one channel of the 2100 A16 to verify that the A16 is reading the channel correctly AO1 is working and the clock and reset BCD...

Page 21: ...umper Settings Note 2 The retransmission modes of AO1 AO2 canbeusedwhentheModbusRTUprotocol is used Note 3 Rev 1 3 ONLY s e s s e r d d A l i o C l i o C x x 0 0 0 t u p u O l i o C x x 0 0 0 t u p u...

Page 22: ...0 0 3 F F F 0 0 0 t i B 2 1 6 1 t u p n I 3 x u M 7 3 0 0 3 s d r o W 2 4 5 7 E E E I 1 1 t u p n I 7 9 0 0 3 F F F 0 0 0 t i B 2 1 1 t u p n I 4 x u M 9 3 0 0 3 s d r o W 2 4 5 7 E E E I 2 1 t u p n...

Page 23: ...en inputs is 4 channels second Channels that are not scanned can be disabled via the station programming dialog boxes To speed up operation for multiplexer mode set the Scan Mode on the advanced dialo...

Page 24: ...the sockets operations You may need to open the IP address and port numbers for the commands to go through We have found problems with Nortons system Works 2003 and found it necessary to disable emai...

Page 25: ...have minimum free air space of 20mm Foreign matter must not enter or block the draft holes 3 Do not subject to vibration or excess temperature or humidity variations 4 Avoid mounting in cabinets with...

Page 26: ...lve motors this may help to stabilise the input signal Use caution when doing this as unless the inputs are at the same potential large earth currents will flow through the 0V rail causing errors on A...

Page 27: ...2 Once the above conditions have been met and the wiring checked apply power to the 2100 A16 the loops sensors 2100 Rs and 2100 Ms Allow a 5 minute warm up period longer for thermocouples refer to Inp...

Page 28: ...not be air or gas tight 3 Check cables entering the RTD sensor head Thermocouple Inputs 1 Repeat 4 of commissioning Do it regularly at least once a month 2 Replace defective protection tubes even if...