background image

 

 

HWHC-2100 Operation Manual   

CONFIDENTIAL

 

 

 

 

21 Harbor Park Dr. N, Port Washington, NY 11050 Phone: 516.626.72211 Fax: 516.626.7201 

                                                Fig.2 HWHC2100 Menu

 (V2.48)

 - 

Lower line of the display

 

VLV=16% ST=148° 
(VLV=16% RT=108°) 

 

SET OPER MODE 

 

NEW Mode=AUTO 

 

 

 

 

 

 

 

 

Rtn Temp=97.4°F 
(Sys Temp =145°) 

 

 

 

NEW Mode=M_OPEN 

 

 

 

 

 

 

 

 

OD Temp = 17.6° 

 

 

 

NEW Mode=M_CLOSE 

 

 

 

 

 

 

 

 

   PUMP ON 

 

 

 

NEW Mode=M_SET 

 

NEW MTGTemp=160°   

 

 

 

 

 

  VLV=15.8% 

 

 

 

NEW Mode=OFF 

 

 

 

 

 

 

 

 

10:25am Nov10'05 

 

 

 

         CACADCB 

 

 

 

 

 

 

 

 

Enter for more…

 

 

SETConfiguratin 

 

Password1:****** 

 

ST-TGT RtnT-NA

   

 

 

 

 

 

 

 

 

 

 

 

RtnT

-

TGT 

ST-NA 

 

 

 

 

 

 

 

 

 

 

 

 

ST-TGT 

RtnT-Ctf   

 

 

 

 

 

 

 

 

 

 

 

RtnT

-

TGT

 ST-Ctf   

 

 

 

 

 

HWHC2100/644 

 

 

 

         CACADCB 

 

 

 

 

 

 

 

 

VERSION V2.48 

 

SETUP 

 

Password1:****** 

 

SET D_Band

 

 

 

NEW D_Band =1.2° 

 

 

 

 

ST-TGT RtnT-NA

 

    

 

 

 

SET RtnCutOffTem   

NEW RCutOffTm=70°   

 

 

 

OD Temp = 17.6°F 

 

 

 

 

 

SET SysCutOffTem   

NEW SCutOffTm=70°   

 

 

 

Sys Temp=168.8°F 

 

 

 

 

   SET MaxWaterTemp   

NEW MaxWTmp=242° 

 

 

 

 

Ret Temp=45.8°F 

 

 

 

 

 

SET MinWaterTemp   

NEW MinWTmp=80° 

 

 

 

 

RtnCutOffTm=70°F 

 

 

 

 

 

SET PumpRunDelay   

NEW PumpRunD=2m 

 

 

 

 

SysCutOffTm=70°F 

 

 

 

  

 

SET HeatUp Time 

 

NEW HeatUpTm=30m 

 

 

 

 

cTGT Temp:196.4° 

 

 

 

          

 

SET Motor Pause 

 

NEW MrPause=20s 

 

 

 

 

D_Band = 1.2° 

 

 

 

 

 

SET VlvCtrl Type   

NEW CtrlTp=Curnt 

 

 

 

 

Motor Type = 2m 

 

 

 

 

 

SET Motor Type 

 

NEW MotorType=2m 

 

 

 

 

Motor Pause=20s  

 

 

 

 

 

SET TIME & DATE 

 

 

 

SET Minute 

 

NEWMinute=56 

VlvCtlType=Curnt 

 

 

 

 

 

SET Com.ID 

 

NEW Com.ID=3 

 

SET Hour 

 

NEW Hour=2PM 

D:Mild = 55°F 

 

 

 

         CACADCB 

 

 

 

 

 

SET Month 

 

NEW Month=02 

N:Mild = 45°F 

 

SET MAINTENANCE 

 

Password1:****** 

 

SET D:Mild  

 

NEW D:Mild=75° 

 

SET Date 

 

NEW Date=5 

N:Stbk = 10°F 

 

 

 

 

 

SET N:Mild 

 

NEW N:Mild=25° 

 

SET Year 

 

NEW Year=9 

MaxWaterTmp=242°F   

 

 

 

 

SET N:Stbk 

 

NEW N:Stbk=20° 

 

 

 

 

MinWaterTmp=180°F   

 

 

 

 

SET Heat Gain 

 

NEW HG=1:1.25 

 

 

 

 

PumpRunDelay=2m 

 

 

 

 

 

SET Compensator 

 

NEW Compens=0° 

 

 

 

 

Heat Gain=1:1.25 

 

 

 

 

 

SET Boost Span 

 

NEW BoostSpn=90m 

 

 

 

 

Compensator=0°F 

 

 

 

 

 

SET BoostAdvance    NEW Boost Adv=12°     

 

 

Boost Span=90m 

 

 

 

 

 

SET In D:CutOff 

 

NEW D:CutOff=70° 

 

 

 

 

BoostAdvance=12° 

 

 

 

 

 

SET In N:CutOff 

 

NEW N:CutOff=70° 

 

 

 

 

D:ICutOff = 70°F 

 

 

 

 

 

SET InDoorDBand 

 

NEW InDBand=4.5° 

 

 

 

 

N:ICutOff = 60°F 

 

 

 

 

 

SET Day Begin 

 

NEW Begin=5:00am    

 

 

 

InDrD_Band=2.5°F 

 

 

 

 

 

SET Day End 

 

NEW End=10:00pm 

 

 

 

 

InDoorTem=N/A 

 

 

 

 

 

SET Winter Begin    NEW Begin=Oct15 

 

 

 

 

Day Begin=5:00am 

 

 

 

 

 

SET Winter End 

 

NEW End=May 15 

 

 

 

 

Day End=10:00pm 

 

 

 

         DDBBCBA 

 

 

 

 

 

 

 

 

WintrBegin=Oct15 

 

SET CALIBRATE 

 

Password2:****** 

 

CAL OUT Temp 

 

NewODTAdj=0.2° 

 

 

 

 

WinterEnd=May 15 

 

 

 

 

 

CAL SYS Temp 

 

NewSysTAdj=0.1° 

 

 

 

 

HeatUp Time=30m 

 

 

 

 

 

CAL Rtn Temp 

 

NewRtnTAdj=0.0° 

 

 

 

 

Com.ID = 1 

 

 

 

 

 

CAL ValveClosePs   

NEW VlPsAdj 

 

 

 

 

 

 

 

HINT: If lost in the menu or a password is unknown - push ESC repeatedly, until the display shows VLV =xx%. You are now in the 

upper left corner of the menu table

 

Summary of Contents for HWHC2100

Page 1: ...temperature or condensate return temperature return water temperature HWHC2100 works as a standalone controller and can be connected to a Local Server which provides additional parameters adjustments...

Page 2: ...es or change settings The control keypad consists of four pushbuttons Escape Esc Down Up Enter Enter The keys are also marked with letters A B C D used to simplify the passwords memorizing During norm...

Page 3: ...ened or closed depending on the mode of the last operation as follows Operation Mode Valve Direction Status Information AUTO To Close Position Sync_C M_SET To Close Position Sync_C M_CLOSE To Close Po...

Page 4: ...d then one should enter a certain key sequence For convenience the passwords are coded as the sequence of letters e g DDBBCBA Starting point of the menu is the topmost item of the leftmost box current...

Page 5: ...s SET TIME DATE SET Minute NEWMinute 56 VlvCtlType Curnt SET Com ID NEW Com ID 3 SET Hour NEW Hour 2PM D Mild 55 F CACADCB SET Month NEW Month 02 N Mild 45 F SET MAINTENANCE Password1 SET D Mild NEW D...

Page 6: ...h between the different configuration one should press Up or Down keys Hitting Enter key accepts the new configuration Esc rejects and leaves the configuration unchanged 6 Modes of operation The upper...

Page 7: ...he NIGHT MILD WEATHER and NIGHT SETBACK parameters Please see an example in section 6 Notes The valve will be unconditionally set to 0 when Out Door Temperature achieves Day time Mild Weather Set Poin...

Page 8: ...Fig 3b With any of the ratios the colder it becomes outside the hotter the temperature of the system water On the both examples Compensator 0 and NIGHT SETBACK 0 Positive Compensator values shift the...

Page 9: ...g 4 illustrates effects of the Compensator on the control curve Range 40 F to 40 F with 1 step Default value is 0 F D Mild DAY MILD WEATHER The controller closes the valve completely when the outdoor...

Page 10: ...ens 10 Boost Span Morning boost time span The controller boosts heat only with AUTO mode in effect Range 0 30 60 90 120 minutes 0 means no boost or Vari Boost the length of the Boost time depends on t...

Page 11: ...d from host computer is higher than this set point and the time is between Day End and Day Begin then the valve will be closed completely N ICOFF state Range 40 to 80 F InDrD_Band Used along with In D...

Page 12: ...de of operation specify the appropriate time in seconds between the Valve Motor motion Normally this parameter is set at the system installation time Range 0 to 127 seconds with 1 second step Default...

Page 13: ...ration Valve position is 37 open System temperature is 144 F Morning Heat Up Calculated Target Temperature is 188 F AUTO 189 BOOST AUTO 140 D Mild AUTO 140 N Mild VLV 37 ST 155 VLV 12 ST 144 VLV_0 ST...

Page 14: ...ign will change to Mode of Operation OFF Mode of Operation M_SET SET 180 VLV 67 ST 123 Target Temperature is 180F Normal operation system temperature is 123F For the motorized valve controlled by rela...

Page 15: ...adjustment valve position would perform at the close position Pump would be turn off after period of time set by the Pump Run On set point System Temperature Sensor fails Initial Synchronization Valv...

Page 16: ...and shows actual reading of the temperature sensor ST zz x 3 The lower line of the display shows possible adjustment for example NewSysTAdj 0 2 4 Press Up or Down key to make the reading equal to the...

Page 17: ...MCI Transformer 4 06 7345 1 5 10 9 7 6 Pump1 2 Pump1 1 Pump2 1 Pump2 2 9 5 12 4 8 13 14 Terminals Board J1 1 2 3 H H 8 9 10 11 12 13 14 7 4 5 6 1 2 J2 1 2 Transformer 1 9 5 4 8 9 5 Motor Controls comm...