14.02-15
2100-A
16
RS232 Serial Connection.
The 2100-A16 with RS232 comes complete with:
z
z
z
z
z
1 x 5m RJ11 RS232 Cable. (2, 10 & 15m available.)
z
z
z
z
z
1 x 9 Pin D-type Connector. (25 pin D-type available.)
z
z
z
z
z
USB to RS232 convertor available. Part No. BF-810.
Location of RJ11 Socket on 2100-A
16
Series.
2100-RS232 Kit-Omron
RS232 Kit for Omron PLC. Includes 2m cable & 9 pin D-type connector.
Installation.
Plug one end of the RS232 Comms cable into the RS232 RJ11
Socket on the 2100 Module. Plug the other end into either the 9 or
25 pin D-type connector. (Check for the correct D-type connector
on the computer (or Omron PLC) RS232 port being used.) For
further software and hardware information, Refer to the Microscan
Manual ‘Programming the 2100 Series Remote Station.’
2100-A
16
RS232 Radio Modem Serial Connection.
Note: The ‘2100-RS232-Radio’ 9 pin D connector differs from the
2100-RS232 9 pin D supplied, and must be ordered separately.
It can be exchanged at no charge for the 9 pin and 25 pin D
connectors supplied with the 2100-RS232 Remote Station.
1.
Refer to Installation paragraph above.
2.
Fit the ‘2100-RS232-Radio’ 9 pin D connector between the
Radio end of the RS232 comms cable, and the Radio. This
connector will work with most types of radio, but this is not
guaranteed. Pin2=TX; Pin3=RX; Pin5=GND; Pin7=RTS.
3.
Refer to ‘H2 Comms Settings.’ to jumper as per RS232 Radio.
4.
Refer to radio manual for hardware handshaking settings for TX control. TXE & TX delay may need to be altered
in the Scada Station Advanced Dialog box to suit the radio. Best case TX speed is one transmission per second.
(Depends on Radio.) Default settings are: TXE = 25ms; TX = 0ms.
5.
If using more than one station at a remote radio site,
2100-RS422
Remote Stations with a 2100-IS with an adaptor
kit must be used. (Do not use 2100-RS485.) Refer to 2100-IS installation Guide.
2100-A
16
Station Number Programming and Serial Number.
Important:
When commissioning remote stations, you must programme a unique station number before using the
programme setup button in the Scada Software. Requires Microscan Version 4.02 onwards.
For detailed programming info, refer to ‘Programming 2100-Series Remote Station’ in the Microscan Manual.
1.
Close the Microscan Scada down and turn the power off to the 2100 422/485 converter. Connect the new Remote
Station, referring to ‘
Wiring and Installation
’ and ‘
Commissioning
’
2.
Turn power back on to the 2100 422/485 converter, and start the ‘Setup Manager’ in the Microscan Scada.
3.
Select ‘Recorder Setup’, or ‘Tag Setup’.
4.
Select ’Program Address’. (Located in ‘Station Programming Panel’, at the bottom right of the window.
5.
Enter the 2100-A
16
serial number. (Written both on the 2100-A
16
cover and the circuit board behind the power
supply terminals. 80, 81 & 82. If the cover has been removed, the number on the circuit board is always correct.
Replace with the correct cover to avoid future confusion.) Then enter the desired station number.
6.
Select ‘Program’. The station number will now be stored in 2100-A
16
permanent memory.
7.
A new station number will be created on the outstation map. This is ready for connection to tags or lines.
8.
Restart the Microscan Scada.
2100-A
16
Station Software Programming.
*Requires Microscan Version 4.02 onwards.
1.
If the system is already running, close the Scada down. Start the ‘Setup Manager’.
2.
Select ‘Recorder Setup’, or ‘Tag Setup’.
3.
Move to the required station number, using ‘next’ or ‘prev’ buttons.
4.
Select ‘Program Setup’. The serial number of the 2100-A
16
will be recalled automatically. The software recalls
the settings from the outstation, and displays them in the dialogue box.
5.
Enter the required options and select ‘Program’ to write the data to the station.
e
l
b
a
T
t
u
o
n
i
P
S
M
M
O
C
1
1
J
R
9
B
D
5
2
B
D
S
T
R
:
1
8
5
D
N
G
:
2
5
7
X
T
:
3
2
3
S
T
C
:
4
7
4
c
/
n
:
5
1
1
X
R
:
6
3
2
RS232 COMMS Hardware.
10VA
50/60Hz
85~264Vac/dc
23~90Vdc
10~28Vac/dc
H
M
L
COMMS
RS232
RS422
RS485
Ph N E
RS422/RS485 COMMS
COM TX TX RX RX
82 81 80
74 73 72 71 70
49 48 47
RS232 RJ11 Socket
Radio
RS232
2100-RS232
Remote station.
‘2100-RS232-Radio’
9 pin D-type connector.
Do Not cut RS232 Cable
to extend the length.